Isolator Barriers
Loop-powered binary output
Ex i field circuit
Model: 9276/10-21-40-00s
Art. No.: 261441
Key Features
- A comprehensive portfolio for a wide range of solenoid valves
- Space savings due to a slim design – 12.5 mm wide
- Can be used for functional safety levels up to SIL 3 (IEC/EN 61508)
Certifications: Ex SIL Safety Integrity Level IEC 61508 IEC 61511
Series 9276 digital outputs issue signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs.
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Application range (zones) | 2 |
Ex interface zone | 0, 1, 2, 20, 21, 22 |
IECEx gas certificate | IECEx IBE 17.0045X |
IECEx gas explosion protection | Ex ec [ia Ga] IIC T4 Gc |
IECEx dust certificate | IECEx IBE 17.0045X |
IECEx dust explosion protection | [Ex ia Da] IIIC |
IECEX firedamp certificate | IECEx IBE 17.0045X |
IECEx firedamp protection | [Ex ia Ma] I |
ATEX gas certificate | IBEXU 17 ATEX 1153 X |
ATEX gas explosion protection | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
ATEX dust certificate | IBEXU 17 ATEX 1153 X |
ATEX dust explosion protection | II (1) D [Ex ia Da] IIIC |
ATEX firedamp certificate | IBEXU 17 ATEX 1153 X |
ATEX firedamp protection | I (M1) [Ex ia Ma] I |
cULus certificate | E81680 |
Marking cULus | Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA Group IIC AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC T4 any mounting pos. Ta = 60°C |
Certificates | ATEX (IBE), Canada (UL), China (CQM), IECEx (IBE), Korea (KTL), SIL (exida), USA (UL) |
Ship approval | DNV |
Declaration of conformity | ATEX (EUK), China (CCC) |
Safety Data | |
Max. voltage U/Voc | 25.1 V |
Max. current I (Ex ia) | 87 mA |
Max. power P. | 550 mW |
Max. permissible external capacitance C/C for IIC | 0.108 μF |
Max. permissible external inductance L/La for IIC | 5 mH |
Max. permissible external capacitance C/C for IIB | 0.83 μF |
Max. permissible external inductance L/La for IIB | 20 mH |
Max. permissible external capa.IIA | 2.93 μF |
Max. permissible external inductance L。 for IIA | 45 mH |
Max. perm. ext. capacit. IIIC | 0.83 μF |
Max. permis. ext. induct. IIIC | 20 mH |
Max. permissible ext. capac. I | 2.93 μF |
Max. permissible external inductance L。 for I | 45 mH |
Internal capacitance | Negligible |
Internal inductance | Negligible |
Safety-related max. voltage | 253 V AC |
Intrinsically safe limiting values inductance L/capacitance C。
Circuit Type | L. [mH] | C. [µF] | L. [mH] | C. [µF] | L. [mH] | C. [µF] | L. [mH] | C. [µF] |
---|---|---|---|---|---|---|---|---|
IIC | 2 mH | 0.052 μF | 1 mH | 0.082 μF | 0.500 mH | 0.100 mH | 0.200 mH | 0.108 μF |
IIB | 10 mH | 0.380 μF | 5 mH | 0.440 μF | 1 mH | 0.108 μF | 0.100 mH | 0.820 μF |
IIA | 20 mH | 0.600 μF | 5 mH | 0.610 µF | 1 mH | 0.640 μF | 0.100 mH | 0.108 μF |
IIIC | 10 mH | 0.380 μF | 5 mH | 0.440 μF | 1 mH | 0.100 mH | 0.820 μF | 0.100 mH |
I | 20 mH | 0.600 μF | 5 mH | 0.610 μF | 1 mH | 0.640 μF | 1 μF | 1 μF |
Functional Safety
Parameter | Value |
---|---|
SIL | 3 |
HFT | 0 |
SFF | 100% |
Lambda SD | 0 FIT |
Lambda SU | 50 FIT |
Lambda DD | 0 FIT |
Lambda DU | 0 FIT |
Electrical Data
Parameter | Value |
---|---|
Number of channels | 1 |
Auxiliary power | without |
Max. power dissipation | 1.06 W |
Auxiliary Power
Parameter | Value |
---|---|
Polarity reversal protection | Yes |
Galvanic Isolation | EN IEC 60079-11 |
Test voltage as per standard | 375 V AC peak value |
Galvanic separation Ex i output to input | 375 V AC peak value |
Input
Parameter | Value |
---|---|
Input voltage for ON | 15 – 30 V |
Input voltage for OFF | 0 – 5 V |
Output
Parameter | Value |
---|---|
Output open-circuit voltage U | 21.9 V |
Max. output current Ia max | 40 mA |
Output internal resistance R₁ | 287 Ω |
Switching delay ON/OFF | ≤ 20 ms |
Switching delay OFF/ON | ≤ 20 ms |
Response time output | 20 ms |
Switching state indication | Yellow "STAT" LED |
Ambient Conditions
Parameter | Value |
---|---|
Ambient temperature °C | -40 °C ... 60 °C |
Ambient temperature °F | -40 °F ... +140 °F |
Storage temperature °C | -40 °C ... 80 °C |
Storage temperature °F | -40 °F ... +176 °F |
Max. relative humidity | 10 to 95% |
Use at the height of | < 2000 m |
Electromagnetic compatibility | EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4 |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) | IP30 |
Degree of protection (IP) terminals | IP20 |
Fire resistance (UL 94) | VO |
Enclosure material | Polyamide |
Grid dimension | 12.5 mm |
Width | 12.5 mm |
Width, inches | 0.49 in |
Height | 114.5 mm |
Height in inches | 4.51 in |
Length | 112.5 mm |
Length in inches | 4.43 in |
Weight | 165 g |
Weight | 0.36 lb |
Mounting / Installation
Parameter | Value |
---|---|
Connection type | Screw terminal |
Min. rigid conductor cross section | 0.2 mm² |
Max. rigid conductor cross section | 2.5 mm² |
Min. flex conductor cross section | 0.2 mm² |
Max. flex conductor cross section | 2.5 mm² |
Connection cross-section AWG | 24 ... 14 |
Mounting type | DIN rail NS35/15, NS35/7.5 |
Mounting orientation | Vertical Horizontal |
Technical Drawings
Hazardous Location vs. Nonhazardous Location
Diagram showing the relationship between hazardous and nonhazardous locations for the isolator barrier.
Output characteristic curve 9276/10-21-40-00: Plot of output current I, [mA] vs. output voltage U [V].
Connection diagram 9276/10
Dimensional Drawings (All Dimensions in mm [inches])
Diagram showing the dimensions of the isolator barrier, including overall length, height, and width, with callouts for specific measurements.
Illustration referencing ISpac Series 9260, 9265, 9270, 9275, 9276, 9282 with screw terminal.
R. STAHL, INC. | 13259 N. Promenade Blvd. | Stafford, TX 77477 | Tel. +1 800 782 4357
Email US: sales.us@r-stahl.com | Email CAN: sales.ca@r-stahl.com | rstahl.com
Related Documents
![]() |
R. STAHL 9276A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators Technical specifications and data for the R. STAHL 9276A series loop-powered binary output Ex i field circuit isolators. Details include explosion protection, safety data, electrical characteristics, environmental conditions, and mechanical data for model 9276/10-21-40-00s. |
![]() |
R. STAHL 9276A Galvanic Isolator: Technical Specifications for Ex i Field Circuits Detailed technical specifications for the R. STAHL 9276A galvanic isolator, a loop-powered binary output device for Ex i field circuits. Includes ATEX, IECEx, and cULus certifications, electrical and mechanical characteristics, and safety data. |
![]() |
R. STAHL 9276/10-21-40-00s: Loop-Powered Binary Output for Ex i Field Circuits Technical data sheet for the R. STAHL 9276/10-21-40-00s loop-powered binary output device for Ex i field circuits. Features include intrinsic safety, SIL 3 capability, and a compact design. |
![]() |
R. STAHL 9276/10-24-48-00s Isolator Barrier for Ex i Field Circuits Technical data sheet for the R. STAHL 9276/10-24-48-00s loop-powered binary output isolator barrier, designed for Ex i field circuits. Features include SIL 3 capability, slim design, and comprehensive explosion protection certifications. |
![]() |
R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit - Technical Data Detailed technical specifications and safety information for the R. STAHL 9276A loop-powered binary output Ex i field circuit, including explosion protection, electrical data, safety, and mechanical dimensions. |
![]() |
R. STAHL 9276/10-21-40-00s Loop-Powered Binary Output Isolator - Technical Data Detailed technical specifications for the R. STAHL 9276/10-21-40-00s loop-powered binary output isolator, designed for Ex i field circuits. Includes explosion protection, safety data, electrical specifications, ambient conditions, and mechanical data. |
![]() |
R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit - Technical Data Technical specifications and data for the R. STAHL 9276A loop-powered binary output for Ex i field circuits. Details include explosion protection, safety data, electrical specifications, environmental conditions, and mechanical data. |
![]() |
R. STAHL 9276A Series Loop-Powered Binary Output Ex i Field Circuit Isolators Technical specifications and safety data for the R. STAHL 9276A series loop-powered binary output isolators, designed for Ex i field circuits. Features include ATEX, IECEx, and cULus certifications, various protection methods, and detailed electrical and mechanical data. |