R. STAHL LS Leitungsschutzschalter 8530/1-MCB-STA102-C2-500-3

Art. Nr. 272131

Product Overview

The R. STAHL 8530/1-MCB-STA102-C2-500-3 Miniature Circuit Breaker (MCB) is part of the system components range. These MCBs offer good current limiting for short circuits and high breaking capacity of 10, 15, or 25 kA, resulting in reduced stress on conductors and higher selectivity with upstream fuses. The modular design allows for 1- to 4-pole versions and nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 module widths (TE).

Key features include:

Technical Data

Explosion Protection

Parameter Value
Einsatzbereich (Zonen) 1, 2
Einsatzbereich (Zonen) Hinweis Usable in Zone 21 / 22 with protection by enclosure Ex tb / tc
IECEx Bescheinigung Gas IECEx FMG 19.0029U
IECEx Gasexplosionsschutz Ex db eb IIC Gb
ATEX Bescheinigung Gas FM19ATEX0191U
ATEX Gasexplosionsschutz II 2 G Ex db eb IIC Gb
Bescheinigungen ATEX (FM), Brazil (ULB), IECEx (FM), People's Republic of China (CQST)
Konformitätserklärungen Conformity certification (ATEX), People's Republic of China (CCC)

Electrical Data

Parameter Value
Bemessungsbetriebsspannung AC (Rated operating voltage AC) 230/400 V
Bemessungsbetriebsstrom (Rated operating current) 2 A
Frequenz (Frequency) 50/60 Hz
Bemessungsschaltvermögen (Rated breaking capacity) 10 kA
Elektrische Lebensdauer (Electrical service life) 2 x 10⁴
Mechanische Lebensdauer (Mechanical service life) 2 x 10⁴
Hilfsfunktion (Auxiliary function) 1 changeover auxiliary contact + 1 changeover fault signal contact
Bemessungsspannung 1. Hilfsfunktion AC (Rated voltage 1st auxiliary function AC) 230 V
Max. Bemessungsstrom 1. Hilfsfunktion (Max. rated current 1st auxiliary function) 2 A
2. Hilfsfunktion (2nd auxiliary function) None
Max. Spannung 2. Hilfsfunktion DC (Max. voltage 2nd auxiliary function DC) -
Auslösecharakteristik (Trip characteristic) C
Polzahl (Number of poles) 2-pole

Environmental Conditions

Parameter Value
Umgebungstemperatur (Ambient temperature) -40 °C ... 70 °C (-40 °F ... 158 °F)
Umgebungstemperatur Hinweis (Ambient temperature note) Deviating ambient temperatures based on current certificates available upon request.

Mechanical Data

Parameter Value
Schutzart (IP) (IEC 60529) (Degree of protection (IP)) IP2X
Gehäusematerial (Enclosure material) Thermoplast
Anschlussquerschnitt min. (Connection cross-section min.) 1.5 mm²
Anschlussquerschnitt max. (Connection cross-section max.) 25 mm²
Anschlussquerschnitt AWG min. (Connection cross-section AWG min.) 16 AWG
Anschlussquerschnitt AWG max. (Connection cross-section AWG max.) 4 AWG
Anschlussquerschnitt 2 min. (Connection cross-section 2 min.) 1.5 mm²
Anschlussquerschnitt 2 max. (Connection cross-section 2 max.) 10 mm²
Anschlussquerschnitt 2 AWG min. (Connection cross-section 2 AWG min.) 16 AWG
Anschlussquerschnitt 2 AWG max. (Connection cross-section 2 AWG max.) 8 AWG
Anschlussquerschnitt HIKO min. (Connection cross-section HIKO min.) 0.5 mm²
Anschlussquerschnitt HIKO max. (Connection cross-section HIKO max.) 4 mm²
Anschlussquerschnitt HIKO AWG min. (Connection cross-section HIKO AWG min.) 18 AWG
Anschlussquerschnitt HIKO AWG max. (Connection cross-section HIKO AWG max.) 14 AWG
Anzugsdrehmoment min. (Tightening torque min.) 2 N·m
Anzugsdrehmoment max. (Tightening torque max.) 3 N·m
Anschlussquerschnitt Hinweis (Connection cross-section note) 2-conductor connection (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (A cross-section difference between the upper and lower chamber of max. 1 is permitted.) The permitted combination possibilities of connection cross-sections can be found in the operating manual.
Breite (Width) 83 mm [3.27 in]
Länge (Length) 165 mm [6.5 in]
Einbautiefe (Mounting depth) 138.3 mm [5.44 in]
Gewicht (Weight) 1.3 kg [2.867 lb]

Montage / Installation

Parameter Value
Anzugsdrehmoment (Tightening torque) 2-3 N·m
Anzugsdrehmoment lbf in (Tightening torque lbf in) 17.7 ... 26.6 lbf-in
Anzugsdrehmoment Hilfskontakt (Tightening torque auxiliary contact) 0.4-0.6 Nm
Anzugsdrehmoment Hilfskontakt Ibf in (Tightening torque auxiliary contact lbf in) 3.5 ... 5.3 lbf in

Diagrams and Technical Drawings

Trip Time Curve: A graph shows trip time in seconds and minutes against multiples of the rated current (I/In). The curve is labeled 'C' for the trip characteristic. It includes a cold state limit curve and indicates that the device is usable in Zone 21 / 22 with enclosure protection Ex tb / tc.

Dimensional Drawings:

Accessories

Locking Device (4-way)

A Lock-out / Tag-out shackle for individual locking of the component using up to 4 cylinder locks.

Mounting Set

A mounting set for attaching the component to the mounting plate without a top-hat rail.

Cylinder Lock

For locking (shackle Ø 3)

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-c2-500-3-272131-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B16-500-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B16-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and installation information.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-C25-000-2: Technical Data and Features
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C25-000-2 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA102-B10-000-2 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B10-000-2 miniature circuit breaker, including electrical data, explosion protection, mechanical data, and accessories. Features good current limitation, high breaking capacity, and modular design for various applications.
Preview R. STAHL 8530/1-MCB-STA102-C25-500-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C25-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 21/22 hazardous areas.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA101-B16-500-2 - Technical Data and Features
Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA101-B16-500-2. Includes information on explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA101-C6-500-2 Miniature Circuit Breaker Datasheet
Technical datasheet for the R. STAHL 8530/1-MCB-STA101-C6-500-2 Miniature Circuit Breaker, detailing its features, technical specifications, explosion protection, electrical data, mechanical data, and accessories.