ActronAir Wall Controller
Installation Instructions
Controller Model Numbers: LR7-1W, LR7-1G
Introduction
This document provides installation instructions for the ActronAir LR7 Wall Controller. Please read this manual carefully before installing or operating your air conditioning unit.
ActronAir: That's better. That's Actron.
Table of Contents
- 01. Safety Precautions
- 02. Specifications
- 03. Installation
- 04. Wiring Diagram
- 04.01. Single Wall Control to Indoor Board
- 04.02. Multiple Wall Control
- 05. Controller Assignment
- 06. Sensor Enable/Calibration
- 07. Enabling Zones and Assigning Sensors
- 08. Minimum and Maximum Zone Positions
- 09. Advance Series Self-Learn Mode (EVV Indoor Models)
- 09.01. Initiating Self-Learn Mode
01. Safety Precautions
- Read all instructions in this manual before operating the air conditioning unit. Failure to do so may result in damage to the unit and void your warranty.
- Turn off the power supply to the unit and follow necessary LOCK-OUT/TAG-OUT (LOTO) procedures to ensure that power supply is not re-energised accidentally.
- This control interface is connected to the wall control terminal block on the Indoor board via screwed terminals and Cat5e UTP (AWG24) Data Cable. Ensure that this unit is not installed on voltages other than specified.
- Make sure that the unit installation complies with all relevant council regulations and building code standards. All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections must follow the electrical diagram provided.
- WH&S rules and regulations must be observed and will take precedence during installation process.
- Only use this Control Interface with an ActronAir air conditioner as described in this installation guide.
02. Specifications
- Voltage: 12VDC +/- 10% (LR7 control connects directly to the Indoor board)
- Data: Cat5e UTP (AWG24) Data Cable, Maximum Cable Length up to 100m
- Operating conditions: -10 to 60°C, < 90% RH non-condensing
- Storage conditions: -20 to 70°C, < 90% RH non-condensing
- Dimensions (mm): 130 x 130 x 14.5 (W x H x D)
NOTE: Do not use ActronAir 4 Core Data Cable Part Numbers: 4070-003/AMDC4 or Non-Twisted Pair multi-core cable.
03. Installation
Step 1: Remove Back Cover
Insert and gently twist a screwdriver into the slots at the top and bottom of the Control Interface. Do this procedure alternately between the four slots until the back cover separates. Use a large enough flat blade screwdriver to fit into the slot to avoid damaging the Control Interface.
Diagram Description: Shows the back cover of the controller with indicated slots for removal.
Step 2: Mount Back Cover to the Wall
Mount the back cover to the wall using screws (not supplied) via the screw holes. If required, the use of a plasterboard mounting bracket (not supplied) is recommended. Ensure that the Control Interface back cover is aligned and leveled on the wall before tightening the screws.
Diagram Description: Illustrates mounting the back cover to a wall, showing screw holes and an optional plasterboard mounting bracket.
Step 3: Connect Wiring at the Back of Control Interface
Ensure that all wiring is tightly connected. All wiring must be in accordance with the provided wiring diagram.
Wall Control Wiring:
- POWER: BROWN / ORANGE
- 485 A: BLUE
- 485 B: BLUE-WHITE
- GND: BROWN-WHITE / ORANGE-WHITE
- NOT USED: GREEN / GREEN-WHITE (CUT OFF AND DO NOT CONNECT)
Diagram Description: Shows the terminal block on the back of the controller with wire color assignments for POWER, 485 A, 485 B, and GND. It also indicates the wire to be cut off.
Step 4: Attach PCB Casing to the Back Cover
Attach the PCB casing by aligning it with the back cover mounted on the wall. Ensure the PCB casing makes a 'click' sound after mounting.
Diagram Description: Illustrates aligning and attaching the PCB casing to the already mounted back cover.
Step 5: Select Zone Buttons
Remove the relevant zone buttons for zone naming and attach them to the wall control. Ensure the buttons make a 'click' sound when attached to the PCB casing.
Diagram Description: Shows the zone buttons being attached to the PCB casing.
Step 6: Attach the Front Cover
IMPORTANT: Ensure the protective film is removed from the inside of the front cover before attaching. After attaching the front cover, check that the Control Interface is aligned and leveled on the wall.
Diagram Description: Shows the front cover being attached to the installed controller.
NOTE: The front cover can be removed even after installation by pressing at the bottom of the control interface and pulling the front cover.
04. Wiring Diagram
04.01. Single Wall Control to Indoor Board
Diagram Description: Shows a single Wall Controller (WC-1) connected to an Indoor Control Board using specific wire colors (BR/OR, BL, BL-WH, BR-WH/OR-WH) for Power, 485 A, 485 B, and GND. The Green/Green-White wire is shown cut off.
Wall Control Wiring:
- POWER: BROWN / ORANGE
- 485 A: BLUE
- 485 B: BLUE-WHITE
- GND: BROWN-WHITE / ORANGE-WHITE
- NOT USED: GREEN / GREEN-WHITE
04.02. Multiple Wall Control
04.02.01. Star Wall Control to Indoor Board
Diagram Description: Depicts multiple Wall Controllers (WC-1) connected in a star configuration to a single Indoor Control Board. Each controller uses the same wire color scheme.
04.02.02. Series Wall Control to Indoor Board
Diagram Description: Illustrates multiple Wall Controllers (WC-1) connected in a series (daisy chain) configuration to an Indoor Control Board. The wiring follows a specific sequence.
Item | Description | Maximum Cable Length |
---|---|---|
ID Control Board to WC-1 | Indoor PCB to Wall Controller 1 | 100 m |
ID Control Board to WC-2, ID Control Board to WC-3 | Indoor PCB to Wall Controller 3 (last controller) | 75m (Daisy Chain)* |
*Maximum Daisy Chain connection is up to 2 Wall Controllers.
05. Controller Assignment
NOTE: For installations where an LR7 is being installed with a Neo Wall Control, C-1 will always need to be assigned to the Neo Wall Control.
Upon initial start-up, all connected LR7 controls (up to 3) will display C-0. After 3 seconds, an auto-assignment process occurs, displaying C-1, C-2, and C-3. The user can change assignments between C-1 and C-3 using the [UP] or [DOWN] buttons. A C-1 controller is required for the system to function correctly, with each controller needing a unique assignment. The displayed text remains until the user presses the [PROG] button to enter the Home Screen. Subsequent power cycles will show controller IDs for 3 seconds before proceeding to the Home Screen.
Manual Controller Assignment
- Press and hold the [REPEAT] and [TIMER] buttons for 3 seconds, then release to enter Service Menu.
- Press the [PROG] button to enter Service Menu 01.
- Press the [UP] or [DOWN] buttons to select the appropriate controller assignment.
- Press the [PROG] button to accept the selection.
- Press the [EXIT] button once to return to Main Screen.
NOTE: If the C-1 controller is disconnected, other LR7 controllers may show an error code (E56 - No main wall controller detected). To troubleshoot: Check the wiring and connection of the C-1 controller. If E56 persists on C-2 and C-3, connect a replacement LR7 controller; it will auto-assign itself on its first power-on cycle.
06. Sensor Enable/Calibration
- Press and hold the [REPEAT] and [TIMER] buttons for 3 seconds, then release to enter Service Menu.
- Press the [DOWN] button to scroll through to Service Menu 02.
- Press the [PROG] button to enter Service Menu 02.
NOTE: The display toggles between sensor name (CS1 - Wall Control Sensor 1) and actual temperature reading. By default, all connected sensors are enabled (ON) with a calibration factor of 0. CS1/CS2/CS3 represent wall controller sensors, and rS represents remote sensors.
- Press the [UP] or [DOWN] buttons to select the appropriate sensor to calibrate or turn ON/OFF.
- Press the [PROG] button to enter Wall Control Sensor settings.
- Press the [UP] or [DOWN] buttons to change the temperature offset of the Wall control sensor.
NOTE: Offset range is ±9, with 0.1 increments per [UP]/[DOWN] button press. The [PROG] button may be pressed to enable/disable the sensor.
- Press the [PROG] button to accept the changes.
- Repeat steps 4-7 to enable/disable and calibrate all applicable sensors.
- Press the [EXIT] button twice to return to Main Screen.
07. Enabling Zones and Assigning Sensors
NOTE: On initial power-up, an automatic zone detection takes place. If zones do not appear upon commissioning, cycling power will enable another automatic zone detection.
- Press and hold the [REPEAT] and [TIMER] buttons for 3 seconds, then release to enter Service Menu. Press the [DOWN] button to scroll through to Service Menu 14.
- Press the [PROG] button to enter Service Menu 14. Press the [UP] or [DOWN] buttons to change the zone you wish to enable or the required zone button on the zone pad. The display will show the zone number, enabled ON/OFF status, and the number of assigned sensors to that zone. The selected zone will also be indicated by the zone's LED on the zone pad.
NOTE: ZONE 1 settings appear by default. Zone 1 is ON by default.
- Press the [PROG] button to enter ZONE 1 settings. Press the [UP] or [DOWN] buttons to toggle between ON and OFF. For this example, switch ON ZONE 1.
- Press the [PROG] button to assign a sensor to the selected zone. Press the [UP] or [DOWN] buttons to cycle through available sensors. For this example, select zone controller sensor C-1.
NOTE: The sensors are determined by what appears on the display screen.
Controller Name | Description | Sensor Name | Description |
---|---|---|---|
C-1 | Wall Control 1 | RS1 | Remote Sensor 1 |
C-2 | Wall Control 2 | RS2 | Remote Sensor 2 |
C-3 | Wall Control 3 | RS3 | Remote Sensor 3 |
Diagram Description: Shows interface elements for zone selection and sensor assignment, including a table listing controller and sensor names.
- Press the [PROG] button to select a second sensor. By default, the value is '---', indicating no assigned second sensor. Press the [UP] or [DOWN] buttons to cycle through available sensors. If a second sensor is selected, the zone temperature will be averaged between the two sensors.
- Press the [PROG] button to return to the zone selection screen. Repeat steps 3-5 to configure zones. Press the [EXIT] button to return to Main Screen.
08. Minimum and Maximum Zone Positions
- Press and hold the [REPEAT] and [TIMER] buttons for 3 seconds, then release to enter Service Menu. Press the [DOWN] button to scroll through to Service Menu 15.
- Press the [PROG] button to enter Service Menu 15. Press the [UP] or [DOWN] buttons to change zones or press the required zone button on the zone pad. The display will show the zone number, enabled ON/OFF status, and the number of assigned sensors to that zone. The selected zone will also be indicated by the zone's LED on the zone pad.
NOTE: ZONE 1 settings appear by default. Detected Zones are ON by default.
- Press the [PROG] button to enter the selected zone's settings. The display will show the zone OPEN percentage and HIGH. By default, this will be 100. Press the [UP] or [DOWN] buttons to change the value.
NOTE: OPEN and HIGH range is 5-100%, with 5% increments per the [UP]/[DOWN] buttons press.
- Press the [PROG] button to accept changes. The display will show the zone CLOSE percentage and LOW. By default, this will be 0. Press the [UP] or [DOWN] buttons to change the value.
NOTE: CLOSED and LOW range is 0-45%, with 5% increments per the [UP]/[DOWN] buttons press.
- Press the [PROG] button to accept changes and return to the zone selection screen. Press the [EXIT] button to return to Service Menu.
09. Advance Series Self-Learn Mode (EVV Indoor Models)
Prerequisites:
- Ensure all connected zones have been detected or enabled.
- Before activating, ensure the following:
- Return air filter, box, and grille are properly installed.
- All doors or any other restrictions that may obstruct the air path back to the return and grille are open.
- Adjustable outlets should be in open position and System Air Balance should be complete.
09.01. Initiating Self-Learn Mode
- System should be in the OFF MODE before activating self-learn mode.
- Press and hold the [FAN SPEED] button and the [MODE] button (or similar power/mode button) for 5 seconds, or until the word "Lrn" appears on the display, then release.
- Press the [FAN SPEED] button once and release.
- "AUTO" will flash on the controller display during programming of self-learn mode.
NOTES:
- If a self-learn passes, "PAS" will display on the wall controller.
- If a self-learn fails, "FAL" will display on the wall controller.
Note: Refer to Service Manual for troubleshooting.
To return to Main Menu, press [EXIT]. To cancel Self-learn Mode, press the [MODE] button or [EXIT].