R. STAHL 8530/1-MCB-STA102-C2-500-3 Line Protection Circuit Breaker

Article Number: 272131

Product Overview

The R. STAHL 8530 series line protection circuit breakers, specifically the 8530/1-MCB-STA102-C2-500-3 model, offer excellent current limitation for short circuits with high switching capacities of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modular and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).

Key features include:

Technical Characteristics

Explosion Protection

Characteristic Value
Application Area (Zones) 1, 2
Application Area (Zones) Note Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure
IECEx Gas Certificate IECEx FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX Gas Certificate FM19ATEX0191U
ATEX Gas Explosion Protection II 2 G Ex db eb IIC Gb
Certificates ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of Conformity ATEX (FM), China (CCC)

Electrical Characteristics

Characteristic Value
Rated Operational Voltage AC 230/400 V
Rated Service Current 2 A
Frequency 50/60 Hz
Rated Switching Capacity 10 kA
Electrical Service Life 2 x 104
Mechanical Service Life 2 x 104
1st Auxiliary Function Auxiliary contact 1 changeover + signal contact 1 changeover
Voltage 1st Auxiliary Function AC 230 V
Max. Current 1st Auxiliary Function 2 A
2nd Auxiliary Function None
Max. Voltage 2nd Auxiliary Function DC C
Tripping Characteristic C
Number of Poles 2-pole

Ambient Conditions

Characteristic Value
Ambient Temperature -40 °C ... 70 °C
Ambient Temperature -40 °F ... 158 °F
Ambient Temperature Note Ambient temperatures differing based on current certificates, upon request

Mechanical Characteristics

Characteristic Value
Degree of Protection (IP) (IEC 60529) IP2X
Enclosure Material Thermoplastic
Minimum Connection Terminal Size 1.5 mm²
Maximum Connection Terminal Size 25 mm²
Minimum AWG Connection Terminal Size 16 AWG
Maximum AWG Connection Terminal Size 4 AWG
Minimum Connection Terminal Size 2 1.5 mm²
Maximum Connection Terminal Size 2 10 mm²
Minimum AWG Connection Terminal Size 2 16 AWG
Maximum AWG Connection Terminal Size 2 8 AWG
Min. Connection Terminal Size (Auxiliary) 0.5 mm²
Max. Connection Terminal Size (Auxiliary) 4 mm²
Min. AWG Connection Terminal Size (Auxiliary) 18 (unece.unit.AWG)
Max. AWG Connection Terminal Size (Auxiliary) 14 (unece.unit.AWG)
Minimum Tightening Torque 2 N·m
Maximum Tightening Torque 3 N·m
Connection Terminal Note Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.)
Allowed connection terminal combinations are indicated in the operating manual.
Width 83 mm
Width (inches) 3.27 in
Length 165 mm
Length (inches) 6.5 in
Mounting Depth 138.3 mm
Mounting Depth (inches) 5.44 in
Weight 1.3 kg
Weight (lbs) 2.867 lb

Mounting / Installation

Characteristic Value
Tightening Torque 2-3 N·m
Tightening Torque (lbf-in) 17.7 ... 26.6 lbf-in
Tightening Torque (Auxiliary Contact) 0.4 – 0.6 Nm
Tightening Torque (Auxiliary Contact lbf-in) 3.5 ... 5.3 lbf in

Technical Drawings

Diagram 1: Shows the dimensions of the circuit breaker, including width, length, and mounting depth. The overall dimensions are 83 mm width, 165 mm length, and 138.3 mm mounting depth.

Diagram 2: Illustrates the tripping characteristic curve for the circuit breaker. The curve shows the relationship between the multiple of the rated current (I/In) and the tripping time in seconds for both AC and DC circuits, with a 'C' tripping characteristic.

Diagram 3: Provides a footprint plan with dimensions for the 8530/1 unit, indicating it occupies 3 division units.

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual component locking using up to 4 cylinder locks.

Description Article Number
Quadruple locking/unlocking system for individual component locking with up to 4 cylinder locks. 227232

Fixing Kit

A fixing kit for mounting the component onto a mounting plate without a DIN rail.

Description Article Number
Fixing kit for mounting the component onto a mounting plate without a DIN rail. 276618

Cylinder Lock

For locking (shackle Ø 3).

Description Article Number
For locking (shackle Ø 3) 107115

Note: Technical characteristics, dimensions, weight, construction types, and delivery possibilities are subject to change. Figures are for illustrative purposes only.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-c2-500-3-272131-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA102-C2-500-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C2-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Features include high current limiting, modular design, and ATEX/IECEx certifications.
Preview R. STAHL 8530/1-MCB-STA102-C2-500-3 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C2-500-3 circuit breaker, including explosion protection, electrical data, mechanical dimensions, and accessories. Suitable for use in Ex e enclosures.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C1-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B25-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C40-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C40-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C25-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C25-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B6-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B6-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B16-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B16-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.