R. STAHL 9176/20-15-00s Isolator Barriers

Loop-powered binary output for Ex i field circuits

Art. No. 222180

Product Overview

The 9176 series binary outputs are designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, or horns. These devices are powered by the control circuit and do not require a separate auxiliary power supply. The intrinsically safe outputs are galvanically separated from the inputs. Two-channel variants offer galvanically separated channels, reducing space requirements.

Technical Data

Explosion Protection

Parameter Value
Application range (zones) 2
Ex interface zone 0, 1, 2, 20, 21, 22
IECEX gas certificate IECEx BVS 13.0012 X
IECEx gas explosion protection Ex nA [ia Ga] IIC T4 Gc
IECEx dust certificate IECEx BVS 13.0012 X
IECEx dust explosion protection [Ex ia Da] IIIC
ATEX gas certificate BVS 04 ATEX E 075 X
ATEX gas explosion protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX dust certificate BVS 04 ATEX E 075 X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
FM certificate FM16US0122X
CFM certificate FM16CA0067X
Marking cFMus Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC
Temperature rating T4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C
Certificates ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
Ship approval CCS, EU RO MR (DNV)
Declaration of conformity ATEX (EUK), China (CCC)

Safety Data

Parameter Value
Max. voltage Uo/Voc 27.6 V
Max. current Io (Ex ia) 86.5 mA
Max. current Io (Ex ib) 44 mA
Max. power Po 596 mW
Max. permissible external capacitance Co for IIC 0.085 μF
Max. permissible external inductance Lo/La for IIC 1.8 mH
Max. permissible external capacitance Co for IIB 0.667 μF
Max. permissible external inductance Lo/La for IIB 17 mH
Internal capacitance 1.1 nF
Internal inductance Negligible
Max. voltage Uo parallel 27.6 V
Max. power Po parallel 1192 mW
Max. current Io (Ex ia) parallel 173 mA
Max. current Io (Ex ib) parallel 88 mA
Internal capacitance parallel 2.2 nF
Internal inductance parallel negligible
Safety-related max. voltage 253 V
Intrinsically safe limiting values inductance Lo/capacitance Co Max. connectable inductance Lo/capacitance Co: 2 parallel channels
IIC Lo [mH] 2.5 mH
IIC Co [µF] 0.665 μF
IIB Lo [mH] 2.500 mH
IIB Co [µF] 0.665 μF
IIIC Lo [mH] 2.500 mH
IIIC Co [µF] 0.665 μF

Electrical Data

Parameter Value
Number of channels 2
Internal resistance Ri 320 Ω
Auxiliary power without
Auxiliary power consumption 0.5 W + (I x 37 mW/mA)
Polarity reversal protection Yes
Galvanic Isolation Test voltage as per standard (Ex i input to Ex i input) EN IEC 60079-11, 500 V AC
Galvanic Isolation Test voltage as per standard (Input to input) EN 50178, 350 V AC

Input

Parameter Value
Input characteristics In accordance with EN 61131-2
Input voltage for ON 18 – 31.2 V
Input voltage for OFF 0 – 5 V
Control Power PE 0.5 W + (IA x 37 mW/mA) (with IA = max. required output current)

Output

Parameter Value
Output open-circuit voltage Uo 25 V
Max. output current Ia max 29 mA
Max. output current Inote Parallel channels: 58 mA
Internal resistance Ri note 320 Ω/parallel: 160 Ω
Output residual ripple < 100 mV
Output switching frequency ≤ 10 Hz
Switching delay ON/OFF ≤ 50 ms
Switching delay OFF/ON ≤ 18 ms
Switching state indication Yellow "OUT" LED

Output Characteristic Curve

The diagram shows the output characteristic for the 9176/.0-15-00 model. Curve A represents the characteristic for each channel, and Curve B represents the characteristic for channel 1 and parallel channel 2 (for types 9176/20-...). The x-axis represents the current in mA, and the y-axis represents the voltage in V.

Conditions: At UN; -20 to +60 °C

Curve A: Characteristic curve for each channel

Curve B: Characteristic curve for channel 1, parallel channel 2 (only types 9176/20-..-..)

Ambient Conditions

Parameter Value
Ambient temperature °C (Single device) -20 °C ... 70 °C
Ambient temperature °C (Group assembly) -20 °C ... 60 °C
Ambient temperature °F (Single device) -4 °F ... +158 °F
Ambient temperature °F (Group assembly) -4 °F ... +140 °F
Storage temperature °C -40 °C ... 80 °C
Storage temperature °F -40 °F ... +176 °F
Max. relative humidity 95%
Use at the height of < 2000 m
Electromagnetic compatibility Tested to the following standards and regulations: EN 61326-1. For use in industrial areas; NAMUR NE 21

Note: The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".

Mechanical Data

Parameter Value
Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) V0
Enclosure material Polyamide
Grid dimension 17.6 mm
Width 17.6 mm
Width, inches 0.69 in
Height 114.5 mm
Height in inches 4.51 in
Length 108 mm
Length in inches 4.25 in
Weight 185 g
Weight 0.41 lb

Mounting / Installation

Parameter Value
Mounting orientation Vertical, Horizontal
Connection type Screw terminal
Min. rigid conductor cross section 0.2 mm²
Max. rigid conductor cross section 2.5 mm²
Min. flex conductor cross section 0.2 mm²
Max. flex conductor cross section 2.5 mm²
Connection cross-section AWG 24 ... 14

Technical Drawings

Connection Diagram 9176/10-..-..

This diagram illustrates the connection for hazardous and non-hazardous locations, showing the Field Device, ISpac Isolator, and Control System.

Connection Diagram 9176/20-..-..-..

This diagram illustrates the connection for hazardous and non-hazardous locations, showing the Field Device, ISpac Isolator, and Control System across different division and zone classifications.

Accessories

Transparent cover

For 91xx ISpac modules. Yellow, transparent. Provides clear identification of the device for SIL applications. (Packaging unit: 10 pieces)

Art. No. 200914

Spare Parts

Screw terminal

Description Art. No.
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: green 112817
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: black 112816
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: blue 112818

Screw terminal with test tap

Description Art. No.
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: black 113005
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: blue 113004

Spring clamp terminal

Description Art. No.
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, color: green 112825
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, color: black 112824
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, color: blue 112826

R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-20-15-00s-222180-en-us-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176/20-15-00s Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for Ex i field circuits. This document covers safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.
Preview R. STAHL 9176A Galvanic Isolator: Ex i Field Circuit Output
Technical specifications and features of the R. STAHL 9176A loop-powered binary output Ex i field circuit isolator, including safety, electrical, and mechanical characteristics.
Preview R. STAHL 9176/20-15-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176 Series: Loop-Powered Binary Output for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176 series of loop-powered binary outputs for Ex i field circuits. This document details technical specifications, safety data, certifications, and accessories for the 9176/20-15-00s model.
Preview R. STAHL 9176/20-15-00k Isolator Barrier: Technical Specifications and Features
Detailed technical data, safety information, and specifications for the R. STAHL 9176/20-15-00k loop-powered binary output isolator barrier for Ex i field circuits. Includes explosion protection, electrical data, ambient conditions, and mechanical data.
Preview R. STAHL 9176A Isolator Barriers: Loop-Powered Binary Output for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176A series isolator barriers, designed for loop-powered binary outputs in Ex i field circuits. Features include intrinsic safety, galvanic separation, and suitability for solenoid valves and signaling devices.
Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators
Technical data and specifications for the R. STAHL 9176A series of loop-powered binary output isolators for Ex i field circuits. Details include safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.