Composants pour technique de systèmes

Disjoncteur Disjonct. protection de ligne

Article Number: 272160

Model: 8530/1-MCB-STA103-B6-000-3

Product Description

The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation during short circuits and high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modular and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).

Key Features

Technical Characteristics

Explosion Protection

Characteristic Details
Application Area (Zones) 1, 2
Application Area (Zones) Note Usable in Zone 21 / 22 with Ex tb / tc enclosure protection
IECEx Certificate Gas IECEx FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX Certificate Gas FM19ATEX0191U
ATEX Gas Explosion Protection Ex db eb IIC Gb
Certificates ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of Conformity Certificate of Conformity (ATEX), China (CCC)

Electrical Characteristics

Characteristic Value
Rated Operational Voltage AC 230/400 V
Rated Service Current 6 A
Frequency 50/60 Hz
Rated Switching Capacity 10 kA
Electrical Service Life 2 x 10⁴
Mechanical Service Life 2 x 10⁴
1st Auxiliary Function None
Voltage 1st Auxiliary Function AC -
Max. Current 1st Auxiliary Function -
2nd Auxiliary Function None
Max. Voltage 2nd Auxiliary Function DC -
Tripping Characteristic B
Number of Poles 3 poles

Ambient Conditions

Characteristic Value
Ambient Temperature -40 °C ... 70 °C
Ambient Temperature -40 °F ... 158 °F
Ambient Temperature Note Different ambient temperatures based on current certificates, on request

Mechanical Characteristics

Characteristic Value
Degree of Protection (IP) (IEC 60529) IP2X
Housing Material Thermoplastic
Minimum Connection Terminal Size 1.5 mm²
Maximum Connection Terminal Size 25 mm²
Minimum AWG Connection Terminal Size 16 AWG
Maximum AWG Connection Terminal Size 4 AWG
Connection Terminal Size 2 Minimum 1.5 mm²
Connection Terminal Size 2 Maximum 10 mm²
AWG Connection Terminal Size 2 Minimum 16 AWG
AWG Connection Terminal Size 2 Maximum 8 AWG
Minimum Tightening Torque 2 N·m
Maximum Tightening Torque 3 N·m
Connection Terminal Note 2-conductor connection (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Permitted combination possibilities of connection terminals are indicated in the operating instructions.
Width 83 mm (3.27 in)
Length 165 mm (6.5 in)
Mounting Depth 138.3 mm (5.44 in)
Weight 1.4 kg (3.087 lb)

Mounting / Installation

Characteristic Value
Tightening Torque 2–3 N·m
Tightening Torque in lbf·in 17.7 ... 26.6 lbf·in
Auxiliary Contact Tightening Torque 0.4–0.6 N·m
Auxiliary Contact Tightening Torque lbf·in 3.5 ... 5.3 lbf·in

Technical Drawings

Tripping Characteristic Curve

A graph shows the tripping characteristic curve for type B, with time in seconds on the y-axis and multiple of rated current (I/In) on the x-axis. The curve indicates tripping times for AC and DC.

Overall Dimensions

Diagrams showing the overall dimensions of the circuit breaker in mm and inches. Key dimensions include width, height, and depth, with mounting dimensions also indicated.

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.

Description Article Number
Quadruple locking device for individual locking of the component using up to 4 cylinder locks. 227232

Fixing Kit

A fixing kit for mounting the component onto the mounting plate without a DIN rail.

Description Article Number
Fixing kit for mounting the component onto the mounting plate without a DIN rail. 276618

Cylinder Lock

For locking (shackle Ø 3).

Description Article Number
For locking (shackle Ø 3). 107115

Note: Technical characteristics, dimensions, weights, construction types, and delivery options are subject to change. Figures are for illustrative purposes only.

Contact Information:

R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG

Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103-b6-000-3-272160-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103-B6-000-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-B6-000-3 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for system solutions and hazardous environments.
Preview R. STAHL 8530/1-MCB-STA103-B6-000-3 LS Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-B6-000-3 LS Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C32-000-3 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C32-000-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical features, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C63-000-3 Line Protection Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C63-000-3 line protection circuit breaker, including features, electrical characteristics, mechanical specifications, and explosion protection.
Preview R. STAHL 8530/1-MCB-STA103-C10-000-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C10-000-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C6-000-3 Line Protection Circuit Breaker Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C6-000-3 line protection circuit breaker, including features, electrical characteristics, mechanical specifications, and explosion protection details.
Preview R. STAHL 8530/1-MCB-STA103-B25-000-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-B25-000-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-B40-000-3 Line Protection Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-B40-000-3 line protection circuit breaker, including features, electrical characteristics, mechanical specifications, and explosion protection data.