COLDZONE A2L CENTER MOUNT UNIT COOLER

Walk-Ins: Small to Medium Cooler and Freezer Applications

FEATURES

Center Mount Unit Coolers are designed for use in walk-in coolers and freezers with very low headroom clearance. Units mount flush to the ceiling to provide extra storage space. Features include two-way air flow for even circulation and temperature, easy serviceability, usability with multiple refrigerants, and are available in air and electric defrost models.

SIZES

Available with capacities ranging from 4,500 to 33,700 BTUH at a 10°TD. One through five fan models are available with air flow spanning a range of 572 to 3,150 CFM.

HOUSING

The embossed aluminum casing is lightweight yet durable. Each fan section is baffled to prevent short cycling of the discharge air. Units mount flush to the ceiling and are compliant with NSF requirements. The top panel contains 3/8" mounting holes for simplified installation. The housing is sloped for efficient condensate draining. A uniquely shaped control access cover allows for easy access for service in confined spaces.

COIL

Copper hairpins consist of high efficiency 3/8" enhanced copper tubes, staggered and mechanically expanded into corrugated aluminum fins for maximum heat transfer and reduced refrigerant charge. Die formed fin collars provide even fin spacing. Medium temperature models have 6 fins per inch (FPI) and low temperature models have 6 and 4 FPI. Sweat connections are standard on all models.

MOTORS

Standard models feature highly efficient Dual Speed Electronically Commutated (EC) motors. Available for 115V or 208-230V/1 and compliant with California Title 24 regulations. All motors include thermal overload protection.

FANS AND FAN GUARDS

Aluminum 12" fans are balanced for vibration-free operation. Improved black plastic fan guard design and deep draw venturi achieve optimal air pattern. Fan motors and blades can be easily accessed by removing the fan guard.

REFRIGERANTS

Center Mount Unit Coolers are optimized for multiple A2L refrigerants including R454A, R454C, and R455A. Please specify refrigerant requirements when ordering. A separate compartment is provided for all refrigerant connections, allowing for internal mounting of expansion valves.

AIR DEFROST

Air Defrost models are designed for use in coolers down to 35°F. All Air Defrost models are 6 FPI.

ELECTRIC DEFROST

Electric Defrost 6 FPI models are designed for use in coolers and freezers down to -10°F, and 4 FPI models are designed for use in freezers between 32°F to -10°F.

ELECTRICAL

Available for 115V and 208-230V/1. All components are factory wired to terminal strips and are UL and cUL listed.

OPTIONAL FEATURES

MODEL NOMENCLATURE

Brand Refrigerant Class Style Fins per Inch (FPI) Defrost Type BTUH by Hundreds Unit Voltage Motor Type Vintage
C = Coldzone A2L E = Center Mount 4 FPI A = Air XXX A = 115/1/60 D = Dual Speed EC A
6 FPI E = Electric D = 208-230/1/60

¹ EcoNet Control Package includes: EEV; suction pressure transducer; suction, entering air coil temp. thermistors; local on-board two-row LCD display and push-button adjustments. (Controller replaces TXV, liquid line solenoid valve, room thermostat, defrost termination and fan delay, and time clock.) EcoNet approved refrigerants are: RR454A, R454C, R455A.

^50 Hz available. Contact Factory for additional information.

ECONET® ENABLED UNIT COOLERS (OPTIONAL)

Developed in conjunction with Rheem Manufacturing specifically for walk-in coolers and freezers, it builds in the reliability and efficiency of Rheem's EcoNet technology.

Optional EcoNet Command Center with intuitive graphical interface controls up to 32 devices (including the Command Center) through one display, provides continuous communication between system components, and the remote mount display allows for EcoNet Enabled Unit Coolers to be programmed, monitored and troubleshot outside of the space being cooled.

APPLICATION RATING & ELECTRICAL DATA

AIR DEFROST MODELS

Model No. BTUH Capacity @ 25°F ST & 10TD CFM No. of Fans 115V/1 208-230V/1
R454A,R454C R455A Total Fan Amps MCA MOPD Total Fan Amps MCA MOPD
CAE6A051*DA 5,100 572 1 0.8 15.0 20 0.5 15.0 20
CAE6A085*DA 8,500 1,204 2 1.6 15.0 20 1.0 15.0 20
CAE6A103*DA 10,300 1,144 2 1.6 15.0 20 1.0 15.0 20
CAE6A128*DA 12,800 1,806 3 2.4 15.0 20 1.5 15.0 20
CAE6A157*DA 15,700 1,716 3 2.4 15.0 20 1.5 15.0 20
CAE6A173*DA 17,300 2,408 4 3.2 15.0 20 2.0 15.0 20
CAE6A207*DA 20,700 2,288 4 3.2 15.0 20 2.0 15.0 20
CAE6A249*DA 24,900 2,860 5 4.0 15.0 20 2.5 15.0 20
CAE6A316*DA 31,600 3,150 5T 4.0 15.0 20 2.5 15.0 20

*Asterisks represents variable character based on voltage ordered. See nomenclature on page 3.

Dual Speed EC Motors include thermal overload protection.

ELECTRIC DEFROST MODELS

Model No. BTUH Capacity @ -20°F ST & 10TD CFM No. of Fans Total Fan Amps Base Model Econet Enabled Heater Amps Heater Watts
R454A,R454C R455A MCA MOPD MCA MOPD MCA MOPD
CAE6E045DDA 4,500 602 1 0.5 15.0 20.0 15.0 20.0 15.0 20.0 3.3 750
CAE6E054DDA 5,400 572 1 0.5 15.0 20.0 15.0 20.0 15.0 20.0 3.3 750
CAE6E090DDA 9,000 1, 204 2 1.0 15.0 20.0 15.0 20.0 15.0 20.0 6.5 1,500
CAE6E107DDA 10,700 1,144 2 1.0 15.0 20.0 15.0 20.0 15.0 20.0 6.5 1,500
CAE6E129DDA 12,900 1,806 3 1.5 15.0 20.0 15.0 20.0 15.0 20.0 9.8 2,250
CAE6E149DDA 14,900 1,716 3 1.5 15.0 20.0 15.0 20.0 15.0 20.0 9.8 2,250
CAE6E160DDA 16,000 2,408 4 2.0 15.0 20.0 18.8 20.0 18.8 20.0 13.0 3,000
CAE6E217DDA 21,700 2,288 4 2.0 15.0 20.0 18.8 20.0 18.8 20.0 13.0 3,000
CAE6E265DDA 26,500 2,860 5 2.5 15.0 20.0 22.4 25.0 22.4 25.0 16.3 3,750
CAE6E337DDA 33,700 3,150 5T 2.5 15.0 20.0 33.0 35.0 33.0 35.0 24.4 5,620
Capacity Correction for Electric Defrost Evaporators
S.S.T. (Dew) Multiply Capacity by:
20 1.15
0 1.075
-10 1.0375
-20 1

Dual Speed EC Motors include thermal overload protection.

208-230 ratings include 2 AMP for controls on Econet Enabled units.

1AMP Minimum allowed for Econet control circuit.

Econet Enabled units are not powered by the condensing unit so defrost heaters are incorporated into shown MCA/MOPD.

DISTRIBUTOR NOZZLES & EXPANSION VALVES SELECTIONS

AIR DEFROST MODELS

Model No. Nozzle @ Liquid Temp TXV @ Liquid Temp EEV @ Liquid Temp No. of Circuits
50°F 100°F 50°F 100°F 50°F 100°F
CAE6A051*DA 1/6, TYPE L 1/2,TYPE L SBFTE-AAA-C SBFTE-AA-C SER-AA SER-AA 2
CAE6A085*DA 1/4,TYPE L 3/4,TYPE L SBFTE-AA-C SBFTE-AA-C SER-A SER-A 2
CAE6A103*DA 1/3, TYPE L 3/4,TYPE L SBFTE-AA-C SBFTE-A-C SER-A SER-A 2
CAE6A128*DA 1/3, TYPE L 1, TYPE L SBFTE-A-C SBFTE-A-C SER-A SER-A 4
CAE6A157*DA 1/2,TYPE L 1-1/2, TYPE L SBFTE-A-C SBFTE-A-C SER-A SER-B 4
CAE6A173*DA 1/2,TYPE L 1-1/2, TYPE L SBFTE-A-C SBFTE-A-C SER-A SER-B 4
CAE6A207*DA 3/4,TYPE L 1-1/2, TYPE L SBFTE-A-C SBFTE-B-C SER-A SER-B 4
CAE6A249*DA 3/4,TYPE L 2, TYPE L SBFTE-B-C SBFTE-B-C SER-B SER-B 8
CAE6A316*DA 1, TYPE L 2-1/2, TYPE L SBFTE-B-C SBFTE-B-C SER-B SER-C 6

ELECTRIC DEFROST MODELS

Model No. Nozzle @ Liquid Temp TXV @ Liquid Temp EEV @ Liquid Temp No. of Circuits
50°F 100°F 50°F 100°F 50°F 100°F
CAE6E045DDA 1/4,TYPE L 1/2,TYPE L SBFTE-AA-Z SBFTE-AA-Z SER-AA SER-AA 2
CAE6E054DDA 1/3, TYPE L 3/4,TYPE L SBFTE-AA-Z SBFTE-AA-Z SER-AA SER-AA 2
CAE6E090DDA 1/2,TYPE L 3/2, TYPE L SBFTE-A-Z SBFTE-A-Z SER-A SER-A 4
CAE6E107DDA 3/4,TYPE L 3/2, TYPE L SBFTE-A-Z SBFTE-A-Z SER-A SER-A 4
CAE6E129DDA 3/4,TYPE L 3/2, TYPE L SBFTE-A-Z SBFTE-B-Z SER-A SER-A 4
CAE6E149DDA 1, TYPE L 2, TYPE L SBFTE-A-Z SBFTE-B-Z SER-A SER-B 4
CAE6E160DDA 1, TYPE L 2, TYPE L SBFTE-A-Z SBFTE-B-Z SER-A SER-B 4
CAE6E217DDA 1-1/2, TYPE L 1-1/2, TYPE L SBFTE-B-Z SBFTE-C-Z SER-B SER-B 8
CAE6E265DDA 2, TYPE L 3, TYPE L SBFTE-B-Z SBFTE-C-Z SER-B SER-B 8
CAE6E337DDA 1-1/2, TYPE G 4, TYPE G SBFTE-C-Z SBFTE-C-Z SER-B SER-C 12

The Distributor lines are 3/16" diameter and 18" long.

Expansion valve selections based on -20 Suction Temp and 8F to 12F evaporator TD. Contact factory for operating conditions outside this range.

Do not use pressure limiting TXV's when the condensing unit includes a CPR valve.

SBFTE Expansion valves are compatible with R454A refrigerant. SBFVE Expansion valves are compatible with R454C and R455A refrigerants.

For other valves, follow manufacturers selection guidelines.

Base models (with no factory-mounted components) include nozzles sized for 100F liquid, shipped loose.

LOOSE COMPONENTS REQUIRED FOR A2L ISOLATION CONTROLS

AMIN (MINIMUM ALLOWABLE ROOM SIZE) VALUES // AIR DEFROST MODELS

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve @ Liquid Temp Loose CSOV Isolation CV
10 Ft Line Run 20 Ft Line Run 30 Ft Line Run 40 Ft Line Run 50 Ft Line Run Size 50°F 100°F Size Description
CAE6A051*DA 20 26 31 37 43 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAE6A085*DA 23 29 34 40 46 3/8 SSOV3S130 SSOV3S130 5/8 CSOV-5S
CAE6A103*DA 26 32 38 44 50 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAE6A128*DA 28 34 40 46 52 3/8 SSOV3S130 SSOV6S130 7/8 CSOV-7S
CAE6A157*DA 33 39 45 51 57 3/8 SSOV3S130 SSOV6S130 7/8 CSOV-7S
CAE6A173*DA 33 39 45 51 57 3/8 SSOV3S130 SSOV6S130 7/8 CSOV-7S
CAE6A207*DA 39 45 51 57 63 3/8 SSOV6S130 SSOV6S130 7/8 CSOV-7S
CAE6A249*DA 51 63 74 86 97 1/2 SSOV6S140 SSOV6S140 1-1/8 CSOV-9S
CAE6A316*DA 67 78 90 101 113 1/2 SSOV6S140 SSOV6S140 1-1/8 CSOV-9S

AMIN (MINIMUM ALLOWABLE ROOM SIZE) VALUES // ELECTRIC DEFROST MODELS

Model No. Amin Values (Ft2) Loose SSOV Isolation Valve @ Liquid Temp Loose CSOV Isolation CV
10 Ft Line Run 20 Ft Line Run 30 Ft Line Run 40 Ft Line Run 50 Ft Line Run Size 50°F 100°F Size Description
CAE6E045DDA 18 24 29 35 41 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAE6E054DDA 20 25 31 37 42 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAE6E090DDA 23 29 35 40 46 3/8 SSOV3S130 SSOV3S130 7/8 CSOV-7S
CAE6E107DDA 26 32 38 44 50 3/8 SSOV3S130 SSOV3S130 1-1/8 CSOV-9S
CAE6E129DDA 28 33 39 45 51 3/8 SSOV3S130 SSOV3S130 1-1/8 CSOV-9S
CAE6E149DDA 32 38 44 50 55 3/8 SSOV3S130 SSOV6S130 1-1/8 CSOV-9S
CAE6E160DDA 32 38 44 49 55 3/8 SSOV3S130 SSOV6S130 1-1/8 CSOV-9S
CAE6E217DDA 43 54 66 77 88 1/2 SSOV6S140 SSOV6S140 1-3/8 CSOV-11S
CAE6E265DDA 50 61 72 83 95 1/2 SSOV6S140 SSOV6S140 1-3/8 CSOV-11S
CAE6E337DDA 64 76 87 98 109 1/2 SSOV6S140 SSOV6S140 1-3/8 CSOV-11S

Solenoid Shut off valves (SSOV) operate as double duty isolation / liquid line solenoid valve and are required to ship loose and be installed in the field, outside the refrigerated space.

*Asterisk represents a variable character based on voltage ordered. See nomenclature page for details.

SSOV/CSOV (Check Shut off valves) Selection Criteria: Maximum 10 Ft Line Rise, 100 Foot Line Run, 1:1 Condensing Unit / Evaporator.

Contact applications for additional lengths or design considerations.

Amin values calculated using operating conditions included in UL 60335-2-89 101.DVU.1.2 and standard connection sizes (liquid and Suction).

Amin values provided for 10 ft, 20 ft, 30 ft, 40 Ft and 50 Ft line lengths. Contact applications for additional lengths or design considerations.

Amin values intended to determine compliance with UL 2-89 and is NOT for charging calculations.

SPECIFICATIONS

AIR DEFROST MODELS

Model No. No. of Fans No. of Hanger Slot Locations Connection Sizes Dimensions (Inches) Approximate Weight (Lbs)
Liquid Line Size Suction Line Size Length Width Height Figure Net Ship
CAE6A051*DA 1 4 3/8 5/8 36 28-3/8" 11-1/4" 1 55 190
CAE6A085*DA 2 6 3/8 5/8 56 28-3/8" 11-1/4" 2 75 210
CAE6A103*DA 2 6 3/8 7/8 56 28-3/8" 11-1/4" 2 80 215
CAE6A128*DA 3 8 3/8 7/8 76 28-3/8" 11-1/4" 3 95 230
CAE6A157*DA 3 8 3/8 7/8 76 28-3/8" 11-1/4" 3 105 240
CAE6A173*DA 4 10 3/8 7/8 96 28-3/8" 11-1/4" 4 120 280
CAE6A207*DA 4 1 3/8 7/8 96 28-3/8" 11-1/4" 4 130 290
CAE6A249*DA 5 12 1/2 1-1/8 116 28-3/8" 11-1/4" 5 145 330
CAE6A316*DA 5T 12 1/2 1-1/8 116 28-3/8" 13-3/4" 6 155 340

ELECTRIC DEFROST MODELS

Model No. No. of Fans No. of Hanger Slot Locations Connection Sizes Dimensions (Inches) Approximate Weight (Lbs)
Liquid Line Size Suction Line Size Length Width Height Figure Net Ship
CAE6E045DDA 1 4 3/8 7/8 36 28-3/8" 11-1/4" 1 50 185
CAE6E054DDA 1 4 3/8 7/8 36 28-3/8" 11-1/4" 1 55 190
CAE6E090DDA 2 6 3/8 7/8 56 28-3/8" 11-1/4" 2 75 210
CAE6E107DDA 2 6 3/8 1-1/8 56 28-3/8" 11-1/4" 2 80 215
CAE6E129DDA 3 8 3/8 1-1/8 76 28-3/8" 11-1/4" 3 95 230
CAE6E149DDA 3 8 3/8 1-1/8 76 28-3/8" 11-1/4" 3 105 240
CAE6E160DDA 4 10 3/8 1-1/8 96 28-3/8" 11-1/4" 4 120 280
CAE6E217DDA 4 10 1/2 1-3/8 96 28-3/8" 11-1/4" 4 130 290
CAE6E265DDA 5 12 1/2 1-3/8 116 28-3/8" 11-1/4" 5 145 330
CAE6E337*DA 5T 12 1/2 1-3/8 116 28-3/8" 13-3/4" 6 155 340
CAE4E043DDA 1 4 3/8 7/8 36 28-3/8" 11-1/4" 1 55 190
CAE4E087DDA 2 6 3/8 7/8 56 28-3/8" 11-1/4" 2 80 215
CAE4E127DDA 3 8 3/8 1-1/8 76 28-3/8" 11-1/4" 3 105 240
CAE4E183DDA 4 10 3/8 1-1/8 96 28-3/8" 11-1/4" 4 130 290
CAE4E222DDA 5 12 1/2 1-3/8 116 28-3/8" 11-1/4" 5 145 330
CAE4E283DDA 5T 12 1/2 1-3/8 116 28-3/8" 13-3/4" 6 155 340

*Asterisk represents a variable character based on voltage ordered. See nomenclature page for details.

Drain connection is 3/4" NPT for all models.

For units with mounted TXV components, see nozzle/TXV table for distributor connection size when TXV is field supplied.

TXV Type: Externally Equalized

PHYSICAL DIMENSIONS

Figure 1: Single Fan

Bottom View:

Diagram showing a rectangular unit with a single fan. Dimensions are indicated: 36" length, 28-3/8" width. Mounting holes are 3/8" diameter. Suction and Liquid ports are labeled.

Side View:

Diagram showing the side of the unit. Dimensions are indicated: 6-3/8" height, 11-1/8" depth. Includes 6 knockouts (4 side, 2 top) and a 3/4" x 1/2" NPT drain.

Figure 2: Two Fan

Bottom View:

Diagram showing a rectangular unit with two fans. Dimensions are indicated: 56" length, 28-3/8" width. Mounting holes are 3/8" diameter. Suction and Liquid ports are labeled.

Side View:

Diagram showing the side of the unit. Dimensions are indicated: 6-3/8" height, 11-1/8" depth. Includes 6 knockouts (4 side, 2 top) and a 3/4" x 1/2" NPT drain.

Figure 3: Three Fan

Bottom View:

Diagram showing a rectangular unit with three fans. Dimensions are indicated: 76" length, 28-3/8" width. Mounting holes are 3/8" diameter. Suction and Liquid ports are labeled.

Side View:

Diagram showing the side of the unit. Dimensions are indicated: 6-3/8" height, 11-1/8" depth. Includes 6 knockouts (4 side, 2 top) and a 3/4" x 1/2" NPT drain.

Figure 4: Four Fan

Bottom View:

Diagram showing a rectangular unit with four fans. Dimensions are indicated: 96" length, 28-3/8" width. Mounting holes are 3/8" diameter. Suction and Liquid ports are labeled. Mounting holes on four and five fan units are located 20" on center at each tube sheet.

Side View:

Diagram showing the side of the unit. Dimensions are indicated: 6-3/8" height, 11-1/8" depth. Includes 6 knockouts (4 side, 2 top) and a 3/4" x 1/2" NPT drain.

Figure 5: Five Fan

Bottom View:

Diagram showing a rectangular unit with five fans. Dimensions are indicated: 116" length, 28-3/8" width. Mounting holes are 3/8" diameter. Suction and Liquid ports are labeled. Mounting holes on four and five fan units are located 20" on center at each tube sheet.

Side View:

Diagram showing the side of the unit. Dimensions are indicated: 6-3/8" height, 11-1/8" depth. Includes 6 knockouts (4 side, 2 top) and a 3/4" x 1/2" NPT drain.

Figure 6: Five Tall Fan

Bottom View:

Diagram showing a rectangular unit with five fans. Dimensions are indicated: 116" length, 28-3/8" width. Mounting holes are 3/8" diameter. Suction and Liquid ports are labeled. Mounting holes on four and five fan units are located 20" on center at each tube sheet.

Side View:

Diagram showing the side of the unit. Dimensions are indicated: 8-7/8" height, 13-5/8" depth. Includes 6 knockouts (4 side, 2 top) and a 3/4" x 1/2" NPT drain.

All dimensions are in inches.

Measurements noted on the end view drawing are the same for all units. All mounting holes are 3/8" diameter.

EVAPORATOR APPLICATION RATINGS

Multiple conditions combine to determine the application capacity of an evaporator: Walk-in space temperature, relative humidity, saturated suction temperature difference, and outdoor ambient temperature. All of these factors are considered when calculating an evaporator application rating. These ratings are considerably higher than the net capacity value used for DOE ratings (AWEF).

The AWEF of an evaporator is calculated using the dry coil capacity and the daily evaporator power consumption. Power consumption includes fan and defrost power. Evaporator net capacity reported to the DOE database is dry coil capacity less the full power fan watts. DOE test conditions are at 10°F evaporator/SST temperature difference and less than 50% relative humidity and 96°F liquid temperature. These conditions create a uniform test method, but should not be used for equipment selection, as the equipment selected would be too large for the application.

Published application ratings are a guideline for proper equipment selection. They account for true operating conditions experienced by equipment.

AWEF RATINGS // COOLER AND FREEZER MODELS

Model No. Defrost Type FPI AWEF Model No. Defrost Type FPI AWEF
Cooler Models¹ Freezer Models²
CAE6A051*DA Air Defrost 6 9.00 CAE6E045DDA Electric Defrost 6 4.15
CAE6A085*DA Air Defrost 6 9.00 CAE6E054DDA Electric Defrost 6 4.15
CAE6A103*DA Air Defrost 6 9.00 CAE6E090DDA Electric Defrost 6 4.15
CAE6A128*DA Air Defrost 6 9.00 CAE6E107DDA Electric Defrost 6 4.15
CAE6A157*DA Air Defrost 6 9.00 CAE6E129DDA Electric Defrost 6 4.15
CAE6A173*DA Air Defrost 6 9.00 CAE6E149DDA Electric Defrost 6 4.15
CAE6A207*DA Air Defrost 6 9.00 CAE6E160DDA Electric Defrost 6 4.15
CAE6A249*DA Air Defrost 6 9.00 CAE6E217DDA Electric Defrost 6 4.15
CAE6A316*DA Air Defrost 6 9.00 CAE6E265DDA Electric Defrost 6 4.15
CAE6E045DDA Electric Defrost 6 9.00 CAE6E337DDA Electric Defrost 6 4.15
CAE6E054DDA Electric Defrost 6 9.00 CAE4E043DDA Electric Defrost 4 3.96
CAE6E090DDA Electric Defrost 6 9.00 CAE4E087DDA Electric Defrost 4 4.02
CAE6E107DDA Electric Defrost 6 9.00 CAE4E127DDA Electric Defrost 4 4.07
CAE6E129DDA Electric Defrost 6 9.00 CAE4E183DDA Electric Defrost 4 4.13
CAE6E149DDA Electric Defrost 6 9.00 CAE4E222DDA Electric Defrost 4 4.15
CAE6E160DDA Electric Defrost 6 9.00 CAE4E283DDA Electric Defrost 4 4.15
CAE6E217DDA Electric Defrost 6 9.00
CAE6E265DDA Electric Defrost 6 9.00
CAE6E337DDA Electric Defrost 6 9.00

*Asterisks represents a variable character based on voltage ordered. See nomenclature on page 3.

1. If the model has a numerical value in the table above, the following statement applies: "The refrigeration system is designed and certified for use in walk-in cooler applications."

2. If the model has a numerical value in the table above, the following statement applies: "The refrigeration system is designed and certified for use in walk-in freezer applications."

COLDZONE

ENGINEERED FOR COOL.

©2025 Heat Transfer Products Group

Published June 2025

CZ-CTX-A2L-0625

coldzone.htpg.com

This information is the most current and accurate information available and is subject to change without notice. HTPG makes no warranty or guarantee of any kind, express or implied, regarding the information set forth herein, including without limitation warranty regarding its currency, accuracy or completeness or any warranty of merchantability or fitness for a particular purpose.

PDF preview unavailable. Download the PDF instead.

CZ-CTX-A2L-0625 Adobe PDF Library 17.0 Adobe InDesign 20.3 (Windows)

Related Documents

Preview Coldzone A2L Heavy Duty Unit Cooler Specifications and Data
Comprehensive technical specifications, features, application ratings, and dimensional data for the Coldzone A2L Heavy Duty Unit Cooler series, designed for medium to large walk-in cooler and freezer applications. Includes details on air defrost, electric defrost (medium and low temperature), refrigerants, electrical specifications, and optional features.
Preview COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler Specifications
The COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler is designed for small to medium walk-in cooler and freezer applications, featuring advanced performance, air and electric defrost options, high-efficiency motors, and compatibility with A2L refrigerants.
Preview COLDZONE A2L Low Velocity Center Mount Unit Cooler
Discover the COLDZONE A2L Low Velocity Center Mount Unit Cooler, designed for efficient cooling in small to medium walk-in applications. Explore features, specifications, and application ratings for both Air Defrost and Electric Defrost models.
Preview COLDZONE A2L Medium Profile Unit Cooler: Specifications & Applications
Discover the COLDZONE A2L Medium Profile Unit Cooler, an efficient evaporator solution for walk-in coolers and freezers. This document details technical specifications, application ratings, electrical data, and dimensional drawings for various defrost types and refrigerants.
Preview Coldzone A2L Medium Profile Unit Cooler: Features, Specifications, and Ratings
Detailed technical specifications, application ratings, and dimensional data for Coldzone's A2L Medium Profile Unit Coolers, designed for walk-in cooler and freezer applications. Includes information on defrost types, capacities, electrical data, and model nomenclature.
Preview Coldzone A2L Warehouse Unit Coolers: Specifications and Applications
Explore the Coldzone A2L Warehouse Unit Cooler series, designed for medium to large walk-in cooler and freezer applications. Features include air and electric defrost options, various BTUH capacities, and compatibility with refrigerants R454A, R454C, and R455A.