Coldzone A2L Next Gen All-Temp Low Profile Unit Cooler

Designed for Walk-Ins: Small to Medium Cooler and Freezer Applications

Features

Coldzone's All-Temp unit coolers pioneered the low profile, air draw-through design, establishing the industry standard for walk-in coolers, freezers, and various other applications. The Next-Gen All-Temp models represent an advancement, featuring a new fan guard design and deep draw venturi for optimized airflow and enhanced serviceability. These units are compatible with multiple refrigerants and are available in both air and electric defrost configurations.

Sizes

Available in a wide array of sizes, these units offer capacities ranging from 2,700 to 45,900 BTUH at a 10° TD. Models with one to six fans are available, providing airflow from 800 to 4,650 CFM.

Housing

The lightweight yet durable embossed aluminum casing is engineered to prevent short cycling of the discharge air through baffled fan sections. These units meet NSF requirements and are designed for flush ceiling mounting. The top panel includes 1/2" wide slotted mounting points for straightforward installation. The drain pan features a removable drain fitting at the bottom for easy field connection and replacement. End panels slide out from the front, offering convenient access to the electrical and piping compartments for simplified maintenance.

Coil

The coils feature high-efficiency 3/8" enhanced copper hairpins, staggered and mechanically expanded into corrugated aluminum fins for maximum heat transfer and reduced refrigerant charge. Die-formed fin collars ensure consistent fin spacing. Models are available with 4 or 6 fins per inch (FPI). Sweat connections are standard.

Motors

Standard models are equipped with highly efficient Dual Speed Electronically Commutated (EC) motors, available for 115V or 208-230V. These motors comply with California Title 24 regulations and include thermal overload protection.

Fans and Fan Guards

Heavy-duty 12" aluminum fans are balanced for vibration-free operation. An improved black plastic fan guard design and deep draw venturi contribute to optimal air patterns.

Refrigerants

Low Profile Unit Coolers are optimized for multiple A2L refrigerants, including R454A, R454C, and R455A. Please specify refrigerant requirements when ordering. A separate compartment is provided for all refrigerant connections, allowing for internal mounting of expansion valves.

Electrical

Units are available for 115V and 208-230V. A spacious electrical compartment is integrated within the unit for housing electrical components, easily accessible by removing the slide-out end panel. All models are UL and cUL listed and are available for 60 Hz or 50 Hz applications.

Air Defrost Models

Air Defrost models are designed for use in coolers operating at 35°F and warmer. All components are factory wired to convenient screw-type terminal strips.

Electric Defrost Models

Electric Defrost 6 FPI models are suitable for coolers and freezers between 34°F to -20°F. Electric Defrost 4 FPI models are designed for freezers between 32°F to -20°F. Defrost heaters are mounted on the air intake side for optimal performance and easy maintenance. An additional lower heater is installed in the drain pan for fast, reliable drainage. A defrost termination fan delay thermostat manages the defrost cycle, and a heater safety thermostat prevents overheating.

Optional Features

¹ EcoNet Control Package includes: EEV, suction pressure transducer, suction entering air coil temp. thermistors, local on-board two-row backlit LCD display and push-button adjustments. (Controller replaces TXV, liquid line solenoid valve, room thermostat, defrost termination, fan delay, and time clock.)

EcoNet® Enabled Unit Coolers (Optional)

Developed in conjunction with Rheem Manufacturing, these units integrate Rheem's EcoNet technology for enhanced reliability and efficiency in walk-in coolers and freezers. Key benefits include:

The optional EcoNet Command Center provides an intuitive graphical interface for controlling up to 32 devices, offering continuous communication between system components. The remote mount display allows for programming, monitoring, and troubleshooting of EcoNet Enabled Unit Coolers remotely.

Model Nomenclature

The model nomenclature follows a configurable base model structure:

Brand Refrigerant Class Connections Fins per Inch (FPI) Defrost Type BTUH in Hundreds Unit Voltage Motor Type Vintage
C = Coldzone A2L L = Standard
U = Reverse
4 FPI
6 FPI
A = Air
E = Electric (Low Temp)
XXX A = 115/1/60
D = 208-230/1/60
E = 208-230/3/60
D = Dual Speed EC A

¹ Refrigerant and electrical connection locations differ for Next-Gen All-Temp designs. Standard connections "L" are opposite to legacy All-Temp models. Mirror connections "U" are the same as legacy All-Temp models and available only as built-to-order base units without installed options.

² EcoNet approved refrigerants: R454A, R454C, R455A.

³ EcoNet Control Package includes: EEV, suction pressure transducer, suction, entering air coil temp. thermistors; local on-board two-row LCD display and push-button adjustments. (Controller replaces TXV, room thermostat, defrost termination and fan delay, and time clock.)

Application Rating & Electrical Data

Air Defrost Models // 6 FPI

Model No. BTUH Capacity @ 25F ST and 10TD
R454A,R454C R455A
CFM No. of Fans 115V 208-230/1
Total Fan Motor Amps (1Phase)
EC Motors
MCA MOPD Total Fan Motor Amps (1Phase)
EC Motors
MCA MOPD
CAL6A050*DA 5,000 800 1 0.8 15.0 20 0.5 15.0 20
CAL6A062*DA 6,200 785 1 0.8 15.0 20 0.5 15.0 20
CAL6A081*DA 8,100 775 1 0.8 15.0 20 0.5 15.0 20
CAL6A088*DA 8,800 1,600 2 1.6 15.0 20 1.0 15.0 20
CAL6A113*DA 11,300 1,570 2 1.6 15.0 20 1.0 15.0 20
CAL6A141*DA 14,100 1,550 2 1.6 15.0 20 1.0 15.0 20
CAL6A159*DA 15,900 1,550 2 1.6 15.0 20 1.0 15.0 20
CAL6A170*DA 17,000 2,355 3 2.4 15.0 20 1.5 15.0 20
CAL6A196*DA 19,600 2,355 3 2.4 15.0 20 1.5 15.0 20
CAL6A220*DA 22,000 2,325 3 2.4 15.0 20 1.5 15.0 20
CAL6A234*DA 23,400 3,140 4 3.2 15.0 20 2.0 15.0 20
CAL6A289*DA 28,900 3,140 4 3.2 15.0 20 2.0 15.0 20
CAL6A316*DA 31,600 3,199 4 3.2 15.0 20 2.0 15.0 20
CAL6A375*DA 37,500 3,875 5 4.0 15.0 20 2.5 15.0 20
CAL6A404*DA 40,400 4,650 6 4.8 15.0 20 3.0 15.0 20
CAL6A477*DA 47,700 4,650 6 4.8 15.0 20 3.0 15.0 20

* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature.

Dual Speed EC Motors include thermal overload protection.

Electric Defrost Models // 6 FPI

Model No. BTUH Capacity @
25F ST and 10TD
R454A,R454C
R455A
CFM No. of
Fans
Total Fan
Motor Amps
(1Phase)
EC Motors
208-230V/1 208-230V/3 Heater Amps Heater
Watts
Base Model Econet Enabled Base Model Econet Enabled 1PH 3PH
CAL6E042DDA 4,200 800 1 0.5 15.0 20 15.0 20 4.9 - 1,125
CAL6E051DDA 5,100 785 1 0.5 15.0 20 15.0 20 4.9 - 1,125
CAL6E058DDA 5,800 775 1 0.5 15.0 20 15.0 20 4.9 - 1,125
CAL6E079DDA 7,900 1,600 2 1.0 15.0 20 15.0 20 9.8 - 2,250
CAL6E092DDA 9,200 1,570 2 1.0 15.0 20 15.0 20 9.8 - 2,250
CAL6E110DDA 11,000 1,550 2 1.0 15.0 20 15.0 20 9.8 - 2,250
CAL6E129DDA 12,900 1,550 2 1.0 15.0 20 15.0 20 9.8 - 2,250
CAL6E148DDA 14,800 2,355 3 1.5 15.0 20 19.9 20 14.3 - 3,300
CAL6E173DDA 17,300 2,325 3 1.5 15.0 20 19.9 20 14.3 - 3,300
CAL6E194DDA 19,400 3,140 4 2.0 15.0 20 26.1 30 19.2 - 4,425
CAL6E218DDA 21,800 3,100 4 2.0 15.0 20 26.1 30 19.2 - 4,425
CAL6E237*DA 23,700 3,925 5 2.5 15.0 20.0 32.2 35 15.0 20 24.1 14.0 5,550
CAL6E290*DA 29,000 4,710 6 3.0 15.0 20.0 38.3 40 15.0 20 29.0 16.8 6,675
CAL6E343*DA 34,300 4,650 6 3.0 15.0 20.0 38.3 40 15.0 20 29.0 16.8 6,675

* Each asterisk represents a variable character based on voltage ordered. See nomenclature on page 4 for details.

Dual Speed EC Motors include thermal overload protection.

Econet not available in 208-230/3.

Note: 208-230 ratings include 2 amp for controls on Econet Enabled units.

Electric Defrost Models // 4 FPI

Model No. BTUH Capacity @
-20F ST and
10TD
R454A,R454C
R455A
CFM No. of
Fans
Total Fan
Motor Amps
(1Phase)
EC Motors
208-230V/1 208-230V/3 Heater Amps Heater
Watts
Base Model Econet Enabled Base Model Econet Enabled 1PH 3PH
CAL4E032DDA 3,200 800 1 0.5 15.0 20 15 20 4.9 - 1,125
CAL4E040DDA 4,000 785 1 0.5 15.0 20 15 20 4.9 - 1,125
CAL4E046DDA 4,600 775 1 0.5 15.0 20 15 20 4.9 - 1,125
CAL4E061DDA 6,100 1,600 2 1.0 15.0 20 15 20 9.8 - 2,250
CAL4E076DDA 7,600 1,570 2 1.0 15.0 20 15 20 9.8 - 2,250
CAL4E099DDA 9,900 1,550 2 1.0 15.0 20 15 20 9.8 - 2,250
CAL4E114DDA 11,400 2,355 3 1.5 15.0 20 19.9 20 14.3 - 3,300
CAL4E133DDA 13,300 2,325 3 1.5 15.0 20 19.9 20 14.3 - 3,300
CAL4E150DDA 15,000 3,140 4 2.0 15.0 20 26.1 30 19.2 - 4,425
CAL4E170DDA 17,000 3,100 4 2.0 15.0 20 26.1 30 19.2 - 4,425
CAL4E184*DA 18,400 3,925 5 2.5 15.0 20.0 32.2 35 15.0 20 24.1 14.0 5,550
CAL4E232*DA 23,200 4,710 6 3.0 15.0 20.0 38.3 40 15.0 20 29.0 16.8 6,675
CAL4E281*DA 28,100 4,650 6 3.0 15.0 20.0 38.3 40 15.0 20 29.0 16.8 6,675

* Each asterisk represents a variable character based on voltage ordered. See nomenclature on page 4 for details.

Dual Speed EC Motors include thermal overload protection.

Econet not available in 208-230/3.

Note: 208-230 ratings include 2 amp for controls on Econet Enabled units.

Capacity Correction for Electric Defrost Evaporators

SST (Dew) 20 -10 -20 -30
Multiply Capacity by: 1.15 1.0375 1 0.9625

Distributor Nozzle & Expansion Valve Selections

Air Defrost Models // 6 FPI

Model No. Nozzle @ Liq. Temp. Part Numbers EEV @ Liq. Temp No. of Circuits
50°F 100°F 50°F 100°F 50°F 100°F
CAL6A050*DA - SBFTE-AAA-C SBFTE-AA-C SER-AA SER-AA 1
CAL6A062*DA - SBFTE-AAA-C SBFTE-AA-C SER-AA SER-AA 1
CAL6A081*DA 1/4,TYPE L 3/4,TYPE L SBFTE-AA-C SBFTE-A-C SER-AA SER-A 2
CAL6A088*DA 1/3,TYPE L 3/4,TYPE L SBFTE-AA-C SBFTE-A-C SER-AA SER-A 2
CAL6A113*DA 1/3,TYPE L 1,TYPE L SBFTE-AA-C SBFTE-A-C SER-A SER-A 2
CAL6A141*DA 1/2,TYPE L 1-1/2,TYPE L SBFTE-A-C SBFTE-A-C SER-A SER-A 3
CAL6A159*DA 1/2,TYPE L 1-1/2,TYPE L SBFTE-A-C SBFTE-B-C SER-A SER-B 3
CAL6A170*DA 3/4,TYPE L 1-1/2,TYPE L SBFTE-A-C SBFTE-B-C SER-A SER-B 4
CAL6A196*DA 3/4,TYPE L 1-1/2,TYPE L SBFTE-A-C SBFTE-B-C SER-B SER-B 3
CAL6A220*DA 3/4,TYPE L 2,TYPE L SBFTE-A-C SBFTE-B-C SER-B SER-B 4
CAL6A234*DA 3/4,TYPE L 2,TYPE L SBFTE-A-C SBFTE-B-C SER-B SER-B 4
CAL6A289*DA 1,TYPE L 2-1/2,TYPE L SBFTE-B-C SBFTE-C-C SER-B SER-B 6
CAL6A316*DA 1,TYPE L 2-1/2,TYPE L SBFTE-B-C SBFTE-C-C SER-B SER-C 6
CAL6A375*DA 1-1/2, TYPE L 3,TYPE L SBFTE-B-C SBFTE-C-C SER-B SER-C 8
CAL6A404*DA 1-1/2,TYPE L 3,TYPE L SBFTE-B-C SBFTE-C-C SER-B SER-C 7
CAL6A477*DA 1-1/2,TYPE L 4,TYPE L SBFTE-C-C SBFTE-C-C SER-C SER-C 8

Air Defrost Models // 6 FPI (R454A)

Model No. Nozzle @ Liq. Temp. TXV @ Liq. Temp. EEV @ Liq. Temp No. of Circuits
50°F 100°F 50°F 100°F 50°F 100°F
CAL6A050*DA - SBFVE-AAA-C SBFVE-AA-C SER-AA SER-AA 1
CAL6A062*DA - SBFVE-AA-C SBFVE-AA-C SER-AA SER-AA 1
CAL6A081*DA 1/4,TYPE L 3/4,TYPE L SBFVE-AA-C SBFVE-A-C SER-A SER-A 2
CAL6A088*DA 1/3,TYPE L 3/4,TYPE L SBFVE-AA-C SBFVE-A-C SER-A SER-A 2
CAL6A113*DA 1/3,TYPE L 1,TYPE L SBFVE-A-C SBFVE-A-C SER-A SER-A 2
CAL6A141*DA 1/2,TYPE L 1-1/2,TYPE L SBFVE-A-C SBFVE-A-C SER-A SER-B 3
CAL6A159*DA 1/2,TYPE L 1-1/2,TYPE L SBFVE-A-C SBFVE-B-C SER-A SER-B 3
CAL6A170*DA 3/4,TYPE L 1-1/2,TYPE L SBFVE-A-C SBFVE-B-C SER-B SER-B 4
CAL6A196*DA 3/4,TYPE L 2,TYPE L SBFVE-A-C SBFVE-B-C SER-B SER-B 3
CAL6A220*DA 3/4,TYPE L 2,TYPE L SBFVE-B-C SBFVE-B-C SER-B SER-B 4
CAL6A234*DA 3/4,TYPE L 2,TYPE L SBFVE-B-C SBFVE-B-C SER-B SER-B 4
CAL6A289*DA 1,TYPE L 2-1/2,TYPE L SBFVE-B-C SBFVE-C-C SER-B SER-C 6
CAL6A316*DA 1,TYPE L 3,TYPE L SBFVE-B-C SBFVE-C-C SER-B SER-C 6
CAL6A375*DA 1-1/2,TYPE L 4,TYPE L SBFVE-C-C SBFVE-C-C SER-C SER-C 8
CAL6A404*DA 1-1/2,TYPE L 4,TYPE L SBFVE-C-C SBFVE-C-C SER-C SER-C 7
CAL6A477*DA 1-1/2,TYPE L 4,TYPE L SBFVE-C-C SBFVE-C-C SER-C SER-C 8

The Distributor lines are 3/16" diameter and 14" long.

* Each asterisk represents a variable character based on voltage ordered. See nomenclature on page 4 for details.

Expansion valve selections based on +25° Suction Temp and 8°F to 12°F evaporator TD. Contact factory for operating conditions outside this range.

SBFTE Expansion valves are compatible with R454A refrigerant. SBFVE Expansion valves are compatible with R454C and R455A refrigerants.

For other valves, follow manufacturer's selection guidelines.

Base models (with no factory-mounted components) include nozzles sized for 100°F liquid, shipped loose.

Loose Components Required for A2L Isolation Controls

Amin (Minimum Allowable Room Size) Values // Air Defrost Models

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve
@ Liquid Temp
Loose CSOV
Isolation CV
10 Ft
Line Run
20 Ft
Line Run
30 Ft
Line Run
40 Ft
Line Run
50 Ft
Line Run
Size 50°F 100°F Size Description
CAL6A050*DA 17 23 28 34 40 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL6A062*DA 19 25 31 36 42 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL6A081*DA 21 27 33 38 44 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL6A088*DA 21 27 32 38 44 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL6A113*DA 25 31 37 43 49 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6A141*DA 27 33 39 45 51 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6A159*DA 29 35 41 47 53 3/8 SSOV3S130 SSOV6S130 7/8 CSOV-7S
CAL6A170*DA 29 35 41 47 53 3/8 SSOV3S130 SSOV6S130 7/8 CSOV-7S
CAL6A196*DA 36 47 58 69 80 1/2 SSOV3S130 SSOV6S140 7/8 CSOV-7S
CAL6A220*DA 42 53 64 75 86 1/2 SSOV3S130 SSOV6S140 7/8 CSOV-7S
CAL6A234*DA 39 50 61 72 84 1/2 SSOV6S140 SSOV6S140 7/8 CSOV-7S
CAL6A289*DA 42 54 65 77 88 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6A316*DA 50 61 73 84 96 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6A375*DA 57 69 81 92 104 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6A404*DA 59 71 82 94 105 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6A477*DA 65 76 88 99 111 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S

Solenoid Shut Off Valves (SSOV) operate as double duty isolation/liquid line solenoid valves and are required to ship loose and be installed in the field, outside the refrigerated space.

SSOV/CSOV (Check Shut Off Valves) Selection Criteria: Maximum 10 Foot Line Rise, 100 Foot Line Run, 1:1 Condensing Unit/Evaporator.

Contact applications for additional lengths or design considerations.

Amin values calculated using operating conditions included in UL 60335-2-89 101.DVU.1.2 and standard connection sizes (liquid and suction).

Amin values provided for 10 Ft, 20 Ft, 30 Ft, 40 Ft and 50 Ft line lengths.

Contact applications for additional lengths or design considerations.

Amin values intended to determine compliance with UL 2-89 and is NOT for charging calculations.

Loose Components Required for A2L Isolation Controls

Amin (Minimum Allowable Room Size) Values // Electric Defrost Models // 6 FPI

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve
@ Liquid Temp
Loose CSOV
Isolation CV
10 Ft
Line Run
20 Ft
Line Run
30 Ft
Line Run
40 Ft
Line Run
50 Ft
Line Run
Size 50°F 100°F Size Description
CAL6E042DDA 17 22 28 33 39 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL6E051DDA 19 25 30 36 42 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E058DDA 21 27 32 38 44 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E079DDA 21 26 32 38 43 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E092DDA 25 30 36 42 47 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E110DDA 26 32 38 44 50 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E129DDA 29 35 40 46 52 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E148DDA 31 36 42 48 54 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E173DDA 41 52 63 74 85 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6E194DDA 41 52 63 74 85 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6E218DDA 48 60 71 82 93 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E237*DA 46 58 69 80 91 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E290*DA 52 63 74 85 97 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E343*DA 62 74 85 96 107 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S

Solenoid Shut Off Valves (SSOV) operate as double duty isolation/liquid line solenoid valves and are required to ship loose and be installed in the field, outside the refrigerated space.

SSOV/CSOV (Check Shut Off Valves) Selection Criteria: Maximum 10 Foot Line Rise, 100 Foot Line Run, 1:1 Condensing Unit/Evaporator.

Contact applications for additional lengths or design considerations.

Amin values calculated using operating conditions included in UL 60335-2-89 101.DVU.1.2 and standard connection sizes (liquid and suction).

Amin values provided for 10 Ft, 20 Ft, 30 Ft, 40 Ft and 50 Ft line lengths.

Contact applications for additional lengths or design considerations.

Amin values intended to determine compliance with UL 2-89 and is NOT for charging calculations.

Loose Components Required for A2L Isolation Controls

Amin (Minimum Allowable Room Size) Values // Electric Defrost Models // 4 FPI

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve
@ Liquid Temp
Loose CSOV
Isolation CV
10 Ft
Line Run
20 Ft
Line Run
30 Ft
Line Run
40 Ft
Line Run
50 Ft
Line Run
Size 50°F 100°F Size Description
CAL4E032DDA 17 22 28 33 39 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL4E040DDA 19 24 30 35 41 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL4E046DDA 21 27 32 38 44 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E061DDA 21 26 32 38 43 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E076DDA 25 30 36 42 47 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E099DDA 28 34 40 45 51 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E114DDA 31 36 42 48 54 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E133DDA 36 42 48 54 60 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E150DDA 36 42 48 53 59 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E170DDA 43 49 55 61 66 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E184*DA 46 57 68 79 90 1/2 SSOV3S130 SSOV6S140 11/8 CSOV-9S
CAL4E232*DA 52 63 74 85 97 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL4E281*DA 62 74 85 96 107 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S

Solenoid Shut Off Valves (SSOV) operate as double duty isolation/liquid line solenoid valves and are required to ship loose and be installed in the field, outside the refrigerated space.

SSOV/CSOV (Check Shut Off Valves) Selection Criteria: Maximum 10 Foot Line Rise, 100 Foot Line Run, 1:1 Condensing Unit/Evaporator.

Contact applications for additional lengths or design considerations.

Amin values calculated using operating conditions included in UL 60335-2-89 101.DVU.1.2 and standard connection sizes (liquid and suction).

Amin values provided for 10 Ft, 20 Ft, 30 Ft, 40 Ft and 50 Ft line lengths.

Contact applications for additional lengths or design considerations.

Amin values intended to determine compliance with UL 2-89 and is NOT for charging calculations.

Loose Components Required for A2L Isolation Controls

Amin (Minimum Allowable Room Size) Values // Electric Defrost Models // 6 FPI

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve
@ Liquid Temp
Loose CSOV
Isolation CV
10 Ft
Line Run
20 Ft
Line Run
30 Ft
Line Run
40 Ft
Line Run
50 Ft
Line Run
Size 50°F 100°F Size Description
CAL6E042DDA 15 20 25 29 34 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL6E051DDA 17 22 27 32 37 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E058DDA 18 23 29 34 39 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E079DDA 18 23 28 33 38 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E092DDA 22 27 32 37 42 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E110DDA 23 28 33 39 44 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E129DDA 25 30 36 41 46 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E148DDA 27 32 37 43 48 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E173DDA 36 46 56 65 75 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6E194DDA 36 46 56 65 75 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6E218DDA 43 53 63 73 82 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E237*DA 41 51 61 71 81 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E290*DA 46 56 66 75 85 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E343*DA 55 65 75 85 95 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S

Solenoid Shut Off Valves (SSOV) operate as double duty isolation/liquid line solenoid valves and are required to ship loose and be installed in the field, outside the refrigerated space.

SSOV/CSOV (Check Shut Off Valves) Selection Criteria: Maximum 10 Foot Line Rise, 100 Foot Line Run, 1:1 Condensing Unit/Evaporator.

Contact applications for additional lengths or design considerations.

Amin values calculated using operating conditions included in UL 60335-2-89 101.DVU.1.2 and standard connection sizes (liquid and suction).

Amin values provided for 10 Ft, 20 Ft, 30 Ft, 40 Ft and 50 Ft line lengths.

Contact applications for additional lengths or design considerations.

Amin values intended to determine compliance with UL 2-89 and is NOT for charging calculations.

Loose Components Required for A2L Isolation Controls

Amin (Minimum Allowable Room Size) Values // Electric Defrost Models // 4 FPI

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve
@ Liquid Temp
Loose CSOV
Isolation CV
10 Ft
Line Run
20 Ft
Line Run
30 Ft
Line Run
40 Ft
Line Run
50 Ft
Line Run
Size 50°F 100°F Size Description
CAL4E032DDA 17 22 28 33 39 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL4E040DDA 19 24 30 35 41 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL4E046DDA 21 27 32 38 44 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E061DDA 21 26 32 38 43 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E076DDA 25 30 36 42 47 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E099DDA 28 34 40 45 51 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL4E114DDA 31 36 42 48 54 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E133DDA 36 42 48 54 60 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E150DDA 36 42 48 53 59 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E170DDA 43 49 55 61 66 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL4E184*DA 46 57 68 79 90 1/2 SSOV3S130 SSOV6S140 11/8 CSOV-9S
CAL4E232*DA 52 63 74 85 97 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL4E281*DA 62 74 85 96 107 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S

Solenoid Shut Off Valves (SSOV) operate as double duty isolation/liquid line solenoid valves and are required to ship loose and be installed in the field, outside the refrigerated space.

SSOV/CSOV (Check Shut Off Valves) Selection Criteria: Maximum 10 Foot Line Rise, 100 Foot Line Run, 1:1 Condensing Unit/Evaporator.

Contact applications for additional lengths or design considerations.

Amin values calculated using operating conditions included in UL 60335-2-89 101.DVU.1.2 and standard connection sizes (liquid and suction).

Amin values provided for 10 Ft, 20 Ft, 30 Ft, 40 Ft and 50 Ft line lengths.

Contact applications for additional lengths or design considerations.

Amin values intended to determine compliance with UL 2-89 and is NOT for charging calculations.

Loose Components Required for A2L Isolation Controls

Amin (Minimum Allowable Room Size) Values // Electric Defrost Models // 6 FPI

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve
@ Liquid Temp
Loose CSOV
Isolation CV
10 Ft
Line Run
20 Ft
Line Run
30 Ft
Line Run
40 Ft
Line Run
50 Ft
Line Run
Size 50°F 100°F Size Description
CAL6E042DDA 15 20 25 29 34 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAL6E051DDA 17 22 27 32 37 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E058DDA 18 23 29 34 39 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E079DDA 18 23 28 33 38 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E092DDA 22 27 32 37 42 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAL6E110DDA 23 28 33 39 44 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E129DDA 25 30 36 41 46 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E148DDA 27 32 37 43 48 3/8 SSOV3S130 SSOV3S130 11/8 CSOV-9S
CAL6E173DDA 36 46 56 65 75 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6E194DDA 36 46 56 65 75 1/2 SSOV6S140 SSOV6S140 11/8 CSOV-9S
CAL6E218DDA 43 53 63 73 82 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E237*DA 41 51 61 71 81 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E290*DA 46 56 66 75 85 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S
CAL6E343*DA 55 65 75 85 95 1/2 SSOV6S140 SSOV6S140 13/8 CSOV-11S

Solenoid Shut Off Valves (SSOV) operate as double duty isolation/liquid line solenoid valves and are required to ship loose and be installed in the field, outside the refrigerated space.

SSOV/CSOV (Check Shut Off Valves) Selection Criteria: Maximum 10 Foot Line Rise, 100 Foot Line Run, 1:1 Condensing Unit/Evaporator.

Contact applications for additional lengths or design considerations.

Amin values calculated using operating conditions included in UL 60335-2-89 101.DVU.1.2 and standard connection sizes (liquid and suction).

Amin values provided for 10 Ft, 20 Ft, 30 Ft, 40 Ft and 50 Ft line lengths.

Contact applications for additional lengths or design considerations.

Amin values intended to determine compliance with UL 2-89 and is NOT for charging calculations.

Specifications // Air Defrost Models

Model No. Fans Refrigerant Connections
Liquid
Suction No. of
Hanger Slot
Locations
Dimensions (Inches) Estimated
Shipping
Weight (Lbs.)
A B C D
CAL6A050*DA 1 3/8 5/8 2 17-1/4 - - 27-1/8 41
CAL6A062*DA 1 3/8 5/8 2 17-1/4 - - 27-1/8 44
CAL6A081*DA 1 3/8 5/8 2 17-1/4 - - 27-1/8 47
CAL6A088*DA 2 3/8 5/8 2 33-1/4 - - 43-5/8 52
CAL6A113*DA 2 3/8 7/8 2 33-1/4 - - 43-5/8 55
CAL6A141*DA 2 3/8 7/8 2 33-1/4 - - 43-5/8 58
CAL6A159*DA 2 3/8 7/8 2 33-1/4 - - 43-5/8 62
CAL6A170*DA 3 3/8 7/8 2 49-1/4 - - 60-1/8 72
CAL6A196*DA 3 1/2 7/8 2 49-1/4 - - 60-1/8 78
CAL6A220*DA 3 1/2 7/8 2 49-1/4 - - 60-1/8 85
CAL6A234*DA 4 1/2 7/8 2 65-1/4 - - 76-5/8 115
CAL6A289*DA 4 1/2 11/8 2 65-1/4 - - 76-5/8 124
CAL6A316*DA 4 1/2 11/8 2 65-1/4 - - 76-5/8 147
CAL6A375*DA 5 1/2 11/8 3 81-1/4 32-5/8 48-5/8 93-1/8 218
CAL6A404*DA 6 1/2 11/8 3 97-1/4 48-5/8 48-5/8 109-5/8 257
CAL6A477*DA 6 1/2 11/8 3 97-1/4 48-5/8 48-5/8 109-5/8 262

* Each asterisk represents a variable character based on voltage ordered. See nomenclature on page 4 for details.

For dimensional distance between hanger slots, consult model's corresponding dimensional drawing. Hanger slots are 3/8" deep x 1" wide.

Drain connection is 1-1/4" NPT for all models.

For shipping dimensions and weights, see the Shipping information included with each dimensional drawing.

Specifications // Electric Defrost Models

Model No. Fans Refrigerant Connections
Liquid
Suction No. of
Hanger Slot
Locations
Dimensions (Inches) Estimated
Shipping
Weight (Lbs.)
A B C D
CAL6E042DDA 1 3/8 5/8 2 17-1/4 - - 27-1/8 41
CAL6E051DDA 1 3/8 7/8 2 17-1/4 - - 27-1/8 44
CAL6E058DDA 1 3/8 7/8 2 17-1/4 - - 27-1/8 47
CAL6E079DDA 2 3/8 7/8 2 33-1/4 - - 43-5/8 52
CAL6E092DDA 2 3/8 7/8 2 33-1/4 - - 43-5/8 55
CAL6E110DDA 2 3/8 11/8 2 33-1/4 - - 43-5/8 58
CAL6E129DDA 2 3/8 11/8 2 33-1/4 - - 43-5/8 62
CAL6E148DDA 3 3/8 11/8 2 49-1/4 - - 60-1/8 78
CAL6E173DDA 3 1/2 11/8 2 49-1/4 - - 60-1/8 85
CAL6E194DDA 4 1/2 11/8 2 65-1/4 - - 76-5/8 124
CAL6E218DDA 4 1/2 13/8 2 65-1/4 - - 76-5/8 147
CAL6E237*DA 5 1/2 13/8 3 81-1/4 32-5/8 48-5/8 93-1/8 195
CAL6E290*DA 6 1/2 13/8 3 97-1/4 48-5/8 48-5/8 109-5/8 238
CAL6E343*DA 6 1/2 13/8 3 97-1/4 48-5/8 48-5/8 109-5/8 262

* Each asterisk represents a variable character based on voltage ordered. See nomenclature on page 4 for details.

For dimensional distance between hanger slots, consult model's corresponding dimensional drawing. Hanger slots are 3/8" deep x 1" wide.

Drain connection is 1-1/4" NPT for all models.

For shipping dimensions and weights, see the Shipping information included with each dimensional drawing.

Specifications // Electric Defrost Models // 4 FPI

Model No. Fans Refrigerant Connections
Liquid
Suction No. of
Hanger Slot
Locations
Dimensions (Inches) Estimated
Shipping
Weight (Lbs.)
A B C D
CAL4E032DDA 1 3/8 5/8 2 17-1/4 - - 27-1/8 40
CAL4E040DDA 1 3/8 5/8 2 17-1/4 - - 27-1/8 42
CAL4E046DDA 1 3/8 7/8 2 17-1/4 - - 27-1/8 46
CAL4E061DDA 2 3/8 7/8 2 33-1/4 - - 43-5/8 50
CAL4E076DDA 2 3/8 7/8 2 33-1/4 - - 43-5/8 52
CAL4E099DDA 2 3/8 7/8 2 33-1/4 - - 43-5/8 55
CAL4E114DDA 3 3/8 11/8 2 49-1/4 - - 60-1/8 79
CAL4E133DDA 3 3/8 11/8 2 49-1/4 - - 60-1/8 84
CAL4E150DDA 4 3/8 11/8 2 65-1/4 - - 76-5/8 124
CAL4E170DDA 4 3/8 11/8 2 65-1/4 - - 76-5/8 144
CAL4E184*DA 5 1/2 11/8 3 81-1/4 32-5/8 48-5/8 93-1/8 191
CAL4E232*DA 6 1/2 13/8 3 97-1/4 48-5/8 48-5/8 109-5/8 257
CAL4E281*DA 6 1/2 13/8 3 97-1/4 48-5/8 48-5/8 109-5/8 262

* Each asterisk represents a variable character based on voltage ordered. See nomenclature on page 4 for details.

For dimensional distance between hanger slots, consult model's corresponding dimensional drawing. Hanger slots are 3/8" deep x 1" wide.

Drain connection is 1-1/4" NPT for all models.

For shipping dimensions and weights, see the Shipping information included with each dimensional drawing.

Dimensional Drawings

Figure 1 - Single Fan

Front View:

Diagram showing a single fan unit with dimensions labeled:

Side View:

Diagram showing the side profile of the unit with dimensions labeled.

Figure 2 - Two Fan

Front View:

Diagram showing a two-fan unit with dimensions labeled:

Side View:

Diagram showing the side profile of the unit with dimensions labeled.

Figure 3 - Three Fan

Front View:

Diagram showing a three-fan unit with dimensions labeled:

Side View:

Diagram showing the side profile of the unit with dimensions labeled.

Figure 4 - Four Fan

Front View:

Diagram showing a four-fan unit with dimensions labeled:

Side View:

Diagram showing the side profile of the unit with dimensions labeled.

Figure 5 - Five Fan

Front View:

Diagram showing a five-fan unit with dimensions labeled:

Side View:

Diagram showing the side profile of the unit with dimensions labeled.

Figure 6 - Six Fan

Front View:

Diagram showing a six-fan unit with dimensions labeled:

Side View:

Diagram showing the side profile of the unit with dimensions labeled.

Measurements noted on the end view drawing are the same for all units. All mounting holes are 3/8" diameter. All dimensions are in inches.

Evaporator Application Ratings

Coldzone's published application ratings are a guideline for proper equipment selection, accounting for true operating conditions. These ratings are higher than the net capacity used for DOE ratings (AWEF). The AWEF is calculated using dry coil capacity and daily evaporator power consumption, including fan and defrost power. DOE test conditions (10°F evaporator/SST, <50% RH, 96°F liquid temp) create a uniform test method but may result in oversized equipment if used for selection.

Cooler Models

Base Model Number Defrost Type FPI AWEF
CAL6A050*DA Air Defrost 6 9.00
CAL6A062*DA Air Defrost 6 9.00
CAL6A081*DA Air Defrost 6 9.00
CAL6A088*DA Air Defrost 6 9.00
CAL6A113*DA Air Defrost 6 9.00
CAL6A141*DA Air Defrost 6 9.00
CAL6A159*DA Air Defrost 6 9.00
CAL6A177*DA Air Defrost 6 9.00
CAL6A196*DA Air Defrost 6 9.00
CAL6A220*DA Air Defrost 6 9.00
CAL6A234*DA Air Defrost 6 9.00
CAL6A289*DA Air Defrost 6 9.00
CAL6A316*DA Air Defrost 6 9.00
CAL6A375*DA Air Defrost 6 9.00
CAL6A404*DA Air Defrost 6 9.00
CAL6A477*DA Air Defrost 6 9.00
CAL6E042DDA Electric Defrost 6 9.00
CAL6E051DDA Electric Defrost 6 9.00
CAL6E058DDA Electric Defrost 6 9.00
CAL6E079DDA Electric Defrost 6 9.00
CAL6E092DDA Electric Defrost 6 9.00
CAL6E110DDA Electric Defrost 6 9.00
CAL6E129DDA Electric Defrost 6 9.00
CAL6E148DDA Electric Defrost 6 9.00
CAL6E173DDA Electric Defrost 6 9.00
CAL6E194DDA Electric Defrost 6 9.00
CAL6E218DDA Electric Defrost 6 9.00
CAL6E237*DA Electric Defrost 6 9.00
CAL6E290*DA Electric Defrost 6 9.00
CAL6E343*DA Electric Defrost 6 9.00

* Each asterisk represents a variable character based on voltage ordered. See nomenclature on page 4 for details.

1. If the model has a numerical value in the table above, the following statement applies: "The refrigeration system is designed and certified for use in walk-in cooler applications."

Freezer Models

Base Model Number Defrost Type FPI AWEF
CAL6E042DDA Electric Defrost 6 3.95
CAL6E051DDA Electric Defrost 6 3.98
CAL6E058DDA Electric Defrost 6 3.99
CAL6E079DDA Electric Defrost 6 4.00
CAL6E092DDA Electric Defrost 6 4.04
CAL6E110DDA Electric Defrost 6 4.06
CAL6E129DDA Electric Defrost 6 4.09
CAL6E148DDA Electric Defrost 6 4.12
CAL6E173DDA Electric Defrost 6 4.15
CAL6E194DDA Electric Defrost 6 4.15
CAL6E218DDA Electric Defrost 6 4.15
CAL6E237*DA Electric Defrost 6 4.15
CAL6E290*DA Electric Defrost 6 4.15
CAL6E343*DA Electric Defrost 6 4.15
CAL4E032DDA Electric Defrost 4 3.95
CAL4E040DDA Electric Defrost 4 3.97
CAL4E046DDA Electric Defrost 4 3.98
CAL4E061DDA Electric Defrost 4 3.99
CAL4E076DDA Electric Defrost 4 4.02
CAL4E099DDA Electric Defrost 4 4.05
CAL4E114DDA Electric Defrost 4 4.08
CAL4E133DDA Electric Defrost 4 4.12
CAL4E150DDA Electric Defrost 4 4.13
CAL4E170DDA Electric Defrost 4 4.15
CAL4E184*DA Electric Defrost 4 4.15
CAL4E232*DA Electric Defrost 4 4.15
CAL4E281*DA Electric Defrost 4 4.15

2. If the model has a numerical value in the table above, the following statement applies: "The refrigeration system is designed and certified for use in walk-in freezer applications."

PDF preview unavailable. Download the PDF instead.

CZ-RLX-A2L-0725 Adobe PDF Library 17.0 Adobe InDesign 20.3 (Windows)

Related Documents

Preview COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler Specifications
The COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler is designed for small to medium walk-in cooler and freezer applications, featuring advanced performance, air and electric defrost options, high-efficiency motors, and compatibility with A2L refrigerants.
Preview COLDZONE A2L Medium Profile Unit Cooler: Specifications & Applications
Discover the COLDZONE A2L Medium Profile Unit Cooler, an efficient evaporator solution for walk-in coolers and freezers. This document details technical specifications, application ratings, electrical data, and dimensional drawings for various defrost types and refrigerants.
Preview Coldzone A2L Medium Profile Unit Cooler: Features, Specifications, and Ratings
Detailed technical specifications, application ratings, and dimensional data for Coldzone's A2L Medium Profile Unit Coolers, designed for walk-in cooler and freezer applications. Includes information on defrost types, capacities, electrical data, and model nomenclature.
Preview Coldzone A2L Heavy Duty Unit Cooler Specifications and Data
Comprehensive technical specifications, features, application ratings, and dimensional data for the Coldzone A2L Heavy Duty Unit Cooler series, designed for medium to large walk-in cooler and freezer applications. Includes details on air defrost, electric defrost (medium and low temperature), refrigerants, electrical specifications, and optional features.
Preview Coldzone A2L Warehouse Unit Coolers: Specifications and Applications
Explore the Coldzone A2L Warehouse Unit Cooler series, designed for medium to large walk-in cooler and freezer applications. Features include air and electric defrost options, various BTUH capacities, and compatibility with refrigerants R454A, R454C, and R455A.
Preview COLDZONE A2L Center Mount Unit Cooler for Walk-Ins
Detailed specifications, features, and application data for COLDZONE A2L Center Mount Unit Coolers, designed for small to medium walk-in cooler and freezer applications. Includes information on air and electric defrost models, refrigerants, electrical specifications, and model nomenclature.