R. STAHL 8530/1-MCB-STA101-C40-500-2 Line Protection Circuit Breaker
Article Number: 294003
Product Overview
The R. STAHL 8530 series line protection circuit breakers, specifically the 8530/1-MCB-STA101-C40-500-2 model, offer excellent current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity with upstream fuses. These components are modular and available in 1 to 4-pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key features include:
- Switch-disconnector function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or extension of existing systems due to modular design
- Simple snap-on mounting on a DIN rail in Ex e enclosures
- Fixed magneto-thermal trip units
- Ergonomic lever for safe operation and shutdown
- Padlockable (accessories) to prevent re-operation during maintenance
Technical Characteristics
Explosion Protection
Characteristic | Value |
---|---|
Application Area (Zones) | 1, 2 |
Application Area (Zones) Note | Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure |
IECEx Certificate Gas | IECEx FMG 19.0029U |
IECEx Protection Against Gas Explosion | Ex db eb IIC Gb |
ATEX Certificate Gas | FM19ATEX0191U |
ATEX Protection Against Gas Explosion | II 2G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Conformity Certificate | ATEX Conformity Certificate |
Electrical Characteristics
Characteristic | Value |
---|---|
Rated Operational Voltage AC | 230 V |
Rated Operational Current | 40 A |
Frequency | 50/60 Hz |
Rated Ultimate Short-Circuit Breaking Capacity | 10 kA |
Electrical Endurance | 104 |
Mechanical Endurance | 2 x 104 |
1st Auxiliary Function | Auxiliary contact: 1 changeover contact + signal contact: 1 changeover contact |
Voltage 1st Auxiliary Function AC | 230 V |
Max. Current 1st Auxiliary Function | 2 A |
2nd Auxiliary Function | None |
Max. Voltage 2nd Auxiliary Function DC | - |
Tripping Characteristic | C |
Number of Poles | 1-pole |
Ambient Conditions
Characteristic | Value |
---|---|
Ambient Temperature | -40 °C ... 70 °C |
Ambient Temperature | -40 °F ... 158 °F |
Ambient Temperature Note | Ambient temperatures differing based on current certificates, upon request |
Mechanical Characteristics
Characteristic | Value |
---|---|
Degree of Protection (IP) (IEC 60529) | IP2X |
Enclosure Material | Thermoplastic |
Minimum Connection Terminal Size | 1.5 mm² |
Maximum Connection Terminal Size | 25 mm² |
Minimum AWG Connection Terminal Size | 16 AWG |
Maximum AWG Connection Terminal Size | 4 AWG |
Minimum Connection Terminal Size 2 | 1.5 mm² |
Maximum Connection Terminal Size 2 | 10 mm² |
Minimum AWG Connection Terminal Size 2 | 16 AWG |
Maximum AWG Connection Terminal Size 2 | 8 AWG |
Min. Connection Terminal for Aux. Contact | 0.5 mm² |
Max. Connection Terminal for Aux. Contact | 4 mm² |
Min. AWG Connection Terminal for Aux. Contact | 18 (unece.unit.AWG) |
Max. AWG Connection Terminal for Aux. Contact | 14 (unece.unit.AWG) |
Minimum Tightening Torque | 2 N·m |
Maximum Tightening Torque | 3 N·m |
Connection Terminal Note | Connection for 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) |
Width | 65 mm (2.56 in) |
Length | 165 mm (6.5 in) |
Mounting Depth | 138.3 mm (5.44 in) |
Weight | 1 kg (2.205 lb) |
Mounting / Installation
Characteristic | Value |
---|---|
Tightening Torque | 2-3 N·m |
Tightening Torque in lbf·in | 17.7 ... 26.6 lbf·in |
Tightening Torque Auxiliary Contact | 0.4 – 0.6 N·m |
Tightening Torque Auxiliary Contact lbf·in | 3.5 ... 5.3 lbf·in |
Technical Drawings
Tripping Characteristic Curve C
The graph shows the tripping characteristic for AC and DC currents, indicating the time in seconds for tripping based on multiples of the rated current (I/In). The curve is labeled as 'limite à partir de l'état froid' (limit from cold state).
Outline Drawing (all dimensions in mm [inches])
Diagrams showing the dimensions of the circuit breaker, including width, height, and depth, with specific measurements provided in both millimeters and inches.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
- Part Number: 227232
Fixing Kit
A fixing kit for mounting the component onto a DIN rail-less mounting plate.
- Part Number: 276618
Cylinder Lock
For locking (shackle Ø 3)
- Part Number: 107115