4-Way Cassette Heat Pump System

Submittal Data Sheet

Brand: Blue Ridge

Model Series: XS3 CC

Features ENERGY STAR certification, AHRI Certified, and ETL Listed compliance.

General Information

FieldValue
Location
Engineer
Submitted to
Submitted by
Reference
Approval
Date
Construction
Unit #
Drawing #

Specifications

Indoor Unit Specifications

ParameterValue
Indoor Air Flow (Turbo/H/M/L/Si)447.3/388.5/317.8/194.2/147.2 CFM
Indoor Noise Level (Turbo/H/M/L/Si)48/44.0/41.0/28.5/24.5 dBA
Dimension (W×D×H)22.44 x 22.44 x 9.65 inch / 570.0×570.0×245.0 mm
Package (W×D×H)28.15 x 25.20 x 11.61 inch / 715×640×295 mm
Net/Gross Weight35.27/41.89 lbs / 16.0/19.0 kg

Outdoor Unit Specifications

ParameterValue
Compressor TypeROTARY
Compressor ModelKSN140D58UFZ
RefrigerantR454B
Refrigerant Oil Charge440 mL
Refrigerant OilVG74
Outdoor Air Flow (Max)1765.8 CFM
Outdoor Noise Level57.5 dBA
Dimension (W×D×H)35.04 x 13.46 x 26.50 inch / 890.0×342.0×673.0 mm
Package (W×D×H)39.17 x 15.67 x 29.13 inch / 995×398×740 mm
Net/Gross Weight92.59/100.31 lbs / 42.0/45.5 kg

Electrical Specifications

ParameterValue
Power Supply208/230V, 60Hz, 1Ph
System MCA18.00 A
Connection Wiring14#x4
System MOCP20 A
Compressor RLA10.0 A
Outdoor Fan Motor RLA0.9 A
Outdoor Fan Motor W80 W
Indoor Fan Motor RLA1.0 A
Indoor Fan Motor W45 W
System Power Input @ Cooling1344 (490~1620) W
System Power Input @ Heating1570 (395~1930) W
MCA: Min. circuit amps(A)
MOCP: Max. over current protection(A)
RLA: Rated load amps(A)
W: Fan motor rated output(W)

Piping Specifications

ParameterValue
Throttle type (Indoor)N/A
Throttle type (Outdoor)EXV+Throttle valve
Liquid Size6.35mm (1/4in)
Gas Size12.7mm (1/2in)
Max. Piping Length98.40 ft (30 m)
Max. Height Difference65.60 ft (20 m)
Max. Pre-charged Length24.6 ft (7.5 m)
Refrigerant Pre-charged Amount47.97 oz (1.36 kg)
Additional Charge of Refrigerant0.16 oz/ft (15 g/m)
Connection MethodFlared

Performance Data

Efficiency

CategoryValue
Cooling (SEER2)20.7
Cooling (EER2)12.5
Heating (HSPF2-4)11.4
Heating (COP)3.36

Performance of Cooling

ParameterValue
Rated Capacity16800 Btu/hr
Min/Max Capacity5300~17800 Btu/hr
Moisture Removal2.05 L/h
Standard Operating Range-13~122 °F (-25~50 °C)
ConditionsIndoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB

Performance of Heating

ConditionValue
1. @ 47°F Rated Capacity18000 Btu/hr
1. @ 47°F Min/Max Capacity7100~21500 Btu/hr
2. @ 17°F Rated Capacity13900 Btu/hr
3. @ 5°F Rated: Capacity / COP12800 / 2.20
3. @ 5°F Max: Capacity12800 Btu/hr
Standard Operating Range-13~75 °F (-25~24 °C)
1. ConditionsIndoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB
2. ConditionsIndoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB
3. ConditionsIndoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB

Features

Dimensions and Installation

Indoor Unit Dimensions

The indoor unit is a rectangular cassette designed for ceiling installation. Key dimensions include a body width of approximately 22.5 inches (570mm), depth of 20.8 inches (531mm), and height of 9.6 inches (245mm). The front panel, which is visible when installed, has dimensions of approximately 24.4 inches (620mm) by 24.4 inches (620mm). Connections are located on the side of the unit, including liquid and gas refrigerant lines, a 1-inch (25mm) drain pipe, and a wiring connection port. A fresh air intake is also indicated.

Outdoor Unit Dimensions

The outdoor unit is a rectangular box shape with a fan grille on the front. Key dimensions include a width of approximately 35.0 inches (890mm) (or 35.25 inches/895mm overall), a depth of 13.5 inches (342mm) (or 13.75 inches/348mm overall), and a height of 26.2 inches (663mm) (or 26.5 inches/673mm overall). Various connection points and mounting details are shown, labeled with dimensions.

Installation Instructions and Clearances

Indoor Unit Installation: Requires specific ceiling clearances. A minimum of 59.1 inches (150cm) is recommended vertically from the ceiling to the unit, with 78.7 inches (200cm) recommended. Horizontal clearances from walls or obstructions are also specified: greater than 59.1 inches (150cm) on sides, greater than 78.7 inches (200cm) from the front, and greater than 90.6 inches (230cm) from the rear. The unit requires a ceiling hole and a front panel. A table provides specific distances from the ceiling and ceiling hole dimensions for different models:

MODELLength of A (Ceiling Hole)Length of H (Distance from Ceiling)Length of B (Overall Width)
9K/12K/18K9.6in (245mm)>10.8in (275mm)23.6in (600mm)
24K8.03in (205mm)9.06in (230mm)
36K9.65in (245mm)10.7in (271mm)35.4in (900mm)
48K11.3in (287mm)12.3in (313mm)

Outdoor Unit Installation: Requires adequate ventilation space. Minimum clearances are specified: 20 inches (500mm) or more on the front and sides when the unit is clear, and 14 inches (350mm) or more on the rear. If two sides (left, right, rear) are clear, 20 inches (500mm) is required on those sides. 4 inches (100mm) or more is required on the remaining sides.

PDF preview unavailable. Download the PDF instead.

blueridgebxs3a18sc0-18cc4specificationssheet 2FEFE663-D23F-4809-A3D1-98FFDEAC6CC8 Google Sheets

Related Documents

Preview Blue Ridge 4-Way Cassette Heat Pump System: Submittal Data Sheet, Specifications, and Installation
Comprehensive submittal data sheet for the Blue Ridge 4-Way Cassette Heat Pump System (Model EKPQ420D1UMUA). Includes detailed efficiency ratings, cooling and heating performance, indoor and outdoor unit specifications, electrical and piping data, dimensional drawings, and installation clearance requirements.
Preview Blue Ridge Slim Duct Heat Pump System: Submittal Data Sheet & Specifications
Detailed submittal data sheet for the Blue Ridge Slim Duct Heat Pump System, including specifications, performance data, dimensions, and installation clearances. Features R454B refrigerant and Energy Star certification.
Preview Blueridge XS5 CC 4-Way Cassette Heat Pump System Submittal Data Sheet
Comprehensive submittal data sheet for the Blueridge XS5 CC 4-Way Cassette Heat Pump System, featuring R454B refrigerant. Includes detailed specifications, performance data for cooling and heating, electrical requirements, piping information, and installation clearance guidelines.
Preview Blue Ridge XS5 FC Ceiling & Floor Heat Pump System Submittal Data Sheet
Submittal data sheet for the Blue Ridge XS5 FC Ceiling & Floor Heat Pump System, detailing specifications, performance, dimensions, and features for HVAC applications.
Preview Blue Ridge XS5 CDH High Static Slim Duct Hyper Heat Series Submittal Data Sheet
Submittal data sheet for the Blue Ridge XS5 CDH High Static Slim Duct Hyper Heat Series heat pump system, detailing efficiency ratings, cooling and heating performance, indoor and outdoor specifications, electrical requirements, piping details, installation guidelines, and fan performance.
Preview Blue Ridge XS3 LW Series R454B Console Heat Pump Technical Specifications
Comprehensive technical specifications for the Blue Ridge XS3 LW Series R454B Console Heat Pump. This document details cooling and heating performance metrics, indoor and outdoor unit specifications, electrical requirements, piping details, and key features. Designed for efficiency and performance, it includes Energy Star certification information.
Preview Blue Ridge High Wall Heat Pump System: Technical Specifications and Installation Guide
Comprehensive technical specifications, performance data, electrical requirements, and installation guidelines for the Blue Ridge High Wall Heat Pump System, including SEER2, HSPF2-4, and detailed operating conditions.
Preview Blue Ridge DS2 High Wall Heat Pump System - Submittal Data Sheet
Detailed submittal data sheet for the Blue Ridge DS2 High Wall Heat Pump System, including specifications for cooling, heating, electrical, piping, dimensions, and installation clearances. Features include humidity control and WiFi capability.