COLDZONE A2L NEXT GEN II 3 TO 22 HP AIR-COOLED CONDENSING UNITS

Product Overview and Technical Specifications

Introduction

The COLDZONE A2L NEXT GEN II series offers air-cooled condensing units ranging from 3 to 22 HP. These units are designed with improvements building on previous generations, featuring a wider selection of compressors compatible with low GWP refrigerants. They are housed in durable G90 galvanized steel enclosures with flow-through guards, highly efficient enhanced copper tube condensers, three-phase fan motors, and externally mounted service valves that are easily accessible from the cabinet exterior. The large control panel includes a swing-wide hinged door and abundant room for standard components and system accessories, along with color-coded and numbered point-to-point wiring that assists in easy service and unit maintenance.

Integral Subcooling Circuit

All A2L Next Gen II units incorporate an integral subcooling circuit. This system directs saturated liquid refrigerant from the receiver to the condenser, where it is subcooled by ambient air. This process typically achieves an average of 3°F to 5°F of subcooling, enhancing efficiency and ensuring optimal expansion device performance.

Features and Options

The following table outlines the standard, optional, and not available features for the A2L Next Gen II condensing units across different configurations (Flooded and Non-Flooded MD). A filled circle (●) indicates standard, an empty circle (○) indicates optional, and a blank cell indicates not available.

Description Flooded Non-Flooded MD
CFD CFO CFB CBD CBO CBB
All weather G90 galvanized steel painted enclosure
Removable top and side panels for ease of service
Large control panel for power and control circuits
Swing wide hinged control panel door
316 Stainless Steel cabinet
Hail / Snow Guards (Loose)
Liquid injection/Demand Cooling™ for low temperature compressors
Copeland Discus™
Copeland Scroll™
Bitzer Semi-Hermetic
High efficiency condenser with enhanced copper tubes/aluminum fins
Integral liquid subcooling circuit
3 phase condenser fan motor(s) (230V and 460V only)
Flooded head pressure control
Fan cycle control
Copper or Electro Fin® coated coil
Crankcase heater
Compressor contactor
Control transformer (460V to 230V) as required
Dual pressure control (auto reset) w/ Refflex® flexible lines
Color-coded wiring for ease of serviceability
Pump down toggle switch
External fused or non-fused disconnect
Phase loss monitor
Current sensing relay
Crankcase pressure regulator
Thru-the-door non-fused disconnect
Electric defrost kits with electronic time clocks
Electronic or mechanical air defrost time clocks
50 HZ defrost timers with or without contactors
Vertical receiver (needs less refrigerant for liquid seal)
Receiver isolation valve
Pressure relief valve (*see note below)
Base mounted liquid & suction shut-off valves (External)
Liquid line kit - piping, sealed filter drier & sight glass
Suction line piping
Additional compressor cooling for medium temp models - liquid injection, suction accumulator, and insulated suction line components and piping.
Additional compressor cooling for low temp models - insulated suction line components and piping
Oversized receiver
Heated and insulated receiver (temperature controlled and low pressure)
Sealed suction filter
Suction line accumulator
Oil separator
Replaceable core liquid and suction filters

* Note: Models in FD1 cabinets include a fusible plug for pressure relief. Models in FD2 and FD3 cabinets include a pressure relief valve.

Model Nomenclature

The model nomenclature provides a structured way to identify unit configurations:

ComponentDescription
BrandC = Coldzone
StyleF = Flooded, B = Non-Flooded
Compressor TypeD = Discus, O = Scroll, B = Bitzer
Compressor ConfigurationS = Single Horizontal (Large)
Horsepowere.g., 004 = 4 HP
Temperature RangeE = Extended Medium, L = Low, M = Medium
Refrigerant Class4A = R454A, R454C, or R455A
Voltage CodeE = 208-230/3/60, G = 460/3/60, N = 200-220/3/50, Q = 380/3/50
VintageA

Capacity Data

Detailed capacity data (BTUH) is provided for various models, refrigerants (R454A, R454C, R455A), compressor types (Discus, Scroll, Bitzer), and temperature ranges (Medium Temperature, Extended Range Medium Temperature, Low Temperature). These tables list capacities at different suction temperatures for specified ambient temperatures.

Due to the extensive nature of the capacity tables, the full data is not transcribed here. Please refer to the original document for complete tables.

Example: Medium Temperature Discus units with R454A refrigerant at 90°F ambient temperature and 40°F suction temperature range from approximately 60,360 BTUH (4 HP) to 175,200 BTUH (15 HP).

Electrical Data

Electrical data, including RLA (Rated Load Amps), LRA (Locked Rotor Amps), Condenser Fan FLA, MCA (Minimum Circuit Ampacity), MOPD (Maximum Overcurrent Protection), Electric Defrost Amps, and Evaporator Fan Amps, is provided for various models and voltage configurations (208-230V/3/60 Hz, 200-220V/3/50 Hz, and 460V/3/60 Hz, 380V/3/50 Hz).

Due to the extensive nature of the electrical data tables, the full data is not transcribed here. Please refer to the original document for complete tables.

Specifications

Specifications include connections (suction/liquid), pump down capacity for standard and oversized receivers, and approximate ship weight. This data is categorized by temperature range (Medium Temperature, Low Temperature) and compressor type (Discus, Scroll, Bitzer).

Example: Medium Temperature Discus units with 4 HP (e.g., C*DS004M4A**) have 1-3/8" suction and 5/8" liquid connections. The ship weight for standard receiver models is approximately 825 Lbs, and for oversized receiver models is 35.4-36.2 Lbs (refrigerant charge).

Due to the extensive nature of the specifications tables, the full data is not transcribed here. Please refer to the original document for complete tables.

Dimensional Drawings

Dimensional drawings are provided for cabinet sizes FD1, FD2, and FD3. These diagrams illustrate the overall dimensions (Depth, Width, Height) and key features like the control panel, suction, liquid, and HG bypass connections.

  • FD1 Cabinets: Feature a single fan and dimensions of approximately 47-3/16" (D) x 38-5/16" (W) x 36-3/8" (H).
  • FD2 Cabinets: Feature two fans and dimensions of approximately 47-3/16" (D) x 68-5/16" (W) x 36-3/8" (H).
  • FD3 Cabinets: Feature two fans and dimensions of approximately 47-3/16" (D) x 68-5/16" (W) x 43-7/8" (H).

Department of Energy Annual Walk-In Energy Factor (AWEF) Ratings

The document includes Department of Energy Annual Walk-In Energy Factor (AWEF) ratings for various models across different temperature ranges and refrigerants (R454A, R454C, R455A). For Medium Temperature units, the AWEF rating is consistently 7.6. For Low Temperature units, the AWEF rating is 3.15. A statement indicates that systems with numerical values are designed and certified for use in walk-in cooler or freezer applications.

Additional Compressor Cooling

Graphs illustrate the conditions under which additional compressor cooling is recommended. This option typically includes liquid injection (TREV), suction accumulator, and insulated suction line components and piping for medium temperature applications, or just insulated suction line components and piping for low temperature applications.

PDF preview unavailable. Download the PDF instead.

CZ-NG2-A2L-0825 Adobe PDF Library 17.0 Adobe InDesign 20.5 (Windows)

Related Documents

Preview COLDZONE A2L Next-Gen II Air-Cooled Condensing Units Specifications
Discover the COLDZONE A2L Next-Gen II series, featuring 3 to 22 HP air-cooled condensing units. This document provides comprehensive technical specifications, capacity data, electrical information, and dimensional drawings for these advanced refrigeration units.
Preview Coldzone A2L R-Series Next-Gen Minicon: 1/2 to 6 HP Air Cooled Condensing Units
Explore the Coldzone A2L R-Series Next-Gen Minicon, a line of 1/2 to 6 HP air-cooled condensing units designed for efficiency and reliability in commercial applications. Features include integral sub-cooling circuits and advanced refrigerant compatibility.
Preview Coldzone A2L R-Series Next-Gen Minicon Condensing Units: 1/2 to 6 HP
Explore the Coldzone A2L R-Series Next-Gen Minicon condensing units, offering 1/2 to 6 HP air-cooled solutions designed for commercial applications. Featuring enhanced efficiency, integral sub-cooling, and compatibility with R454A, R454C, and R455A refrigerants, these units provide robust performance and extensive features. This document details model nomenclature, specifications, capacity data, electrical information, and dimensional drawings.
Preview Coldzone A2L Medium Profile Unit Cooler: Features, Specifications, and Ratings
Detailed technical specifications, application ratings, and dimensional data for Coldzone's A2L Medium Profile Unit Coolers, designed for walk-in cooler and freezer applications. Includes information on defrost types, capacities, electrical data, and model nomenclature.
Preview COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler Specifications
The COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler is designed for small to medium walk-in cooler and freezer applications, featuring advanced performance, air and electric defrost options, high-efficiency motors, and compatibility with A2L refrigerants.
Preview Coldzone A2L Heavy Duty Unit Cooler Specifications and Data
Comprehensive technical specifications, features, application ratings, and dimensional data for the Coldzone A2L Heavy Duty Unit Cooler series, designed for medium to large walk-in cooler and freezer applications. Includes details on air defrost, electric defrost (medium and low temperature), refrigerants, electrical specifications, and optional features.
Preview COLDZONE A2L Center Mount Unit Cooler for Walk-Ins
Detailed specifications, features, and application data for COLDZONE A2L Center Mount Unit Coolers, designed for small to medium walk-in cooler and freezer applications. Includes information on air and electric defrost models, refrigerants, electrical specifications, and model nomenclature.
Preview Coldzone A2L Next Gen All-Temp Low Profile Unit Cooler
Detailed specifications, features, and application ratings for Coldzone's A2L Next Gen All-Temp Low Profile Unit Coolers, designed for walk-in coolers and freezers. Includes information on air and electric defrost models, refrigerant compatibility, and dimensional data.