EMS Kontrol KT-201/241/261 Duct Type Carbon Dioxide Transmitter

User Manual

[EMS Kontrol logo]

Model Numbers: KT-201, KT-241, KT-261

What is it?

The Carbon Dioxide Transmitter measures the carbon dioxide value precisely and outputs it as an analog signal.

How does it work?

It can operate with a supply voltage between 12 V DC and 24 V DC. Measurement values are taken from the analog output terminals and transferred to the desired location.

General Features

Areas of Use

Rules to be Considered for Safety

  1. Always read the user manual before using the device and its apparatus.
  2. Damages caused by opening, breaking, or misuse of the plastic parts of the device and its apparatus are considered out of warranty.
  3. Keep the device and its apparatus away from external influences such as liquid, high dust, high temperature, etc., and protect them.
  4. Do not expose the device cables to any jamming and pressure.
  5. Disconnect the electrical power when your device is not used for a long time.
  6. Our devices and apparatus should be used by paying attention to the points in the user manual. In case of damages and malfunctions arising from external use (liquid contact, falling to the ground, etc.), ask for help from the service.
  7. Failures due to electrical connection errors and electrical voltage or current errors are not covered by the warranty.

Dimensions

Diagram showing dimensions:

Technical Data

ParameterValue
Product NameDuct Type Carbon Dioxide Transmitter
Supply Voltage12-24 V DC
Output0-10 V / 4-20 mA / Modbus
Measurement Range0-5,000 ppm / 0-10,000 ppm
Precision± 10 ppm
Accuracy± 50 ppm + %2
Operating Temperature(-10°C) - (+55°C)
Operating Hum. Range20-80%
Storage Temperature(-20°C) - (+60°C)
Protection ClassIP 67 (Excluding air entrance for sensor)

Wiring Diagrams

0-10 V / 4-20 mA Wiring:

Modbus RTU Wiring:

Installation

  1. Unpack the product and open the top cover.
  2. Make cable connections accordingly.
  3. If the product will be mounted on the wall, use the screws and dowels provided in the package.
  4. The device starts measuring 30 seconds after being energized. It is recommended that the product remains in the environment for at least 5 minutes to obtain stable measurement values.
  5. It is recommended to use shielded cable as the communication cable to prevent communication signals from being affected by external influences.
  6. Since the communication cable will create resistance, check the measurement values again after cable installation.

LED Meanings

LEDStatusMeaning
Power (Red)OnNormal Operation
Power (Red)OffNo Power / Error
Status (Green)OnMeasurement in Progress / Normal
Status (Green)OffPreparation / Idle
Status (Green)BlinkingCalibration Active
Status (Green)Rapid BlinkingCalibration Process Started

Modbus RTU Communication Structure

The RS485 Baud rate in Modbus communication is 9600 by default. Stop bit: 1, Parity: NONE. Default Slave ID is 83. The Carbon Dioxide value is stored in the holding register at address 2 (40003). Carbon Dioxide information can be obtained by reading these registers.

Register Map and Default Values:

Register AddressDefault ValueRead/WriteMin. ValueMax. Value
Slave ID 0 (40001)83R/W1247
Baud rate 1 (40002)3R/W08
CO2 Value 2 (40003)-R--

Slave ID and Baud rate can be changed via Modbus communication. To change the Slave ID, write the desired value to the register with address 0 (40001). To change the Baud rate, write the value for the desired Baud rate according to the table below into the register with address 1 (40002).

Baud Rate Settings:

Min. ValueMax. Value
0 (1200)8 (115200)
1 (2400)
2 (4800)
3 (9600)
4 (14400)
5 (19200)
6 (38400)
7 (57600)

Press and hold the "Calibration" button to reset changes made to the Slave ID or Baud rate to their default values. Wait until the Status (green) LED turns off (approximately 30 seconds). After the LED turns off, release the button. The Slave ID and Baud rate will be returned to their default values.

Before Calibration

  1. The product is sold as calibrated. Please do not calibrate unless necessary.
  2. Perform calibration only when it is certain that the product is measuring incorrectly.
  3. Compare the measurement value of the device with another device or with a clean and open air environment for control.
  4. If the device measures values outside the range of 350 ppm - 450 ppm in clean and open air, calibration can be performed.

Calibration

  1. Select a clean and open area away from any carbon dioxide source for calibration.
  2. The amount of carbon dioxide in clean and open air varies between 350 ppm - 450 ppm. When calibration is done, the product sets the value at the time of calibration to 400 ppm.
  3. When the "Calibration" button on the product is pressed, the Status (green) LED starts blinking. Release the button when the LED is fully lit (approximately 10 seconds) to start the calibration process. The Status LED will then blink rapidly. The calibration process is completed when the blinking stops.

Declaration of Conformity

Headquarters and place of production: Halkapınar Mah. 1376 Sok. Boran Plaza No:1/L Konak / İZMİR - TÜRKİYE. EMS KONTROL ELEKTRONİK VE MAKİNE SAN. TİC. A.Ş. declares that the product marked with CE, whose name and specifications are given below, covers the specified directives and provisions.

Brand: EMS KONTROL

Product Name: KT- 2XX

Product Type: Duct Type Carbon Dioxide Transmitter

Compatible Directives:

Additional information: This product can be used in combination with other devices, and compliance with the directives covers only the product. EMS KONTROL is not responsible for the compliance of the entire system with the directives. This declaration is not valid if the product is modified without our approval.

[CE conformity mark]

Warranty Terms

  1. The warranty period of the devices and apparatus starts from the invoice date and is guaranteed for 2 years against manufacturing defects.
  2. Devices and apparatus are delivered to the customer in working condition from our company. On-site commissioning is subject to a service fee.
  3. The repair of devices and apparatus under warranty is carried out at our company. In on-site services, transportation and accommodation expenses of the service personnel belong to the customer. The cost of working time spent on the road is added to the service fee and collected in advance.
  4. Maintenance of devices and apparatus is done at our company. Transportation fees to and from our company for maintenance belong to the customer.
  5. In case of malfunction of devices and apparatus within the warranty period, whether the malfunction is caused by the customer or the manufacturer is tested at our company and reported.
  6. If manufacturer-induced faults are detected within the warranty period, the customer may request a replacement or full repair coverage, provided it does not exceed the product price.
  7. If faults are determined to be caused by the customer, all costs belong to the customer.
  8. If the customer does not indicate awareness of defects from the warranty start date or is expected to be aware, they cannot benefit from Article 6.
  9. Failures arising from the use of devices and apparatus contrary to the user manual are not covered by the warranty.
  10. Devices and apparatus are not covered by the warranty if they are beaten, broken, or scratched by the customer.
  11. Damages caused by the use of devices and apparatus of other brands and models without manufacturer approval are not covered by the warranty.
  12. Errors caused by rusting, oxidation, and liquid contact due to working in dusty/acidic/humid environments are not covered by the warranty.
  13. Damages that may occur during transportation of devices and apparatus are not covered by the warranty. Transportation insurance can be obtained if the customer wishes.
  14. Damages caused by mains voltage or faulty electrical installation are not covered by the warranty.
  15. Devices and apparatus are not covered by the warranty in case of malfunctions caused by force majeure such as fire, flood, earthquake, etc.
  16. All parts of the devices and apparatus are covered by our company's warranty.
  17. If devices and apparatus malfunction within the warranty period, the repair time is added to the warranty period. The repair period shall not exceed 20 working days, starting from the notification date.
  18. Despite the consumer's right to repair, if the product fails frequently, exceeds repair time, or cannot be repaired (as determined by service), the customer may request a refund or price reduction.
  19. Customers may file complaints and objections with consumer courts or arbitration committees.
  20. The warranty certificate must be kept by the customer. A second document will not be issued if lost. Repair and replacement will be charged if the document is lost.

This device is a Waste Electrical and Electronic Device (WEEE) according to European directives 2002/96/EC. Before scrapping or discarding, prevent potential negative consequences for the environment and human health. This symbol on the product indicates it should not be treated as household waste and must be delivered to electrical and electronic waste collection points. Disposal must comply with local environmental regulations.

[WEEE symbol indicating separate collection for electrical and electronic waste]

Manufacturer Information

Manufacturer: EMS KONTROL ELEKTRONİK VE MAKİNE SAN. VE TİC. A.Ş.

Address: Halkapınar Mah. 1376 Sokak Boran Plaza No:1/L Konak / İzmir-TÜRKİYE

Telephone: 0 (232) 431 2121

E-Mail: info@emskontrol.com

[Company Stamp Area]

Product Details:

Vendor Company Details:

EMS Kontrol reserves the right to make changes and improvements to the product specifications and user manual. For all changes, please visit emskontrol.com.

[EMS Kontrol logo]

Models: KT-201 Duct Type Carbon Dioxide Transmitter, KT-201, Duct Type Carbon Dioxide Transmitter, Carbon Dioxide Transmitter, Dioxide Transmitter, Transmitter

File Info : application/pdf, 2 Pages, 1.76MB

PDF preview unavailable. Download the PDF instead.

KT-2XX-User-Manual-Rev-2.9

References

Corel PDF Engine Version 21.2.0.706 CorelDRAW 2019

Related Documents

Preview EMS Kontrol KT-501/541/561 Temperature, Humidity, Carbon Dioxide Transmitter User Manual
User manual for the EMS Kontrol KT-501/541/561 series transmitters, detailing features, technical specifications, installation, Modbus RTU communication, and calibration for measuring temperature, humidity, and CO2.
Preview EMS KONTROL KT-306/346/366 Humidity and Carbon Dioxide Transmitter User Manual
User manual for the EMS KONTROL KT-306, KT-346, and KT-366 Humidity and Carbon Dioxide Transmitters. Covers technical data, installation, Modbus RTU communication, calibration, safety, and warranty information.
Preview EMS Kontrol KT-601/641/661 User Manual: Temperature, Humidity, CO2 Transmitter
User manual for EMS Kontrol KT-601, KT-641, KT-661 transmitters measuring temperature, humidity, and carbon dioxide. Includes technical data, installation, calibration, and warranty information.
Preview EMS Kontrol KT-3X1 Carbon Dioxide Transmitter User Manual
User manual for the EMS Kontrol KT-3X1 Carbon Dioxide Transmitter, detailing its features, operation, installation, and warranty.
Preview EMS KONTROL OT-301/341/361 Oxygen Transmitter User Manual
User manual for the EMS KONTROL OT-301/341/361 Oxygen O2 Transmitter, detailing technical specifications, installation, operation, Modbus communication, and warranty information.
Preview EMS Kontrol KR-415 Carbon Dioxide Control Device User Manual
User manual for the EMS Kontrol KR-415 Carbon Dioxide Control Device, detailing its features, technical specifications, installation, operation, and warranty information.
Preview EMS Kontrol OT-401/441/461 Oxygen Transmitter User Manual
User manual for the EMS Kontrol OT-401, OT-441, and OT-461 Oxygen Transmitters. Covers product features, technical specifications, installation, Modbus RTU communication, safety guidelines, warranty terms, and declaration of conformity.
Preview EMS Kontrol BT-405/445/465 Differential Pressure Transmitter User Manual
User manual for the EMS Kontrol BT-405, BT-445, and BT-465 Differential Pressure Transmitters, detailing features, technical specifications, installation, Modbus communication, calibration, and warranty information.