Composants pour technique de systèmes
Disjoncteur Disjonct. protection de ligne
Article Number: 272160
Model: 8530/1-MCB-STA103-B6-000-3
Product Description
The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation during short circuits and high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modular and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key Features
- Functionality: Sectioning according to EN 60947-2
- Energy Limitation Class: 3
- Modular Design: Easy replacement or extension of systems.
- Mounting: Simple snap-on mounting on a DIN rail in Ex e enclosures.
- Tripping: Fixed magneto-thermal releases.
- Operation: Ergonomic lever for safe switching on and off.
- Safety: Padlock protection (accessories) prevents re-operation during maintenance.
Technical Characteristics
Explosion Protection
Characteristic | Details |
---|---|
Application Area (Zones) | 1, 2 |
Application Area (Zones) Note | Usable in Zone 21 / 22 with Ex tb / tc enclosure protection |
IECEx Certificate Gas | IECEx FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX Certificate Gas | FM19ATEX0191U |
ATEX Gas Explosion Protection | Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX), China (CCC) |
Electrical Characteristics
Characteristic | Value |
---|---|
Rated Operational Voltage AC | 230/400 V |
Rated Service Current | 6 A |
Frequency | 50/60 Hz |
Rated Switching Capacity | 10 kA |
Electrical Service Life | 2 x 10⁴ |
Mechanical Service Life | 2 x 10⁴ |
1st Auxiliary Function | None |
Voltage 1st Auxiliary Function AC | - |
Max. Current 1st Auxiliary Function | - |
2nd Auxiliary Function | None |
Max. Voltage 2nd Auxiliary Function DC | - |
Tripping Characteristic | B |
Number of Poles | 3 poles |
Ambient Conditions
Characteristic | Value |
---|---|
Ambient Temperature | -40 °C ... 70 °C |
Ambient Temperature | -40 °F ... 158 °F |
Ambient Temperature Note | Different ambient temperatures based on current certificates, on request |
Mechanical Characteristics
Characteristic | Value |
---|---|
Degree of Protection (IP) (IEC 60529) | IP2X |
Housing Material | Thermoplastic |
Minimum Connection Terminal Size | 1.5 mm² |
Maximum Connection Terminal Size | 25 mm² |
Minimum AWG Connection Terminal Size | 16 AWG |
Maximum AWG Connection Terminal Size | 4 AWG |
Connection Terminal Size 2 Minimum | 1.5 mm² |
Connection Terminal Size 2 Maximum | 10 mm² |
AWG Connection Terminal Size 2 Minimum | 16 AWG |
AWG Connection Terminal Size 2 Maximum | 8 AWG |
Minimum Tightening Torque | 2 N·m |
Maximum Tightening Torque | 3 N·m |
Connection Terminal Note | 2-conductor connection (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Permitted combination possibilities of connection terminals are indicated in the operating instructions. |
Width | 83 mm (3.27 in) |
Length | 165 mm (6.5 in) |
Mounting Depth | 138.3 mm (5.44 in) |
Weight | 1.4 kg (3.087 lb) |
Mounting / Installation
Characteristic | Value |
---|---|
Tightening Torque | 2–3 N·m |
Tightening Torque in lbf·in | 17.7 ... 26.6 lbf·in |
Auxiliary Contact Tightening Torque | 0.4–0.6 N·m |
Auxiliary Contact Tightening Torque lbf·in | 3.5 ... 5.3 lbf·in |
Technical Drawings
Tripping Characteristic Curve
A graph shows the tripping characteristic curve for type B, with time in seconds on the y-axis and multiple of rated current (I/In) on the x-axis. The curve indicates tripping times for AC and DC.
Overall Dimensions
Diagrams showing the overall dimensions of the circuit breaker in mm and inches. Key dimensions include width, height, and depth, with mounting dimensions also indicated.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Description | Article Number |
---|---|
Quadruple locking device for individual locking of the component using up to 4 cylinder locks. | 227232 |
Fixing Kit
A fixing kit for mounting the component onto the mounting plate without a DIN rail.
Description | Article Number |
---|---|
Fixing kit for mounting the component onto the mounting plate without a DIN rail. | 276618 |
Cylinder Lock
For locking (shackle Ø 3).
Description | Article Number |
---|---|
For locking (shackle Ø 3). | 107115 |
Note: Technical characteristics, dimensions, weights, construction types, and delivery options are subject to change. Figures are for illustrative purposes only.
Contact Information:
R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com