Temperzone Packaged Rooftop Air Conditioners R32

Econex Series Technical Data

Introduction

The Econex Packaged rooftop HVAC units provide ultimate flexibility and performance demanded in open plan commercial environments. This document details the technical specifications, performance data, and dimensions for the OPA 171/211 Econex Series R32 units.

Econex Key benefits:

Econex Pro Additional benefits:

Applications

Specifically developed for air conditioning of small commercial premises, e.g., retail stores, restaurants, banks, and motels.

Features

Lower GWP

Utilising R32 Refrigerant, Temperzone's Econex Packaged Units enable a 73-76% reduction of Global Warming Potential (GWP) per kW of cooling when compared to R410A units.

Economy

Each Econex (Pro) unit in this series uses a variable capacity inverter, which generally uses less energy than alternative types of compressor.

Efficient

As most air conditioners operate at part load for the vast majority of the time, it makes sense for each unit to incorporate an inverter scroll compressor which is very efficient at part load. Part load efficiency can be even further enhanced by indoor fan part load operation at low loads (e.g., 75% airflow equates to 55% power use). Each indoor air fan incorporates a high efficiency electronically commutated (EC) motor. Large heat exchange coils incorporate inner grooved (rifled) tube for better heat transfer.

Better Comfort

Variable speed technology enables fine tuning of the system, which ultimately delivers temperature stability and therefore better comfort to the occupants in the air-conditioned space. The system also includes head pressure control logic, which enables the system to compensate for outdoor ambient temperatures below 20°C on cooling cycle, and above 15°C on heating cycle.

Intelligence (Econex Pro)

Econex Pro incorporates intelligent technology. Its software understands the surrounding environment and self-adjusts to maintain required temperature and humidity levels. The unit can operate to: (1) maximise part-load efficiency, (2) maximise performance, or (3) balance efficiency and performance. The variable capacity inverter compressor technology can provide close comfort control of the room temperature. Each OPA unit has capacity higher than its nominal available for fast response when well away from set point at start-up, and an energy-saving low capacity turn-down. Econex/EconexPro feature a dynamically balanced forward curved fan with a variable speed EC motor. This variability enables fine tuning to match the supply air requirements. These EC motor fans have a fully integrated speed control that enables soft starting. Fan speed can be stepped to your own requirements or continuously variable using a 0-10V DC control signal.

Quiet

Each integral high efficiency EC fan motor can vary from zero to full speed. This allows slow ramp up with no sudden noise change. The outdoor coil design permits low fan speeds and hence low noise levels. The compressor is in a weatherproof built-in, insulated compartment to minimise noise. The indoor air section is also insulated for noise attenuation, thermal protection of the air stream, and to minimise exterior condensation.

Durable

The cabinet is constructed from high-grade galvanised steel - baked polyester powder coated (to AS 4506:2005; colour Grey) for all-weather protection (IP44 / IPX4). External fasteners are marine-grade SKT® coated steel. The units include a baked polyester powder coated drain tray. Heat exchange coils comprise aluminium corrugated plate fins on mechanically expanded rifled copper tube. Both the indoor and outdoor coils' fins are pre-epoxy coated for extra protection in corrosive environments, e.g., salt-laden sea air. Fan motor bearings are sealed for life so as not to incur regular maintenance. Coil protection guards protect against hail, accidental damage, or vandalism.

Easy Access

These packaged outdoor units are typically installed on a rooftop, where maintenance access is relatively easy during operating hours.

Improves Indoor Air Quality

The indoor air fan ventilates the building by distributing conditioned air throughout the building, with an option for fresh air introduction via Economiser control. (Note: Air filters, economy cycle dampers, and fresh air openings are not included with the unit and should be installed in the external duct system).

Low Maintenance

Commissioning and maintenance costs are reduced through the use of a fan that requires no pulley and belt adjustments or changes like traditional fans.

Inverter Compressor

Each high efficiency variable capacity inverter compressor is hermetically sealed, quiet running, and supported on rubber mounts to minimise vibration. Inverter compressor provides the economy of part load performance.

Soft Starting

EC motors and inverter compressors are soft starting, therefore have none of the problems associated with high in-rush current.

Insulation

Closed-cell foam insulation has been used in the indoor air section to ensure no particles are introduced into the air stream. Both indoor and outdoor air chambers are insulated to prevent external condensation forming on the cabinet exterior. The insulation is foil-faced and meets fire test standards AS 1530.3 (1989) and BS 476 parts 6 & 7.

Unit Control System

Econex: The control system is comprised of a Temperzone UC8 controller which looks after factory settings, status reporting, and alarms display. An external controller is also required.

Econex Pro: The control system is comprised of one Carel c.pCO mini master controller and one Temperzone UC8 slave controller. The master controller looks after the setpoints, operation modes, factory settings, status reporting, scheduling, BMS settings, and alarms display. The unit's fully integrated controls enable it to operate as a 'stand alone' unit. An optional Carel pGN (pn 201-000-867) wired remote display is available for location up to 50m from the unit, enabling easier servicing.

Control Option

The EC fan motor is controlled variably (within a restricted range, p10) by a 0-10 volt DC signal that can be supplied either by a BMS system, or the internal c.pCO Controller (Pro only). The units are BMS compatible, with multi-unit control possible via Modbus RTU, Modbus TCP/IP or BACnet/IP. Refer to Temperzone for other protocols available. Units can also be run as turn-key operation with no BMS connection required.

Extended Capability

Inverters are particularly suitable for applications requiring high proportions of fresh air, VAV, and close control. Supply air temperature control is also possible using BMS or other controls. Refer to Temperzone for capacity range variation options.

System Protection Features

  1. HP and loss of refrigerant protection.
  2. Anti-rapid cycle timer and internal overload for compressor protection.
  3. Circuit breaker control circuits.
  4. Time-and-temperature controlled electronic de-ice switch prevents icing up of the outdoor coil during heating cycle.
  5. Frost protection on cooling cycle.
  6. Sensor fault indication.

Self Diagnostics

Each Unit Controller (UC8) has a LED display to indicate faults and running conditions. No need to connect pressure gauges. Econex: A non-specific/common fault indicator is included for interface to external systems. Econex Pro: Faults can be displayed on the master controller and communicated through BMS (both general and specific).

Lower Installation Costs

This type of air conditioner is compact and self-contained in comparison to Split Systems which require long interconnecting piping. OPA units are quick to install.

Wiring

The electrical supply required is: 3 phase 400 V a.c. 50 Hz with neutral and earth. The compressor crankcase heater requires a 24 hr power supply. The control panel is fully wired ready to accept the main power supply. Each system complies with the requirements of the Regulatory Compliance Mark (RCM) for electrical safety (AS/NZS 60335.2.40) and EMC (AS/NZS CISPR.14). For your convenience, a single phase auxiliary power outlet (10A) is included in the electrical box.

Plant Room Use

Each unit is supplied with a relatively low static (<25 Pa) condenser fan. Nominal outdoor airflow and correct unit clearances, along with no air recirculation, must be maintained in order for the unit to achieve its performance specification.

Configurations

  1. Horizontal supply & return air versions
  2. Upward supply & horizontal return air versions

Optional Equipment

External Economiser Control

For external in-duct dampers: If the outdoor air enthalpy (heat content) is below that of the space condition, a fresh air damper opens and a return air damper closes to provide cooling. Operating costs are reduced as free cooling is obtained. (Note: A separate spill air facility in the building may be necessary for when the return air damper is closed.) Fresh air dampers close to a minimum setting and return air dampers open before normal compressor operation resumes.

This option for Econex units requires external dampers c/w motors and cowl; sensors and controls by others.

This option for Econex Pro units requires external dampers (c/w motors) and an additional temperature & humidity sensor for the outside air, but includes Economy Cycle control functionality.

Controllers

TZT-100 Controller (Optional)

Features include Cool / Cool Dry / Heat / Auto Dry / Auto / Fan Only modes, Auto / High / Medium / Low fan speed selection (customisable), temperature setting range from 1°C - 38°C, LED status indicator, room & set temperature display, real-time clock, 12/24 hour time display, °C or °F display, 7-day timer (up to two events per day), on-demand countdown run timer (up to 9 hours), Auto-Restart or No Restart after power failure, continuous or intermittent fan run-on, backlit screen, soft touch keys, PIN protected menus, keypad/temperature lock, filter monitor, occupancy sensor inputs, integrated Modbus option, battery backup, night mode for energy saving, audible beep, 24V control cable, and optional remote air temperature sensor. Note: TZT-100 is not suitable for Econex Pro units and is not designed to control an Economiser.

Carel c.pCO mini Advanced Controller (Econex Pro)

Features adaptive technology for flexibility and user-friendliness. Fully integrated controls manage every unit function. Includes pre-programmed optimisation and comfort modes, intelligent humidity control, built-in controller display for quick set-up, room and humidity sensor (supplied loose), return and supply air sensors (factory fitted), occupancy offset for temperature setback during unoccupied periods, reduced indoor fan speed during unoccupied times, night/quiet mode, daily scheduled times (up to 4 events/day, 7 days/week), individual time clock for night/unoccupied mode, access security (multi-level control & password), service interface screen with data log features and alarms (USB exportable history file), refrigeration systems information via display or BACnet/IP and Modbus/RTU, quick start-up user settings, remote on/off, and battery backup of settings. Also includes Economy Cycle control of external dampers using enthalpy. Optional sensors include Fresh Air Temp./Humidity, Return Air/Fresh Air damper connections (0-10V), CO2 sensor, and drain sensor. An optional remote wired Service Interface display (pGN) is available.

Performance Data

Cooling Capacity (kW)

OPA 171 Econex & Econex Pro @Nominal Capacity (900 l/s)

TC = Total Capacity (kW), SC = Sensible Capacity (kW), PI = Power Input (kW), EAT = Entering Air Temperature (°C D.B./W.B.). Nominal Air Flow: 900 l/s. Note: Capacities are gross and do not include allowance for fan motor heat loss.

Indoor coil E.A.T.
°C D.B./W.B.
Outdoor coil Entering Air Temperature °C DB
20 25 30 35 40 45 50
TCSCPITCSCPITCSCPITCSCPITCSCPITCSCPITCSCPITCSCPI
1414.29.93.614.410.43.814.710.94.115.011.34.515.211.84.815.412.25.215.512.75.6
1514.78.93.615.09.33.915.39.74.215.510.14.515.710.54.815.910.95.216.111.25.6
1615.37.93.615.68.23.915.98.54.216.18.84.516.39.14.916.59.45.216.79.65.7
1715.96.73.616.26.93.916.57.14.216.77.34.516.97.54.917.17.75.317.37.85.7
1615.09.93.715.210.34.015.510.84.315.811.34.616.011.75.016.112.15.316.312.55.8
1715.58.93.715.89.34.016.19.74.316.310.04.616.510.45.016.710.85.416.811.15.8
1816.17.83.716.48.14.016.68.44.316.98.74.617.19.05.017.39.25.417.49.55.8
1916.76.63.717.06.84.017.27.04.317.57.24.717.77.35.017.97.55.418.07.75.9
1614.811.53.715.112.14.015.312.74.315.613.34.715.813.85.015.914.45.416.114.95.9
1815.89.93.816.110.34.116.310.84.416.511.24.716.711.65.116.912.05.517.112.45.9
2016.97.83.817.28.04.117.48.34.417.68.64.817.98.85.218.09.15.618.29.36.0
2117.56.53.817.76.74.118.06.94.518.27.04.818.47.25.218.67.35.618.87.56.1
1715.212.33.815.512.94.115.713.64.515.914.24.816.114.85.216.315.45.616.415.96.0
1916.110.83.916.411.34.216.611.84.516.812.34.817.012.75.217.213.25.617.313.66.1
2016.69.93.916.910.34.217.110.74.517.311.14.917.511.55.317.711.95.717.812.36.1
2217.77.73.917.97.94.218.28.24.618.48.44.918.68.75.318.88.95.718.99.16.2
1815.612.33.915.913.04.216.113.64.516.314.24.916.514.85.316.715.45.716.815.96.1
1916.011.63.916.312.24.216.612.74.516.813.34.917.013.85.317.114.35.717.314.86.1
2016.510.83.916.811.34.217.011.84.617.212.24.917.412.75.317.613.15.717.713.66.2
2217.58.83.917.89.24.318.09.54.618.39.85.018.510.15.418.610.45.818.710.76.2
1815.613.13.915.913.74.216.114.44.616.315.04.916.515.75.316.716.35.716.816.46.2
2016.511.64.016.712.24.317.012.74.617.213.25.017.413.85.417.514.35.817.714.76.2
2217.49.84.017.710.24.317.910.64.718.111.05.018.311.45.418.511.85.816.511.95.3
2418.57.64.018.77.94.319.08.14.719.28.35.119.48.65.519.58.85.916.38.94.9
1916.113.84.016.314.54.316.615.24.716.815.95.117.016.55.517.116.75.915.314.95.3
2116.912.44.117.113.04.417.413.64.717.614.25.117.814.75.517.915.35.914.914.54.9
2317.810.74.118.011.24.418.311.74.818.512.15.118.612.65.618.813.06.014.411.94.6
2518.78.74.119.09.04.419.29.34.819.59.65.219.69.95.619.810.26.115.29.74.6
2116.913.94.117.214.64.517.415.24.817.615.95.217.816.65.617.917.26.113.813.34.6
2317.712.44.218.013.04.518.213.64.918.414.25.318.614.75.718.715.26.113.112.64.2
2518.610.74.218.811.24.519.111.64.919.312.15.319.412.55.719.612.96.213.711.14.2
2619.19.74.219.310.14.619.610.54.919.810.85.319.911.25.820.111.56.214.010.14.3

OPA 211 Econex & Econex Pro @Nominal Capacity (1050 l/s)

TC = Total Capacity (kW), SC = Sensible Capacity (kW), PI = Power Input (kW), EAT = Entering Air Temperature (°C D.B./W.B.). Nominal Air Flow: 1050 l/s. Note: Capacities are gross and do not include allowance for fan motor heat loss.

Indoor coil E.A.T.
°C D.B./W.B.
Outdoor coil Entering Air Temperature °C DB
20 25 30 35 40 45 50
TCSCPITCSCPITCSCPITCSCPITCSCPITCSCPITCSCPITCSCPI
1419.213.64.018.813.74.418.413.74.818.013.85.217.613.85.617.113.76.116.613.66.5
1519.912.34.019.612.34.419.212.34.818.712.35.218.312.35.617.812.26.117.212.16.6
1620.710.84.020.310.84.419.910.84.819.410.75.219.010.75.718.510.56.217.910.46.6
1721.69.24.121.19.14.420.79.04.920.28.95.319.78.85.719.28.66.218.68.56.7
1620.313.64.119.913.74.519.513.74.919.013.75.318.613.75.818.013.66.217.513.56.7
1721.012.34.120.612.34.520.212.34.919.712.35.419.212.25.818.712.16.318.112.06.8
1821.810.84.121.410.84.520.910.75.020.410.65.419.910.55.919.310.46.318.710.26.8
1922.69.14.122.29.04.621.78.95.021.28.85.420.68.75.920.08.56.419.48.36.9
1620.115.84.219.716.04.619.316.15.018.816.25.418.316.25.917.816.16.317.316.06.8
1821.413.64.221.013.64.620.513.75.020.013.75.519.513.65.918.913.56.418.413.46.9
2022.910.74.222.410.74.721.910.65.121.410.55.520.810.46.020.210.26.519.610.17.0
2123.79.04.223.28.94.722.78.85.122.18.75.621.58.56.120.98.36.620.28.17.1
1720.616.94.320.217.14.719.817.25.119.317.35.518.817.36.018.217.36.517.717.27.0
1921.914.84.321.414.94.720.914.95.120.415.05.619.914.96.119.314.86.618.714.77.1
2022.513.64.322.113.64.721.513.65.221.013.65.620.513.56.119.913.46.619.213.37.1
2224.010.64.323.510.64.822.910.55.222.410.45.721.810.26.221.110.16.720.49.97.2
1821.216.94.320.817.14.720.317.25.219.817.35.619.317.36.118.717.36.618.117.27.1
1921.815.94.321.316.14.820.916.15.220.316.25.619.816.26.119.216.16.618.616.07.1
2022.414.84.421.914.94.821.414.95.220.914.95.720.314.96.219.714.86.719.114.77.2
2223.812.24.423.312.14.822.712.15.322.212.05.721.611.96.220.911.86.720.211.67.3
1821.217.94.420.818.14.820.318.35.219.818.35.719.318.46.118.718.26.618.117.67.1
2022.416.04.421.916.14.821.416.15.320.916.25.720.316.16.219.716.16.719.015.97.2
2223.713.64.423.113.64.922.613.65.322.013.55.821.413.46.320.813.36.820.113.27.3
2425.110.64.424.510.54.924.010.45.423.310.35.922.710.16.422.09.96.921.39.77.4
1921.918.94.521.419.14.920.919.35.320.419.45.819.819.36.319.218.76.818.518.17.3
2122.917.14.522.417.24.921.917.35.421.317.35.920.717.36.420.117.26.919.417.17.4
2324.214.84.523.614.95.023.014.95.422.414.95.921.814.86.421.114.76.920.414.57.5
2525.512.14.524.912.05.024.311.95.523.711.86.023.011.76.522.311.67.021.511.47.6
2123.019.14.622.519.25.022.019.45.521.419.56.020.819.56.520.119.47.019.419.07.5
2324.117.14.623.617.25.123.017.35.522.417.36.021.717.36.521.017.27.120.317.17.6
2525.314.84.624.714.85.124.114.85.623.514.86.122.814.76.622.114.67.121.314.47.7
2626.013.44.625.313.45.124.713.45.624.013.36.123.313.26.622.613.17.221.812.97.7

Heating Capacity (kW)

G = Gross Capacity kW, N = Net Heating Capacity kW (allowing for average defrost), PI = Power Input (kW).

OPA 171 Econex & Econex Pro at Nominal Capacity (900 l/s)

Air on D.B. °C Outdoor coil entering air temperature °C DB
-10 -5 0 5 7 10 15 20 25
GNPIGNPIGNPIGNPIGNPIGNPIGNPIGNPIGNPI
1010.29.03.513.212.04.215.114.24.315.614.94.416.516.54.417.917.94.518.518.54.518.918.94.519.319.34.5
159.88.73.413.512.34.515.514.64.616.015.24.716.916.94.718.318.34.818.918.94.819.319.34.819.719.74.8
209.48.23.312.411.34.015.914.94.916.416.45.017.317.35.118.718.75.119.319.35.119.719.75.220.120.15.2
258.87.83.112.711.64.316.316.35.316.816.85.317.717.75.419.119.15.519.719.75.520.120.15.520.520.55.5

OPA 211 Econex & Econex Pro at Nominal Capacity (1050 l/s)

Air on D.B. °C Outdoor coil entering air temperature °C DB
-10 -5 0 5 7 10 15 20 25
GNPIGNPIGNPIGNPIGNPIGNPIGNPIGNPIGNPI
1012.911.44.514.913.64.617.216.14.717.816.94.818.818.84.820.420.44.821.121.14.921.521.54.922.022.04.9
1513.311.74.715.314.04.917.616.65.018.218.25.019.319.35.120.920.95.121.521.55.222.022.05.222.422.45.2
2013.712.15.015.814.45.118.118.15.318.718.75.319.719.75.421.321.35.422.022.05.522.422.45.522.922.95.5
2514.212.55.316.214.75.418.518.55.619.119.15.720.120.15.721.721.75.822.422.45.822.922.95.823.323.35.8

Indoor Air Flow Correction Factors @ nominal conditions

Indoor Air Flow
-20% -10% Rated +10%
Total Cooling Capacity0.9500.9751.0001.025
Sensible Cooling Capacity0.9000.9501.0001.050
Heating Capacity0.9900.9951.0001.005

Air Handling

Airflows are for a dry coil. Refer to Air Flow Selection (p.4) for further information. Air flows given are for OPA units without filters. Amp figures are 'per phase'.

OPA 171 Air Handling

Pressure (l/s - Pa) Graph: The Y-axis represents Available External Pressure (Pa) from 0 to 500 Pa. The X-axis represents Air Flow (l/s) from 400 to 1000 l/s. Curves are shown for different fan speeds/voltages (5V, 6V, 7V, 8V, 9V, 10V) and current (1.5A, 2.4A, 3.5A, 4.9A, 2.6A). The graph illustrates the relationship between air flow and external pressure for various operating conditions.

Power Input (l/s - W) Graph: The Y-axis represents Power Input (W) from 0 to 1000 W. The X-axis represents Air Flow (l/s) from 400 to 1000 l/s. Curves are shown for different fan speeds/voltages (5V, 6V, 7V, 8V, 9V, 10V). The graph illustrates the relationship between air flow and power input.

Note: Face Velocity is 2.5 m/s at nominal air flow. Max. @2m/s is indicated.

OPA 211 Air Handling

Pressure (l/s - Pa) Graph: The Y-axis represents Available External Pressure (Pa) from 0 to 500 Pa. The X-axis represents Air Flow (l/s) from 400 to 1400 l/s. Curves are shown for different fan speeds/voltages (5V, 6V, 7V, 8V, 9V, 10V) and current (0.5A, 0.6A, 0.8A, 1.2A, 1.3A, 1.4A, 1.8A, 2.2A). The graph illustrates the relationship between air flow and external pressure for various operating conditions.

Power Input (l/s - kW) Graph: The Y-axis represents Power Input (kW) from 0 to 1000 kW. The X-axis represents Air Flow (l/s) from 400 to 1400 l/s. Curves are shown for different fan speeds/voltages (5V, 6V, 7V, 8V, 9V, 10V). The graph illustrates the relationship between air flow and power input.

Note: Max. Face Velocity is @2m/s.

Sound Levels

Indoor Sound Levels

Test Conditions: EN 12102-1:2017. Diffuse field method in a reverberant room. Measured in decibels re 1 picowatt.

Sound Power Levels (SWL) – Supply Air Outlet
Model Fan Speed SWL dB(A) Octave Band Frequency Hz
1252505001k2k4k
OPA 1715 V66.667.364.963.562.259.053.2
7 V *72.573.470.368.368.365.461.1
10 V77.678.475.573.072.870.867.6
OPA 2115 V66.667.364.963.562.259.053.2
6 V *69.670.468.065.965.162.457.7
10 V77.678.475.573.072.870.867.6

* Note: Indoor Air fan running at nominal speed

Sound Pressure Levels (SPL) Within A Room

Deduct the room absorption effect below from the Sound Power Levels (SWL) above to obtain Sound Pressure Levels within a room. Note: Occupant at least 1.5 m from sound source.

Room type Octave Band Frequency Hz
1252505001k2k4k
Soft4811111111
Medium378999
Hard013445

Outdoor Sound Levels

Measured in decibels re 1 picowatt

Sound Power Levels (SWL) – Radiated
Models Fan Speed SWL dB(A) Octave Band Frequency Hz
1252505001K2K4K
OPA 1713 V60.150.357.353.451.442.734.7
6 V74.764.570.268.168.564.056.5
10 V *74.862.967.369.469.965.658.1
OPA 2113 V63.153.360.356.454.445.737.7
6 V77.767.573.271.171.567.059.5
10 V *77.865.970.372.472.968.661.1

* Note: Outdoor fans running at nominal speed

Sound Pressure Levels (SPL)
Models Fan Speed SPL @ 3 m dB(A) Octave Band Frequency Hz
1252505001K2K4K
OPA 1713 V44.134.341.337.435.426.718.7
6 V58.748.554.252.152.54840.5
10 V *58.846.951.353.453.949.642.1
OPA 2113 V47.137.344.340.438.429.721.7
6 V61.751.557.255.155.551.043.5
10 V *61.849.954.356.456.952.645.1

Sound Pressure Level (SPL) in decibels re 20 μPa

Dimensions (mm)

OPA 171RLTFY(D) Horizontal Supply

Point Loads (kg): W: 56, X: 58, Y: 68, Z: 65

Multiple units side-by-side: Allow a minimum of 2m between coil faces.

Diagram Description: A top-down and front view of the OPA 171 unit. The top view shows the unit with two large fans, labelled 'FAN ACCESS', and indicates 'TOP SUPPLY AIR SPIGOT MODEL'. Clearances are marked: 1000 MIN. CLEARANCE above, 500 MIN. CLEARANCE to the sides. The front view shows the unit's exterior with dimensions labelled. Key components and dimensions include: 'ELECTRICAL' panel, 'COMMS. 25 ID', 'POWER 32 ID', 'DRAIN 1/2" BSP female'. Overall dimensions and mounting hole locations are indicated: 1170 MTG CTRS (Mounting Centers), 800 MTG CTRS (12 DIA. HOLES). Side clearances are marked: 2000 MIN. CLEARANCE on the front/back, 1000 MIN. CLEARANCE on the sides. Spigot dimensions are shown: 778 S/A SPIGOT (Supply Air), 1030 R/A SPIGOT (Return Air). Overall dimensions are approximately 1176 O/A (Overall) length, 1254 O/A width, and 1230 O/A height. The diagram includes a PROJECTION view and is 'Not to Scale'.

OPA 211RLTFY(D) Horizontal Supply

Point Loads (kg): W: 71, X: 84, Y: 79, Z: 67

Multiple units side-by-side: Allow a minimum of 2m between coil faces.

Diagram Description: A top-down and front view of the OPA 211 unit. The top view shows the unit with two large fans, labelled 'FAN ACCESS', and indicates 'TOP DISCHARGE SPIGOT MODEL'. Clearances are marked: 1000 MIN. CLEARANCE above, 500 MIN. CLEARANCE to the sides. The front view shows the unit's exterior with dimensions labelled. Key components and dimensions include: 'ELECTRICAL' panel, 'COMMS. 25 ID', 'POWER 32 ID', 'DRAIN 1/2" BSP female'. Overall dimensions and mounting hole locations are indicated: 1571 MTG CTRS (Mounting Centers), 800 MTG CTRS (12 DIA. HOLES). Side clearances are marked: 2000 MIN. CLEARANCE on the front/back, 1000 MIN. CLEARANCE on the sides. Spigot dimensions are shown: 778 S/A SPIGOT (Supply Air), 1030 R/A SPIGOT (Return Air). Overall dimensions are approximately 1174 O/A (Overall) length, 1252 O/A width, and 1230 O/A height. The diagram includes a PROJECTION view and is 'Not to Scale'.

Specifications

Model OPA 171 Econex & Econex Pro OPA 211 Econex & Econex Pro
Cooling Capacity 1 kW16.8 (5.3~20.3)20.3 (7.3~25.3)
Net Cooling Capacity (MEPS) 1 kW16.419.9
TCSPF 1 (cold/mixed/hot)5.73 / 5.16 / 5.206.23 / 5.42 / 4.97
EER / AEER (cooling)3.34 / 3.303.52 / 3.48
Heating Capacity 2 kW17.3 (4.0~20.7)19.7 (5.8~26.4)
HSPF 2 (cold/mixed/hot)3.55 / 3.76 / 3.953.80 / 4.03 / 4.22
COP / ACOP (heating)3.42 / 3.383.67 / 3.63
Nominal Air Flow 3 l/s900 (450~1000)1 050 (525~1400)
Master ControllerUC8 for Econex 6 / Carel c.pCO mini for Econex ProUC8 for Econex Pro
Slave ControllerUC8 for Econex Pro
Power Source 43 phase 400 V a.c. 50 Hz + N + E3 phase 400 V a.c. 50 Hz + N + E
RefrigerantR32 (Class A2L)R32 (Class A2L)
Compressor typeinverter scrollinverter scroll
Indoor air fan typefoward curved EC (x2)EC axial (x2)
Outdoor air fan typeEC axialEC axial (x2)
Indoor Fan Max. Current A2.5 (x2)3.0 (x2)
Running Amps (Total) 1 A/ph.9.0 / 7.5 / 9.010.0 / 8.5 / 11.5
Max. Running Amps (Total) A/ph.14.0 / 10.5 / 13.020.0 / 15.5 / 18.0
IP RatingIP44 / IPX4 5IP44 / IPX4 5
Finishgrey polyester powder coatgrey polyester powder coat
Operating Range (outdoor ambient)
Cooling-10°C to 50°C-10°C to 50°C
Heating-10°C to 25°C-10°C to 25°C
Weight (net/shipping) kg
Unit247 / 280299 / 341

Notes:

  1. Nominal Cooling Capacity (gross) at AS/NZS 3823 conditions: Indoor Entering Air Temperature 27°C D.B., 19°C W.B.; Outdoor Entering Air Temperature 35°C D.B.
  2. Heating Capacity at AS/NZS 3823 conditions: Indoor Entering Air Temperature 20°C D.B.; Outdoor Entering Air Temperature 7°C D.B., 6°C W.B.
  3. Supply air flow at Nominal Cooling Capacity conditions stated above.
  4. Voltage range: 376-440 V
  5. Outdoor fan-guard clearance <100 mm (ref. IEC 60529)
  6. Connects to optional TZT-100 room temperature controller

Compliance: AS/NZS 3823.2:2013 Minimum Energy Performance standards, AS/NZS 60335.2.40:2019 Safety of Electrical Appliances, AS/NZS 61000.6.8:2021 EMC standard, AS 4506:2005 Powder coat salt spray Class D High Marine.

Contact Us

For further information or to locate your nearest branch, please visit www.temperzone.com.

Auckland

Head Office
38 Tidal Rd, Mangere, Auckland
Private Bag 93303, Otahuhu
New Zealand
Phone: (09) 279 5250
Email: nzsales@temperzone.com

Sydney

Head Office
14 Carnegie Place, Blacktown NSW 2148
PO Box 8064, Seven Hills West NSW 2147, Australia
Phone: (02) 8822 5700
Email: nswsales@temperzone.com

Newcastle

Phone: (02) 4692 1155
Email: sales@mcintoshair.com.au

Launceston

Phone: (03) 6331 4209
Email: info@hvac-supplies.net

Hamilton

Phone: (07) 839 2705
Email: tzhamilton@temperzone.com

Adelaide

Phone: (08) 8115-2111
Email: sasales@temperzone.com

Singapore

Phone: +65 6733 4292
Email: sales@temperzone.com.sg

Wellington

Phone: (04) 569 3262
Email: wgtn@temperzone.com

Melbourne

Phone: (03) 8769 7600
Email: vicsales@temperzone.com

Christchurch

Phone: (03) 379 3216
Email: chch@temperzone.com

Brisbane

Phone: (07) 3308 8333
Email: qldsales@temperzone.com

Perth

Phone: (08) 6399 5900
Email: reception@airskill.com

Materials and specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.

© Temperzone Itd 2025. 08/25 Pamphlet No. 4152

PDF preview unavailable. Download the PDF instead.

OPA 171211 Econex Series TD 0825 Adobe PDF Library 17.0 Adobe InDesign 20.5 (Macintosh)

Related Documents

Preview Temperzone Ducted Packaged Units OPA 1410/1710/2110 Econex Series R32 Technical Data
Comprehensive technical data, specifications, performance charts, and features for Temperzone's OPA 1410, 1710, and 2110 Econex Series R32 ducted packaged rooftop air conditioning units, designed for commercial environments.
Preview Temperzone Econex Packaged Units: Efficient, Sustainable, Low-GWP HVAC
Explore Temperzone's Econex Air-Cooled Packaged Units, featuring R32 refrigerant for lower GWP and superior energy efficiency with inverter technology. These low-carbon HVAC solutions are ideal for commercial applications, offering advanced features and durable design.
Preview Temperzone Ducted Packaged Units: Technical Data for Econex Series R32
Comprehensive technical data for Temperzone's Econex Series R32 Ducted Packaged Units, including specifications, performance data, dimensions, sound levels, and nomenclature for models OPA 680, 820, and 970.
Preview Temperzone Econex Pro Packaged Units: Advanced Humidity Control and Energy Efficiency
Discover the Temperzone Econex Pro Air Cooled Packaged Units, designed for superior humidity control, energy efficiency, and reliability. Featuring R32 refrigerant, inverter compressors, and EC fans, these units offer advanced performance for commercial and industrial applications.
Preview temperZONE OPA Econex Pro Technical Guide: Features, Modes, and Controls
Comprehensive technical guide for temperZONE's OPA Econex Pro series air conditioning units. Covers comfort modes, controller overview, settings, and system information for models OPA 171, 211, 680, 820, 970, 1410, 1710, and 2110.
Preview Temperzone Econex Packaged Units: Energy Efficient Air Conditioning
Discover the Temperzone Econex Packaged Units, featuring R32 inverter technology for superior energy efficiency, lower Global Warming Potential (GWP), and advanced comfort control. Explore features, specifications, and benefits for commercial and light commercial applications.
Preview Temperzone OPA 171 Econex (Pro) R32 Ducted Packaged Unit Part Load Performance Data
Comprehensive part load performance data for the Temperzone OPA 171 Econex (Pro) R32 ducted packaged air conditioning unit. Includes detailed cooling and heating capacity tables, power input figures, and indoor air flow correction factors for various operating conditions.