General Information
- Compatible with R-32 VRF air, water, and mini systems.
- The indoor unit features an integral condensate pump with a maximum 29" lift from the bottom of the unit, including a check valve and float switch that disables the indoor unit in the event of condensate overflow.
- The indoor unit includes a built-in Wi-Fi adapter as standard, enabling control and monitoring via the Samsung SmartThings app.
Construction
Constructed from insulated, galvanized steel.
Refrigerant System
- The heat exchanger features a mechanically bonded aluminum fin to copper tube design.
- Refrigerant flow is controlled by an electronic expansion valve at the indoor unit.
- The indoor unit includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Features Smart pressure control that adjusts fan speed based on ESP, delivering consistent heating and cooling power.
- Includes a smart-tuning function for optimized comfort, allowing users to adjust the fan CFM curve to increase or decrease airflow.
- Equipped with automatic air volume scanning for simple setup and optimized comfort settings for the occupant.
Controls
- Control wiring utilizes 2 X 16 AWG wire.
- The unit is operated via a wired remote controller, model VSTAT04P-1 (purchased separately).
- Supports dual set temperature when connected to supported controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- Provides external heat control functionality for configuring fan operation during auxiliary heat, defrost, and emergency heat modes (VSTAT10P-1 accessory required).
- Configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency heat functionality ensures the system continues controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
- Features an Emergency Temperature Output (ETO) function: when the indoor unit is in an error status or when room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like a status light, warning lamp, or buzzer).
Specifications
Specification | Value |
---|---|
Model | VMDD012S6-5P |
Indoor Unit Model Number | VMDD012S6-5P |
Nominal Capacity Cooling (Btu/h) | 12,000 |
Nominal Capacity Heating (Btu/h) | 13,500 |
Voltage | 1/208-230/60 Hz |
Operating Current (max.) Cooling (A) | 0.30 |
Operating Current (max.) Heating (A) | 0.30 |
MCA (A) | 0.91 |
MOP (A) | 15 |
Evaporator Fan Type | BLDC (1) With Sirocco Fan (2) |
Evaporator Fan Consumption (Watts) | 153 |
Evaporator Fan External Static Pressure Standard ("WC) | 0.04 |
Evaporator Fan External Static Pressure Min. / Max. ("WC) | 0 / 0.59 |
Airflow Air Volume (L/M/H/Turbo) Cooling (CFM) | 300 / 353 / 424 |
Airflow Air Volume (L/M/H/Turbo) Heating (CFM) | 300 / 353 / 424 |
Refrigerant Type | R-32 |
Refrigerant A2L Leak Detection | Integral |
Pipe Connections High side | 1/4 |
Pipe Connections Low side | 1/2 |
Condensate Pipe Connection | 1 1/4 in. OD, 1 in. ID |
Dimensions W X H X D (In.) | 33 7/16 X 9 13/16 X 27 9/16 |
Weight (lbs.) | 59.50 |
Duct Connections Supply (in.) | 32 3/16 X 8 11/16 |
Duct Connections Return (ID, in.) | 32 3/16 X 8 11/16 |
Sound Pressure Level Low / Med. / High (dB(A)) | 25 / 27 / 29 |
Safety Certifications | UL 60335-2-40 |
Accessories
Accessory Type | Model Number |
---|---|
Filter box | V1FBX01-4P |
Wired controller (Advanced) | VSTAT04P-1 |
Wired controller (Touchscreen) | VSTAT02P-1 |
Thermostat adapter (for connection to standard 24VAC thermostats) | VSTAT09P-1 |
Wireless signal receiver | VCTRL10P-1 |
Wireless signal control | VSTAT01P-1 |
Wireless controller | VCTRL11P-1 |
External temperature sensor | VSTAT10P-1 |
External contact control interface module | VSTAT10P-1 |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Dimensional Drawing
The unit dimensions are provided in inches. The overall dimensions are approximately 33-7/16 inches in width, 9-15/16 inches in height, and 27-9/16 inches in depth.
Key connection points and features are indicated:
- Liquid pipe connection: 1/4 inch (Item 1)
- Gas pipe connection: 1/2 inch (Item 2)
- Gravity Drain Connection (Item 3)
- Drain Connection (Item 4)
- Opening for Power and Communication Wire Conduit (Item 5)
- Supply Air Outlet Flange (Item 6)
- Return Air inlet (Item 7)
- Suspension Bolt Anchor Points (Item 8)
Duct connections are specified as 32-3/16 inches wide by 8-11/16 inches high for both supply and return.