Lennox VVCD048S6-5P VRF Vertical Air Handler Submittal Data
Powered by Samsung
General Information
- Compatible with R-32 VRF air, water, and mini-VRF systems.
- The system features a built-in Wi-Fi adapter as standard, allowing control and monitoring via the Samsung SmartThings app.
Construction
Constructed from insulated, galvanized steel.
Refrigerant System
- Features a mechanically bonded aluminum fin to copper tube heat exchanger.
- Refrigerant flow is controlled by an electronic expansion valve located at the indoor unit.
- Includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Offers three fan speeds and an auto setting.
Controls
- Control wiring utilizes 2 x 16 AWG wire.
- The unit is operated via a wired remote controller, model VSTAT04P-1 (purchased separately).
- Supports dual set temperature when connected to compatible controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- Provides external heat control functionality, allowing configuration of fan operation during auxiliary heat, defrost, and emergency heat modes (VSTAT10P-1 accessory required when controlling heating devices other than V1EHK0*-1P electric heat kits).
- Configuration settings include options for outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency heat functionality ensures the system continues to control the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
- Features an Emergency Temperature Output (ETO) function. This function outputs a signal to an external source (e.g., backup system, building management system, alert device like a status light, warning lamp, or buzzer) when the indoor unit is in an error status or when room temperature exceeds a configurable temperature level.
Specifications
Specification | Value |
---|---|
Indoor Unit Model Number | VVCD048S6-5P |
Nominal Capacity (Cooling) | 48,000 Btu/h |
Nominal Capacity (Heating) | 54,000 Btu/h |
Voltage | 1 / 208-230 / 60 Hz |
Operating Current (max.) (Cooling) | 2.07 A |
Operating Current (max.) (Heating) | 2.07 A |
MCA | 3.1 A |
MOP | 15 A |
Evaporator Fan Type | Constant Torque With Double-inlet, Forward Curve, Centrifugal Fan |
Consumption | 590 Watts |
External Static Pressure (Standard) | 0.40 "WC |
External Static Pressure (Min. / Max.) | 0.1 / 1 "WC |
Airflow (Cooling) | 939 / 1,140 / 1,409 CFM |
Airflow (Heating) | 939 / 1,140 / 1,409 CFM |
Refrigerant Type | R-32 |
A2L Leak Detection | Integral |
Pipe Connections (Refrigerant High side) | 3/8" |
Pipe Connections (Refrigerant Low side) | 5/8" |
Pipe Connections (Condensate) | 3/4" FNPT |
Dimensions (W x H x D) | 24 1/2 x 58 11/16 x 21 in. |
Weight | 162.00 lbs. |
Duct Connections (Supply) | 14 1/4 x 21 3/4 in. |
Duct Connections (Return ID) | 24 1/2 x 21 3/4 in. |
Sound Pressure Level (Low / Med. / High) | 39 / 41 / 43 dB(A) |
Safety Certifications | UL 60335-2-40 |
Accessories
Accessory | Model Number |
---|---|
Filter box | V1FBS03-4P |
Wired controller (Advanced) | VSTAT04P-1 |
Wired controller (Touchscreen) | VSTAT02P-1 |
Thermostat adapter (for connection to standard 24VAC thermostats) | VSTAT09P-1 |
Wireless signal receiver | VCTRL10P-1 |
Wireless signal control | VSTAT01P-1 |
Wireless controller | VCTRL11P-1 |
External temperature sensor | VSTAT10P-1 |
External contact control interface module | VSTAT10P-1 |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Supplemental electric heat kit (5kW) | V1EHK05-1P |
Supplemental electric heat kit (10kW) | V1EHK06-1P |
Supplemental electric heat kit (15kW) | V1EHK07-1P |
Dimensional Drawing
The dimensional drawing illustrates the unit's physical characteristics and connection points. The unit is a vertical rectangular prism. Overall dimensions are approximately 24.5 inches wide, 21.75 inches deep, and 59.4 inches high. Connection ports are located on the sides and bottom. Specifically, there is a 3/4 inch gas pipe connection (braze) and a 3/8 inch liquid pipe connection (braze) on one side, and a drain pipe connection on the other side. The air outlet opening is located at the top of the unit, and the air inlet opening is at the bottom. The supply duct connection measures 14.25 x 21.75 inches, and the return duct connection measures 24.5 x 21.75 inches.
No. | Description |
---|---|
1 | Gas pipe connection (braze) (3/4) |
2 | Liquid pipe connection (braze) (3/8) |
3 | Drain pipe connection |
4 | Air outlet opening |
5 | Air inlet opening |