Lennox VLOD009S6-5P VRF Low Static Ducted Unit Submittal Data

Lennox VLOD009S6-5P VRF Low Static Ducted Unit

Submittal Data

Powered by SAMSUNG

Product Overview

This document provides submittal data for the Lennox VLOD009S6-5P VRF Low Static Ducted Unit, detailing its features, specifications, construction, and available accessories.

General Information

  • Compatible with R-32 VRF air, water, and mini-VRF systems.
  • Features an integral condensate pump with a maximum 29" lift, equipped with a check valve and float switch to disable the unit in the event of condensate overflow.
  • Includes a built-in Wi-Fi adapter as standard, enabling control and monitoring via the Samsung SmartThings app.

Construction

  • Constructed from insulated, galvanized steel.

Refrigerant System

  • The heat exchanger utilizes a mechanically bonded aluminum fin to copper tube design.
  • Refrigerant flow is managed by an electronic expansion valve located at the indoor unit.
  • The unit is equipped with an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (requires VSTAT10P-1 accessory).

Indoor Fan

  • Offers three fan speeds and an auto setting.

Controls

  • Control wiring uses 2 x 16 AWG wire.
  • Operation is managed via a wired remote controller, model VSTAT04P-1, which must be purchased separately.
  • Supports dual set temperature when connected to compatible controllers.
  • Wired or wireless controllers are available and must be purchased separately.

External Heat Control

  • Provides external heat control functionality for configuring fan operation during auxiliary heat, defrost, and emergency heat cycles (requires VSTAT10P-1 accessory).
  • Configuration settings include options for outside ambient external heat lockout, outside ambient compressor lockout, and time delay (requires VSTAT10P-1 accessory).
  • Emergency heat functionality ensures the system continues to control the external heat source even when system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).

Convenience Features

  • The Emergency Temperature Output (ETO) function provides a signal to an external source (e.g., backup system, building management system, alert device) when the indoor unit is in an error status or when the room temperature exceeds a configurable level.

Certifications

The unit is Intertek ETL Listed and AHRI Certified® for Unitary Small HP, adhering to AHRI Standard 210/240.

Note: Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.

Specifications

VLOD009S6-5P Specifications
Feature Value
Indoor Unit Model NumberVLOD009S6-5P
Nominal Capacity (Cooling)9,500 Btu/h
Nominal Capacity (Heating)10,500 Btu/h
Voltage1 / 208-230 / 60 Hz
Operating Current (max.) (Cooling)0.33 A
Operating Current (max.) (Heating)0.33 A
MCA0.57 A
MOP15 A
Fan TypeBLDC (1) With Sirocco Fan (2)
Consumption84 Watts
Evaporator Fan Static Pressure (Standard)0.04 "WC
Evaporator Fan Static Pressure (Min. / Max.)0 / 0.16 "WC
Airflow (Cooling)353 / 388 / 459 CFM (Low/Med/High)
Airflow (Heating)353 / 388 / 459 CFM (Low/Med/High)
Refrigerant TypeR-32
A2L Leak DetectionIntegral
Refrigerant Pipe Connections (High side)1/4"
Refrigerant Pipe Connections (Low side)1/2"
Condensate Connection1 1/4 in. OD, 1 in. ID
Dimensions (W x H x D)43 5/16" x 7 13/16" x 17 5/16"
Weight49.60 lbs.
Duct Connections (Supply)37 1/16" x 5 7/8"
Duct Connections (Return)38 1/2" x 6 5/8" (inside)
Sound Pressure Level (Low / Med. / High)23 / 25 / 27 dB(A)
Safety CertificationsUL 60335-2-40

Accessories

VLOD009S6-5P Accessories

  • Filter box: V1FBX06-4P
  • Wired controller (Advanced): VSTAT04P-1
  • Wired controller (Touchscreen): VSTAT02P-1
  • Thermostat adapter (for connection to standard 24VAC thermostats): VSTAT09P-1
  • Wireless signal receiver: VCTRL10P-1
  • Wireless signal control: VSTAT01P-1
  • Wireless controller: VCTRL11P-1
  • External temperature sensor: VSTAT10P-1
  • External contact control interface module: JV DB39-01263A CN83 Pigtail
  • CN83 Pigtail (for 12VDC VENT output): JV DB39-01263A CN83 Pigtail

Dimensional Drawing

The unit is a low-profile ducted unit with approximate overall dimensions of 43 5/16 inches (width) x 7 13/16 inches (height) x 17 5/16 inches (depth). Key connection points and features are indicated:

Connection Points and Features
No. Description
1Liquid pipe connection (1/4")
2Gas pipe connection (1/2")
3Gravity drain connection
4Drain connection
5Opening for power and communication wire conduit
6Supply air outlet flange
7Return air (air inlet)
8Suspension bolt anchor point

The drawing illustrates the unit's profile for ceiling or concealed installation, showing air inlet and outlet locations, pipe connection points, and mounting provisions.

PDF preview unavailable. Download the PDF instead.

sbmtl vlod009s6-5p 2509 Adobe InDesign 20.5 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Lennox VHID054S6-5P VRF High Static Ducted Indoor Unit Submittal Data
Technical specifications and features for the Lennox VHID054S6-5P VRF High Static Ducted indoor unit, compatible with R-32 VRF systems, including performance data, dimensions, and accessories.
Preview Lennox VMDD012S6-5P VRF Medium Static Ducted Submittal Data
Submittal data for the Lennox VMDD012S6-5P VRF Medium Static Ducted indoor unit, detailing its specifications, features, accessories, and dimensions. Compatible with R-32 VRF systems and offers Wi-Fi connectivity via Samsung SmartThings app.
Preview Lennox VVCD054S6-5P VRF Vertical Air Handler Submittal Data
Technical specifications and submittal data for the Lennox VVCD054S6-5P VRF Vertical Air Handler, detailing performance, construction, controls, accessories, and dimensions.
Preview Lennox VUCD036S6-5P VRF Ceiling Mount Submittal Data and Specifications
Comprehensive submittal data and technical specifications for the Lennox VUCD036S6-5P VRF Ceiling Mount indoor unit, detailing performance, construction, controls, accessories, and dimensional information.
Preview Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit Specifications
Detailed submittal data and specifications for the Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit, highlighting features like Calm Air mode, Wi-Fi connectivity, R-32 refrigerant compatibility, and external heat control.
Preview Lennox VOWD007S6-5P VRF 1-Way Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox VOWD007S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance metrics, accessories, and dimensional details.
Preview Lennox V36D030S6-5P VRF 360 Cassette Submittal Data and Specifications
Detailed submittal data and technical specifications for the Lennox V36D030S6-5P VRF 360 Cassette indoor unit, including performance, construction, refrigerant, fan, controls, and accessories.
Preview Lennox VOWD012S6-5P VRF 1-Way Cassette Submittal Data
Submittal data for the Lennox VOWD012S6-5P VRF 1-Way Cassette indoor unit, detailing its features, specifications, and accessories. Compatible with R-32 VRF systems.