Mastech MS2308 Earth Resistance Tester
Quick Start Guide
Contact Information
EMEA: MGL EUMAN S.L., C/ Picu Castiellu, Parcelas i1-i4 33163, Argame Morcín, Asturias, Spain. Tel: +34 985-08-18-70, Email: cs.emea@mgl-intl.com
USA: MGL AMERICA, INC., 2810 Coliseum Centre Drive, Ste. 100 Charlotte, North Carolina 28217 USA. Tel: +1 833-533-5899, Email: cs.na@mgl-intl.com
UNITED KINGDOM: MGL GROUP U.K. LIMITED, 14 Weller St, London, SE1 1QU, UK. Tel: +34 985-08-18-70, Email: cs.uk@mgl-intl.com
MEXICO & LATAM: MGL LATAM S.A DE CV, Colonia Industrial Vallejo Del. Azcapotzalco 02300, Mexico D.F. Tel: +1 833-533-5899, Email: cs.latam@mgl-intl.com
APAC: MGL APPA Corporation, Flat 4-1, 4/F, No. 35, Section 3 Minquan East Road, Taipei, Taiwan. Tel: +886 2-2508-0877, Email: cs.apac@mgl-intl.com
SKU Number: MS2308CBGLO
Safety Precautions
Special attention should be paid when using test and measurement instruments. Improper usage may cause electric shock and damage the equipment.
- Use proper measurement category (CAT), voltage, and amperage rated probes, test leads, and adapters.
- Do not use or store the device around explosive gas, vapor, or under high temperature and humidity.
- When handling test probes and crocodile clips, keep fingers behind the physical guard.
- Examine test leads before use. Replace any with deteriorated insulation.
- Connect the common test lead before the live test lead, and remove the live test lead before the common test lead.
- Before measuring current, ensure instrument fuses are available and disconnect power to the circuit under test.
- Remove batteries if the device is not used for an extended period or is stored in temperatures above 45 °C to prevent damage from battery leakage.
Specifications
Measurement | Resolution | Accuracy | Range |
---|---|---|---|
3 Pole & 4 Pole Resistance (Selective mode) | 0.001Ω | ±(5%+10) | 0.02Ω~300kΩ |
3 Pole & 4 Pole Resistance (Non-auxiliary-polar mode) | 0.001Ω | ±(5%+10) | 0.02Ω~20kΩ |
2 Pole R (AC) | 0.001Ω | ±(5%+10) | 0.02Ω~300kΩ |
2/4 Pole R (DC) | 0.001Ω | ±(5%+10) | 0.02Ω~3kΩ |
Soil Resistivity ρ | 0.001Ω | ±(5%+10) | 0.02Ω~1000 (kΩ· m) |
Current (A~) | 1mA | ±(5%+5) | 20mA~2A |
Measurement Configurations
3 POLE/4 POLE Measurement:
A diagram shows the Mastech MS2308 connected using 4 wires for a 3-pole or 4-pole resistance measurement, displaying '1.42 Ω'.
3 POLE/4 POLE Measurement (Simplified):
A diagram shows a simplified 3-pole or 4-pole resistance measurement setup, displaying '1.38 Ω'.
3 POLE/4 POLE Measurement (with Earth Rod):
A diagram illustrates a 3-pole or 4-pole measurement with an earth rod connection, displaying '1.34 Ω'.
2 POLE~ Measurement:
A diagram shows the Mastech MS2308 connected for a 2-pole AC resistance measurement, displaying '21.6 Ω'.
2 POLE/4 POLE= Measurement:
A diagram shows the Mastech MS2308 connected for a 2-pole or 4-pole DC resistance measurement, displaying '1.63 Ω'.
P Measurement (Soil Resistivity):
A diagram illustrates the setup for measuring soil resistivity (ρ) using four stakes arranged in a line, displaying '120.'.
A~ Measurement (Current):
A diagram shows the Mastech MS2308 measuring current, displaying '7 mA'.
Warranty
1 YEAR LIMITED WARRANTY