Sentrol 4300 Series Wireless Smoke Detector

Description

The Sentrol 4300 Series smoke detector requires a Sentrol 4000 RF gateway receiver with Rev J or higher software and a compatible control panel sold separately. To install the detector, the programming guide for the control panel is needed.

Depending on the model, the detector offers features such as:

Transmitted Signal Outputs: Depending on the model, the detector transmits signals to the control panel including: Alarm, Alarm restore, Tamper, Low battery, CleanMe™, Maintenance alert, Supervisory, and Low temperature supervision.

Diagram: Figure 1 - Detector Features. This diagram shows the Sentrol wireless smoke detector. Key features indicated are the sounder vent, an optional temperature sensor, the LED indicator, and the Test/Silence button. The detector is shown attached to its mounting base, with a note about the detector/base lock mechanism.

Selecting a Location

Choosing a suitable location is critical for smoke detector performance. Installation should comply with the National Fire Protection Association's (NFPA) Standard 72. Refer to Figure 2 for placement guidance.

Are More Smoke Detectors Desirable? The required number of smoke detectors may not provide adequate early warning for areas separated by doors from protected areas. Additional detectors are recommended for increased protection in areas like basements, bedrooms, dining rooms, furnace rooms, utility rooms, and hallways. Installation in kitchens, attics, or garages is generally not recommended due to potential for improper operation.

Important: Regulations for smoke detector installations vary by state. Consult your local fire department or authority having jurisdiction for specific information.

Diagram: Figure 2 - Detector Placement. This illustration shows a house floor plan with recommended smoke detector placement. Dots indicate locations for required smoke detectors, and circles with crosses indicate locations for additional detectors for new construction. Areas shown include living room, dining room, kitchen, bedrooms, TV room, and basement.

Installing the Detector

Follow these guidelines in addition to NFPA 72 for optimal performance and reduced false alarms:

Installation Steps:

  1. If using the detector/base lock, remove the two knockouts on the mounting base (See Figure 3).
  2. Slide the battery compartment cover away from the detector to unsnap and lift it off (See Figure 4).
  3. Observe correct polarity and insert the two provided lithium batteries into the compartment. Replace the battery compartment cover.
  4. Record the seven-digit ID address from the detector's backside label. This address must be programmed into the RF gateway receiver per the control panel programming guide.
  5. For 'L' model detectors, program the "Fire Address plus 1" secondary address into the panel in a separate non-fire CCM non-supervised or 24hr non-supervised auxiliary zone.
  6. Program the RF gateway receiver and the control panel according to the control panel programming guide.
  7. Remove the red plastic dust cover from the detector.
  8. Disconnect alarm notification appliances, service release devices, and extinguishing systems. Test communication between the control panel and each smoke detector before permanent mounting:
    • Press the Test/Silence button on the detector for 2 seconds. A test signal is sent to the control panel.
    • Verify the test signal reception and adequate RF signal strength at the control panel. Relocate and retest if the signal is poor or absent.
  9. Mount the base using the provided screws and anchors.
  10. Attach the detector to the mounting base: align the raised tab on the detector's lip with the slot on the base. Insert the detector and turn clockwise approximately 15 degrees until it snaps firmly into place. Important: Batteries must be installed for attachment.
  11. Test communication between the control panel and each smoke detector:
    • Press the Test/Silence button on each detector for 2 seconds.
    • Verify at the control panel that the test signal was received.
  12. Test each detector (refer to "Smoke Testing the Detector") and reconnect all alarm notification appliances, service release devices, and extinguishing systems. Important: Verify control panel alarms and auxiliary functions for a complete system test.

Diagram: Figure 3 - Base Lock Knockouts. This is a close-up view of the smoke detector mounting base, highlighting two circular knockouts. These knockouts are removed to engage the detector/base lock feature.

Diagram: Figure 4 - Detector-to-Base Alignment. This diagram illustrates how to align the Sentrol smoke detector with its mounting base. It shows a raised tab on the detector's lip fitting into a slot on the base. The battery compartment is also visible.

Testing the Detector

Smoke detectors should be tested annually using smoke or canned aerosol simulated smoke. Follow the instructions on the canned smoke or use these steps:

  1. Hold a smoldering punk or cotton wick close to the smoke entry openings.
  2. Gently direct smoke into the detector for 20 seconds or until an alarm is indicated.

Important: Extinguish the smoke source after testing. The detector LED will remain on while the transmitter sends an alarm signal. The detector sounds a temporal rhythm until the Test/Silence button is pressed. It resets automatically when smoke is no longer present.

Detector Sensitivity Testing

The 4300 Series offers a sensitivity level test mode:

  1. Press the Test/Silence button for 2 seconds. The detector performs a test, and the LED flashes one to nine times.
  2. Count the LED flashes to determine detector sensitivity status and required action using the table below:
Flashes (Approx) Obscuration Indication Action
1 N/A Unserviceable hardware fault detected. Reset unit and rerun sensitivity test. If error persists, replace unit.
2-3 N/A Detector is not sensitive enough. Clean unit. Reset unit and rerun sensitivity test. If error persists, replace unit.
4 3.1%/ft Detector is within normal sensitivity range. N/A
5 2.6%/ft N/A
6 2.1%/ft N/A N/A
7 1.6%/ft N/A N/A
8-9 N/A Detector is too sensitive. Verify smoke chamber is snapped down securely. Clean unit.

After flashes, if sensitivity is within limits and other tests pass, the detector alarms and resets after 5 seconds. If sensitivity is out of limits or a hardware fault is detected, the LED extinguishes until serviced, and a CleanMe™ or maintenance alert signal is sent.

Understanding the Test/Silence Button

The Test/Silence button performs three functions:

Understanding the LED

The LED indicates detector status:

Diagram: Figure 5 - Detector/Base Lock. This shows the Sentrol smoke detector mounted on its base. An arrow points to the detector/base lock mechanism, indicating a slot where a screwdriver can be inserted to release the detector.

Detector Attachment, Removal, and Maintenance

Attaching and Removing the Detector

To remove the detector from the mounting base, grasp it and turn counterclockwise approximately 15 degrees; it should snap off. For the detector/base lock, insert a small screwdriver into the locking tab slot on the base side and press in while turning the detector counterclockwise 15 degrees (See Figure 5).

When to Replace the Batteries

A low battery signal is sent to the control panel. The detector chirps every 30 seconds for several days until batteries are replaced. The sounder can be silenced for 24 hours by pressing the Test/Silence button.

Replacing the Batteries

Use only 3V lithium batteries specified in the Specifications section.

  1. Remove the detector from the mounting base.
  2. Slide the battery compartment cover away to unsnap and lift it off.
  3. Remove and properly dispose of old batteries.
  4. Insert two new 3V lithium batteries, observing correct polarity, and replace the cover.
  5. Reattach the detector to the mounting base.
  6. Test the system.

Cleaning the Detector

Clean the detector cover with a dry or damp cloth as needed. For interior cleaning and smoke chamber replacement:

  1. Disconnect alarm notification appliances, service release devices, and extinguishing systems.
  2. Remove the detector from its mounting base.
  3. Remove the batteries.
  4. Slide a flat-blade screwdriver into the detector cap slot and gently push down to pry the cap off (See Figure 6).
  5. Press the sides of the smoke chamber and pull it up and away from the detector to discard (See Figure 7).
  6. Blow out or use a soft-bristled brush to clean dust and dirt from the smoke chamber base.
  7. Align the new smoke chamber with the base and snap it into place.
  8. Replace the detector cap: align it, insert, and turn clockwise approximately 15 degrees until it snaps firmly into place.
  9. Insert batteries, observing polarity, and replace the battery compartment cover.
  10. Reattach the detector to its mounting base.
  11. Test detector sensitivity and reconnect all appliances and systems. Important: Verify control panel alarms and auxiliary functions for a complete system test.

Diagram: Figure 6 - Removing Detector Cap. This illustrates the process of removing the detector cap. A flat-blade screwdriver is shown being inserted into a slot on the detector cap to pry it open.

Diagram: Figure 7 - Detector Parts. This is an exploded view of the Sentrol smoke detector. Components shown include the optical base, smoke chamber, detector unit, and battery compartment. Arrows indicate where to squeeze and pull to remove the smoke chamber.

Maintaining the Detector

The 4300 Series detectors require minimal maintenance when installed and used properly. Test the detector weekly.

When maintenance is required, the detector's LED extinguishes, and a signal is sent to the control panel:

Signal Maintenance Required
CleanMe™ Smoke detector sensitivity is out of range and needs cleaning. Refer to "Cleaning the Detector".
Maintenance alert Detector failed power-up self-test. Perform a sensitivity test. If the problem persists, replace the detector.
Low battery Batteries are low. Replace the batteries.

Fire Prevention and Escape

The purpose of an early warning smoke detector is to detect fires in their early stages and sound an alarm, allowing occupants time to exit safely. No detection device can protect life in all situations; therefore, safeguards should be taken.

Avoid Fire Hazards

In Case of Fire

Be Prepared

Limited Warranty

Sentrol, a brand of SLC Technologies, Inc., warrants this smoke detector (excluding batteries) against defects in material and workmanship under normal use for 3 years from the date of manufacture. Defective products will be repaired or replaced free of charge during the warranty period. Out-of-warranty units may be repaired at the manufacturer's discretion, or a replacement unit proposal will be sent. This warranty does not cover abuse, misuse, negligence, accidents, or unauthorized modifications/repairs. The warranty extends only to the original purchaser.

Warranty Return Instructions: Obtain a Return Authorization Number by calling 1-800-648-7422 or 503-692-4052. Pack the unit securely in a well-padded carton and return, postal charges prepaid, to: Customer Service, Sentrol, 12345 SW Leveton Drive, Tualatin, OR 97062-9938. Include a note detailing the malfunction. Ensure proper packing, as Sentrol is not responsible for damage due to improper packing.

Warranty Limitations: This warranty is in lieu of all other express warranties. Implied warranties of merchantability and fitness for a particular purpose are limited to three years. Manufacturer liability is limited to the purchase price of the product and does not extend to incidental or consequential damages. Some states may not allow limitations on implied warranty duration or consequential damages.

Warning: Smoke detectors CANNOT provide warnings for fires resulting from explosions, smoking in bed or other furniture, ignition of flammable liquids, vapors and gases, or children playing with matches or lighters.

Warning! Limitations of Smoke Detectors

Wireless smoke detectors are reliable but may not work under all conditions. No fire detector provides total protection. Smoke detectors are not a substitute for life insurance.

SMOKE DETECTORS ARE A SIGNIFICANT HELP IN REDUCING LOSS, INJURY AND EVEN DEATH. HOWEVER, NO MATTER HOW GOOD A DETECTION DEVICE IS, NOTHING WORKS PERFECTLY UNDER EVERY CIRCUMSTANCE AND WE MUST WARN YOU THAT YOU CANNOT EXPECT A SMOKE DETECTOR TO ENSURE THAT YOU WILL NEVER SUFFER ANY DAMAGE OR INJURY.

FCC Compliance

This device complies with Part 15 of the FCC rules. Operation is subject to two conditions: (1) it may not cause harmful interference, and (2) it must accept any interference received, including interference that may cause undesired operation.

FCC ID: A794300

Industry Canada Compliance

This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.

IC ID: 145 5102 1202

Specifications

Voltage 3VDC Base dimensions 4.88" x 0.38" (12.3 cm x 0.95 cm)
Typical average standby current 25μA Drift compensation adjustment 0.5%/ft. max.
Typical test current 2mA Heat detector specifications (T, H Models):
Typical alarm current 70mA Rate of rise 15°F/min>105°F (8.3°C/min>40.6°C)
Battery type Duracell® 3V lithium, DL123A
Duracell® 3V lithium, MN1500
Panasonic® lithium, CR123A
Sanyo® lithium, CR123A
Eveready Energizer® lithium, E91
Fixed 135°F ± 5°F (57.2°C ± 2.8°C)
Low battery threshold 2.70V causes low battery signal RF frequency 418MHz
Sounder 85dB at 10' temporal pattern Transmitter ID Pre-programmed, 1 Million codes
Low battery beep rate 1 every 30 sec. ± 2 sec. Modulation type FM, FSK
Sensitivity 2.3% ±0.8% Signal format Manchester Encoded
Operating temperature 40°-100°F (4.4°-37.8°C) Signal types:
Operating humidity range 0-95% non-condensing Primary address alarm, restore, tamper, low battery, trouble(maint./CleanMe),1 hour supervisory
RFI Immunity 20V/m minimum; 0-1000MHz Secondary address(L models) alarm, restore
Color white Listings 4310 Series: UL 217, CSFM
4330 Series: UL 268, CSFM
Detector dimensions 5.5" x 2.3" (14 cm x 5.6 cm) Approvals FCC, IC

Product Ordering

Model Description
4310S Sentrol wireless smoke detector, two 3V lithium batteries, 85dB sounder, UL 217 Listed
4310SLT Sentrol wireless smoke detector, two 3V lithium batteries, 85dB sounder, 135 degree fixed/rate of rise heat detector, low temperature option, UL 217 Listed
4330S Sentrol wireless smoke detector, two 3V lithium batteries, 85dB sounder, base tamper, UL 268 Listed
4330SLTM Sentrol wireless smoke detector, two lithium batteries, 85dB sounder, mercury tilt tamper, 135 degree fixed/rate of rise heat detector, low temperature option, UL 268 Listed

Accessories

Corporate Headquarters

12345 SW Leveton Drive, Tualatin, OR 97062
Tel.: 503.692.4052 Fax: 503.691.7566
http://www.sentrol.com
U.S. & Canada: 800.547.2556
Technical Service: 800.648.7424
FaxBack: 800.483.2495

Sentrol reserves the right to change specifications without notice. © 2000 Sentrol

PDF preview unavailable. Download the PDF instead.

Sentrol 4300 Series Install Instructions 2000 Acrobat Distiller 4.0 for Windows

Related Documents

Preview SafeAir Carbon Monoxide Alarm Installation Instructions
Comprehensive installation, operation, and safety guide for the SafeAir Carbon Monoxide Alarm (Model 240-CO) by Sentrol. It covers safety precautions, CO poisoning symptoms, sources, and limitations of CO detection.
Preview Sentrol ZX400/ZX410 Security System Control Installation Manual
Installation guide for the Sentrol ZX400/ZX410 Security System Control, covering features, wiring, terminal descriptions, zoning, troubleshooting, specifications, and agency requirements.
Preview Sentrol ZXLCD Control Station User Manual - ZX440F Security System
Comprehensive user manual for the Sentrol ZXLCD Control Station and ZX440F Security Control. Covers system operation, programming, testing, fire detection, and safety precautions.
Preview Sentrol ZXLCD/ZXVFD Security System User Manual
User manual for Sentrol ZXLCD/ZXVFD security control stations (ZX200, ZX210, ZX400, ZX410, ZX440F). Covers operation, programming, testing, and safety for Sentrol alarm systems.
Preview Sentrol RCR-50 Range-Controlled Radar Detector Installation Manual
Installation instructions and specifications for the Sentrol RCR-50 Range-Controlled Radar Detector, featuring PIR technology for enhanced false alarm immunity. Includes setup, location guidelines, and LED status.
Preview Sentrol 2300 Series Panel Door Magnetic Contact Installation Instructions
Comprehensive installation instructions and technical specifications for the Sentrol 2300 Series Panel Door Magnetic Contact. Covers description, location selection, installation steps, switch and magnet dimensions, electrical configurations, and ordering details for sectional/panel overhead doors.
Preview Sentrol R1078 Magnetic Contacts: Installation Guide and Specifications
Installation guide and technical specifications for the Sentrol R1078 1" Diameter Steel Door Magnetic Contacts, covering installation steps, UL/ULC ratings, and gap distance details.
Preview Sentrol Advisor X DV1201/DV1221 Structural Vibration Detection System Installation Guide
Installation instructions and technical data for the Sentrol Advisor X Structural Vibration Detection System, models DV1201 and DV1221, designed for detecting break-in attempts on vaults, safes, night deposit units, and other secure physical areas.