Hormann Aluminium Fire Protection Element A / RS 200, as Exterior Door

Main Functions

Dimensions with Frame (in mm)

Feature Width Height
Outer Frame Dimension 1355-3000 1740-3000
Clear Passage (90° Opening) 1067-2712 1670-2930
Clear Passage (180° Opening) 1215-2860 1670-2930
Mullion Gang Leaf 750-1500
Mullion Fixed Leaf 500-1500

Product Description

Profile Material: Aluminium frame profiles made of extruded profiles DIN 1725, 2-shell with thermal insulation through quality-assured, shear-resistant compound made of polyamide 6.6, 25% glass fiber reinforced.

Face Width Leaf / Frame: 150 mm

Installation Depth: 80 mm

Sill Height: 105 / 150 mm

Sprocket Height: 100 mm

Filling: ISO safety glass 24 mm, optionally with panel or combination of panel / glass.

Widening Profiles: 25, 50, 100 or 150 mm

Glass Retaining Strips: Optionally on hinge side or opposite hinge side.

Security Bolts: RAM height 2620 mm 1 bolt, ≤ RAM height 3000 mm 2 bolts per leaf.

Standard Fittings

Further fittings can be found in our dealer price list Part C and in the product configurator.

Surfaces

Performance Characteristics

Feature Achievable Values Function
Smoke Protection S200 ● (Main function - standard)
Thermal Insulation Up to 1.6 W/(m²·K)
Sound Insulation Up to 40 dB
Burglar Resistance RC2
Resistance to Wind Load Class C2 / B2
Driving Rain Tightness Up to Class 3A with thermally separated sill
Driving Rain Tightness Up to Class 1A with retractable bottom seal
Air Permeability Class 3
Operating Forces Class 2
Differential Climate Behavior Class 2(d) / 2(e)

The specified performance characteristics are only achieved with the corresponding equipment. The values depend on the door equipment and installation situation.

● Main function - standard

○ Additional function - optional with corresponding equipment

Permissible Walls and Minimum Wall Thicknesses

Wall Type Minimum Wall Thickness (RAM Height) Burglar Resistance RC2 Burglar Resistance RC3
Masonry according to DIN 1053-1, Stone Strength Class ≥ 12, Mortar Group ≥ II ≥ 115 ≥ 115
Concrete according to DIN 1045-1, Strength Class ≥ C12/15 ≥ 100 ≥ 100
Aerated Concrete Block Stones or Aerated Concrete Plan Stones according to DIN 4165, Strength Class 4 ≥ 150 ≥ 170 ≥ 240
Reinforced - horizontal or vertical - Aerated Concrete Slabs with general building approval (abZ), Strength Class G.4 ≥ 150 ≥ 170 ≥ 240
Fire-rated Walls F90-A according to DIN 4102-4, Table 10.2 ≥ 100 ≥ 120
Fire-rated Walls F90-B according to DIN 4102-4, Table 10.3 ≥ 100 ≥ 120
Fire-rated Wall according to abP According to test certificate

For burglar-resistant doors:

Wall Type Minimum Wall Thickness (RAM Height) RC2 RC3
Masonry according to DIN 1053-1, Stone Strength Class ≥ 12, Mortar Group ≥ II ≥ 115 ≥ 115
Concrete according to DIN 1045-1, Strength Class ≥ C12/15 ≥ 100 ≥ 100
Aerated Concrete Block Stones or Aerated Concrete Plan Stones according to DIN 4165, Strength Class 4 ≥ 150 ≥ 170 ≥ 240

Cross-sections and Dimension References

Diagram showing various cross-sections and dimension references for the door frame and components. Includes labels like RAM (Outer Frame Dimension), LDM (Clear Passage Dimension), LDH (Clear Passage Height), LDVB (Clear Passage Glazing Width), LDVH (Clear Passage Glazing Height), OFF (Top of Finished Floor).

Wall Connections

Diagrams illustrating different wall connection types for masonry and lightweight walls, including dowel mounting, welding mounting, and surface-mounted screwing. Each diagram shows the connection detail with labels indicating the wall type and mounting method.

Masonry / Concrete: Dowel Mounting

Masonry / Concrete: Welding Mounting

Masonry / Concrete: Surface-Mounted Screwing

Lightweight Walls: Welding Mounting

Lightweight Walls: Surface-Mounted Screwing

Lightweight Walls: Screwing Mounting

Door Seal Standard

Plastic bottom seal standard.

Optional with retractable bottom seal.

The information provided, especially the specifications and illustrations, is non-binding and does not constitute an agreement on quality or a guarantee. Subject to changes and errors. The data sheet is protected by copyright. Reprinting, including excerpts, only with our permission.

PDF preview unavailable. Download the PDF instead.

DB ARS200 Aussen DE Acrobat Distiller 25.0 (Windows)

Related Documents

Preview Hormann Aluminium Rauchschutz Element A / RS 100 Exterior Door Data Sheet
Detailed technical data sheet for the Hormann Aluminium Rauchschutz Element A / RS 100 exterior door, including dimensions, materials, performance characteristics, and installation details.
Preview Hormann Aluminium Rauchschutz-Element A / RS 100 Interior Door Datasheet
Technical datasheet for the Hormann Aluminium Rauchschutz-Element A / RS 100 interior door, detailing its features, dimensions, materials, and performance characteristics including smoke protection, sound insulation, and burglary resistance.
Preview HÖRMANN HE 321 Aluminium Fire-Resistant Exterior Door - Technical Data Sheet
Technical specifications and features of the HÖRMANN HE 321 aluminium fire-resistant exterior door, including fire resistance, security, sound insulation, and dimensions.
Preview Hormann Aluminium Fire Protection Element A / RS 350 Fixed Glazing Datasheet
Technical datasheet for the Hormann Aluminium Fire Protection Element A / RS 350, designed as fixed glazing. Details include material, dimensions, performance characteristics like smoke and sound insulation, and installation options for various wall types.
Preview Hormann Aluminium Fire-Resistant Interior Door A / RS 200 Datasheet
Technical datasheet for the Hormann Aluminium Fire-Resistant Interior Door A / RS 200, detailing its features, dimensions, materials, and performance characteristics.
Preview Hormann HE 331 Fire-Resistant Fixed Glazing Datasheet
Technical datasheet for the Hormann HE 331 Aluminium Fire-Resistant Fixed Glazing element, detailing its specifications, performance features, and installation guidelines.
Preview General Technical Approval for Fire Protection Closures: T 30-1-FSA "H3 S-1" and T 30-1-RS-FSA "H3 S-1"
This document outlines the general technical approval (bauaufsichtliche Zulassung) and general construction type approval (Bauartgenehmigung) for the T 30-1-FSA "H3 S-1" and T 30-1-RS-FSA "H3 S-1" fire protection closures manufactured by HÖRMANN KG Freisen. It details the scope of approval, technical specifications, installation requirements, and conditions for use, ensuring compliance with German building regulations for fire safety.
Preview HÖRMANN M4.1 Steel Doors: Planning, Fitting, Operating, and Maintenance Guide
Comprehensive guide for HÖRMANN M4.1 single-leaf and double-leaf steel doors (H60 OD, H120 OD). Covers planning, fitting, operation, maintenance, and safety instructions.