R. STAHL 9276A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators
The R. STAHL 9276A series provides loop-powered binary outputs for Ex i field circuits. These isolators are designed for the operation of intrinsically safe solenoid valves, pilot lights, or horns. They do not require separate auxiliary power, as they are supplied via the control circuit. The intrinsically safe outputs are galvanically separated from the inputs.
Key Features
- Extensive catalog for solenoid valves
- Space-saving design with a width of 12.5 mm
- Usable up to SIL 3 (IEC/EN 61508)
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 2 |
Interface Ex zone | 0, 1, 2, 20, 21, 22 |
Homologation IECEX gas | IECEx IBE 17.0045X |
IECEx Gas Explosion Protection | Ex ec [ia Ga] IIC T4 Gc |
Homologation IECEx dust | IECEx IBE 17.0045X |
IECEx Dust Explosion Protection | [Ex ia Da] IIIC |
Homologation IECEx firedamp | IECEx IBE 17.0045X |
IECEx Firedamp Protection | [Ex ia Ma] I |
Homologation ATEX gas | IBEXU 17 ATEX 1153 X |
ATEX Gas Explosion Protection | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
Homologation ATEX dust | IBEXU 17 ATEX 1153 X |
ATEX Dust Explosion Protection | II (1) D [Ex ia Da] IIIC |
Homologation ATEX firedamp | IBEXU 17 ATEX 1153 X |
ATEX Firedamp Protection | I (M1) [Ex ia Ma] I |
Homologation cULus | E81680 |
cULus Identification | Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC; T4 any mounting pos. Ta = 60°C; See Doc. 9276 6 031 001 3 |
Certifications | ATEX (IBE), Canada (CSA), China (CQM), Korea (KTL), EE.UU. (UL), IECEx (IBE), SIL (exida) |
Naval certification | DNV |
Safety Data
Parameter | Value |
---|---|
Conformity Certificate | ATEX (EUK), China (CCC) |
Maximum voltage U | 25.1 V |
Maximum current I (Ex ia) | 87 mA |
Maximum power P | 550 mW |
Max. permissible external capacitance C for IIC | 0.108 μF |
Max. permissible external inductance L for IIC | 5 mH |
Max. permissible external capacitance C for IIB | 0.83 μF |
Max. permissible external inductance L for IIB | 20 mH |
Max. permissible external capacitance C for IIA | 2.93 μF |
Max. permissible external inductance L for IIA | 45 mH |
Max. permissible external capacitance C for IIIC | 0.83 μF |
Max. permissible external inductance L for IIIC | 20 mH |
Max. permissible external capacitance C for I | 2.93 μF |
Max. permissible external inductance L for I | 45 mH |
Internal capacitance | Irrelevant |
Internal inductance | Irrelevant |
Maximum technical safety voltage | 253 V AC |
Intrinsic safety limits inductance L / capacitance C | Commonly connectable inductance L / capacitance C |
Parameter | IIC | IIB | IIA | IIIC |
---|---|---|---|---|
L₀ [mH] | 2 mH, 1 mH, 0.500 mH, 1 mH, 10 mH, 5 mH, 20 mH, 5 mH | 1 mH, 0.500 mH, 1 mH, 10 mH, 5 mH, 20 mH, 5 mH | 1 mH, 0.500 mH, 1 mH, 10 mH, 5 mH, 20 mH, 5 mH | 1 mH, 0.500 mH, 1 mH, 10 mH, 5 mH, 20 mH, 5 mH |
C₀ [µF] | 0.052 μF, 0.065 μF, 0.082 µF, 0.108 μF, 0.380 μF, 0.380 μF, 0.600 μF, 0.610 µF | 0.082 µF, 0.108 μF, 0.380 μF, 0.380 μF, 0.600 μF, 0.610 µF | 0.100 mH, 0.820 μF, 0.100 mH, 1 μF, 0.100 mH, 0.820 μF, 0.100 mH, 1 μF | 0.100 mH, 0.820 μF, 0.100 mH, 1 μF, 0.100 mH, 0.820 μF, 0.100 mH, 1 μF |
Functional Safety
Parameter | Value |
---|---|
SIL | 3 |
HFT | 0 |
SFF | 100% |
Lambda SD | 0 FIT |
Lambda SU | 50 FIT |
Lambda DD | 0 FIT |
Lambda DU | 0 FIT |
Electrical Data
Parameter | Value |
---|---|
Number of channels | 1 |
Auxiliary Power
Parameter | Value |
---|---|
Auxiliary power | None |
Maximum dissipated power | 1.06 W |
Reverse polarity protection | Yes |
Galvanic Separation
Parameter | Value |
---|---|
Test voltage according to standard | EN IEC 60079-11 |
Galvanic separation output Ex i to input | 375 V AC maximum value |
Input
Parameter | Value |
---|---|
Input voltage for ON | 15 – 30 V |
Input voltage for OFF | 0 – 5 V |
Output
Parameter | Value |
---|---|
Output open-circuit voltage U | 21.9 V |
Maximum output current I max | 40 mA |
Output internal resistance R | 287 Ω |
Switching delay ON/OFF | ≤ 20 ms |
Switching delay OFF/ON | ≤ 20 ms |
Output stabilization time | 20 ms |
Switching status indication | Yellow LED "STAT" |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 60 °C (-40 °F ... +140 °F) |
Storage temperature | -40 °C ... 80 °C (-40 °F ... +176 °F) |
Maximum relative humidity | 10 ... 95% |
Usage at altitude | < 2000 m |
Electromagnetic compatibility | EN 61326-1 industrial use; Immunity according to EN 61000-6-2; Radiated spurious emissions according to EN 61000-6-4 |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) | IP30 |
Degree of protection (IP) terminals | IP20 |
Fire resistance (UL 94) | V0 |
Enclosure material | Polyamide |
Mounting rail dimension | 12.5 mm |
Width | 12.5 mm |
Width | 12.5 mm |
Mounting width in inches | 0.49 in |
Height | 114.5 mm |
Height | 114.5 mm |
Height in inches | 4.51 in |
Length | 112.5 mm |
Length in inches | 4.43 in |
Weight | 165 g |
Weight | 0.36 lb |
Mounting / Installation
Parameter | Value |
---|---|
Mounting type | DIN rail NS35/15, NS35/7.5 |
Mounting position | vertical, horizontal |
Connection type | Screw terminal |
Minimum rigid conductor cross-section | 0.2 mm² |
Maximum flexible conductor cross-section | 2.5 mm² |
Minimum flexible conductor cross-section | 0.2 mm² |
Maximum flexible conductor cross-section | 2.5 mm² |
Ambient temperature AWG | 24 ... 14 |
Dimensional Drawing
All dimensions in mm [inches]. Subject to modifications.
R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.