Hormann HE 331 Aluminium Fire-Resistant Fixed Glazing
Datenblatt (Datasheet)
Main Function
- Fire-resistant F30 (30 minutes)
- Smoke-tight according to DIN 18095
Optional Performance Features
Depending on the specific configuration:
- Sound insulation up to 44 dB
- Burglar resistance RC2/RC3
- Slight-obstacle safety A/C2
Product Description
- Approval Number: Z-19.14-1091
- Profile Material: Aluminium frame profiles DIN 1725, 2-shell with thermal insulation through quality-secured, shear-resistant composite of Polyamide 6.6, 25% glass fiber reinforced.
- Visible Width of Leaf / Frame: 70 mm
- Construction Depth: 80 mm
- Base Height: 150/105/70 mm
- Mullion Height: 100 mm
- Filling: Fire-resistant glass F30, suitable for interior use as standard. Optional with panel or combination of panel/glass.
- Extender Profiles: 25, 50, 100 or 150 mm
- Glass Retaining Strips: Optionally on hinge side or hinge opposite side
Dimensions with Glazing Bead (in mm)
Frame Outer Dimension | Width | Height |
---|---|---|
Frame Outer Dimension | 300 - unlimited | 300-4960/45001) |
Maximum Door Height | 3000 mm |
1) for installation of a door in the glazing
Surfaces
- Standard: High-quality powder coating in RAL9016 matt
- Anodized: Anodized surface E6 / EV1
- RAL on Request: High-quality powder coating in RAL of choice
Gloss Levels: Matt or Matt Fine Structure (Gloss Level 30 ± 5), Satin Gloss (Gloss Level 75 ± 10). High Gloss (Gloss Level > approx. 85, gloss points according to ISO 2813, 60 degree measuring angle) available on request.
Performance Features Achieved Values
Feature | Achieved Value | Function |
---|---|---|
Fire Protection | F30 according to DIN 4102 | ● |
Smoke Protection | according to DIN 18095 | ● |
Sound Insulation | up to 44 dB | ● |
Burglar Resistance | RC2/RC3 | ● |
Slight-Obstacle Safety | A/C2 according to DIN 18008-4 | ● |
The specified performance features are only achieved with the corresponding equipment. The values depend on the door equipment and installation situation.
● Main function - standard
○ Additional function - optional with corresponding equipment
Permissible Walls and Minimum Wall Thicknesses
Minimum Wall Thicknesses (Frame Height):
Permissible Walls | ≤ 3000 mm | ≤ 4000 mm |
---|---|---|
Masonry according to DIN 1053-1, Stone strength class ≥ 12, Mortar group ≥ II | ≥ 115 mm | ≥ 115 mm |
Concrete according to DIN 1045-1, Strength class ≥ C12/15 | ≥ 100 mm | ≥ 100 mm |
Aerated concrete block or plain blocks according to DIN 4165, Strength class 4 | ≥ 115 mm | ≥ 175 mm |
Aerated concrete slabs with general building approval (abZ), Strength class G.4 | ≥ 115 mm | ≥ 175 mm |
Framed walls F30 A according to DIN 4102-4, Table 10.2 | ≥ 100 mm | ≥ 100 mm |
Framed walls F30 B according to DIN 4102-4, Table 10.3 | ≥ 100 mm | ≥ 100 mm |
Framed wall according to AbP2) | as per test certificate | as per test certificate |
For burglar-resistant doors:
Permissible Walls | RC2 | RC3 |
---|---|---|
Masonry according to DIN 1053-1, Stone strength class ≥ 12, Mortar group ≥ II | ≥ 115 mm | ≥ 115 mm |
Concrete according to DIN 1045-1, Strength class ≥ C12/15 | ≥ 100 mm | ≥ 120 mm |
Aerated concrete block or plain blocks according to DIN 4165, Strength class 4 | ≥ 170 mm | ≥ 240 mm |
2) AbP: General building approval
Cross-sections and Dimension References
Diagrams showing cross-sections of the frame and mullion construction, as well as wall connections for different mounting types (plug mounting, welding mounting, screw mounting) in masonry/concrete and lightweight walls.
Note: The information provided, especially details and illustrations, is non-binding and does not constitute an agreement on quality or a guarantee. Changes and errors are expressly reserved. This datasheet is protected by copyright. Reprinting, even in part, is only permitted with our authorization.