SafeAir™ Carbon Monoxide Alarm

Installation Instructions

UL Listed

Description

The SafeAir™ carbon monoxide (CO) alarm monitors CO gas in residential dwellings, providing early warning of dangerous levels. It performs a self-test every 2 minutes. The SafeAir™ is a 4-wire device designed for use with a UL Listed fire or fire/burglary alarm control panel (Class 2 output).

Important: Use only with a UL Listed control panel capable of differentiating alarm signals (fire, burglary, CO) and providing distinct identification for each.

Selecting a Location for the Alarm

Proper location is critical for CO alarm operation. Install an alarm in every bedroom and on each level of a dwelling. At a minimum, place one alarm outside sleeping areas. Refer to Figure 1 for typical locations.

Installation Guidelines:

Figure 1 Description: A diagram illustrating a house with several locations marked for CO alarm installation, typically in bedrooms, hallways, and near living areas.

Installing the Alarm

All wiring must conform to the National Electric Code (NEC) and local codes. Use 16 to 22 AWG wire.

Important: DO NOT connect the CO alarm on an initiating circuit with fire and/or security devices.

Installation Steps:

  1. Run the security system wiring to the alarm location.
  2. Remove the alarm cover by lifting it off.
  3. Important: J1 is factory set for manufacturing purposes. DO NOT change the setting.

  4. Use the base as a template to mark the two top screw hole locations on the mounting surface.
  5. Install two screws on the marks. Use wall anchors if necessary.
  6. Align the base with the screws. Pull wiring through the square hole and slide the base down the screws to the wall. For surface wiring, pull wires through the wiring channel at the top of the base.
  7. Strip 3/8 inch of insulation from each wire and insert under the appropriate screw terminal. Refer to Figure 2 for wiring details.
  8. Install two screws in the bottom two mounting holes. Tighten all four screws to secure the base.
  9. Replace the alarm cover.
  10. Apply power. The LED should flash green for approximately 15 seconds, then light steadily.
  11. Test the installation as described in "Testing the Alarm".

Figure 2 Description: A wiring diagram showing connections from a UL Listed Class 2 control panel to the alarm unit. It details terminals for power (+12V, GND), relay contacts (NO, COM, NC), and internal components like the sensor, LED, and sounder, connected via terminals TB1, TB2, SW1, and J1.

Testing the Alarm

Test the alarm regularly to ensure proper function.

Test Procedures:

  1. CO Alarm Operation Test: Press and release the TEST/HUSH button until the LED turns red. The alarm should beep 4 times, pause for 5 seconds, beep 4 times, and then the LED should turn green, indicating proper installation and function.
  2. Relay Contacts and Panel Test: Press and release the TEST/HUSH button until the LED flashes amber. The LED should continue to flash amber, and the relay should trip. After 9 seconds, the relay resets, and the LED returns to green.
  3. If the alarm fails a test, wait a few minutes and repeat.
  4. If the alarm fails again, replace the unit.

Servicing the Alarm

For servicing, return the alarm to:

Sentrol
12345 SW Leveton Drive
Tualatin, OR 97062

Include a note describing the nature of the malfunction. Use proper packaging to prevent shipping damage.

Maintaining the Alarm

The SafeAir™ CO alarm requires minimal maintenance when installed and used properly. Test the alarm regularly as described above.

Clean the alarm as needed to remove dust and dirt using a clean, dry, or damp (water) cloth.

Important: DO NOT paint the alarm or expose it to cleaning solutions.

Specifications

SpecificationValue
Input voltage12VDC (supplied by a UL Listed control panel)
Current consumption (Normal)8mA
Current consumption (Alarm)60mA max
Relay contact50mA @ 12VDC
Electrical configurationNO, NC
CO alarm level70 ppm / 60-189 minutes
Operating temperature40-100°F (4.4-37.8°C)
Relative humidity15-90% non-condensing
Dimensions (Width)2.7" (6.9 cm)
Dimensions (Length)6" (15.2 cm)
Dimensions (Depth)1.4" (3.6 cm)
Weight4oz (114 g)
ColorWhite
ListingsUL 2075

Limited Warranty

Sentrol warrants the alarm to be free from defects in materials and workmanship under normal intended use and service for a period of 5 years from the date of purchase.

Product Ordering

Model NumberDescription
240-COSafeAir™ carbon monoxide (CO) alarm, Form C, 12VDC

Understanding and Preventing CO Poisoning

Recognizing CO Poisoning

Symptoms related to CO poisoning should be discussed with household members:

Victims may become disoriented and unable to save themselves. Young children and pets may be affected first.

Sources of CO

CO results from the incomplete combustion of fuels (wood, gas, oil, charcoal, gasoline, kerosene). Dangerous CO levels can be produced by:

CO Precautions

No detector can protect in all situations. Take safeguards:

When CO is Detected

The SafeAir™ alarms if harmful CO levels are present: LED turns red, sounder emits four rapid beeps every 5 seconds, and the relay triggers the control panel.

Press the TEST/HUSH button to silence the sounder. The alarm will resume if CO is still present.

In the Event of a CO Alarm

[WARNING] Alarm actuation indicates the presence of CO, which can be fatal.

If alarm signal sounds:

  1. Operate the TEST/HUSH button.
  2. Call your fire department or 911.
  3. Immediately move to fresh air (outdoors or by an open door/window). Conduct a head count. Do not reenter until emergency services arrive, the premises are aired out, and the alarm is functioning normally.

If the alarm reactivates within 24 hours, repeat steps 1-3 and call a qualified technician to examine or turn off fuel-burning appliances. Turn off vehicle engines if idling in an attached garage.

Important: Ensure adequate ventilation when using household cleaning solutions to prevent false alarms.

Important: The alarm automatically resets when CO dissipates.

Understanding the LED and Sounder

The SafeAir™ uses a multi-colored LED and sounder to indicate alarm status. The alarm resets automatically when CO is no longer detected.

LEDSounderStatusDescription
Green (Off)Safe airThe alarm has power and is functioning properly.
RedSounds 4 rapid beeps every 5 seconds.AlarmDangerous level of CO is detected. The relay triggers if connected. Evacuate the premises. Press the TEST/HUSH button to silence the sounder.
Flashing amber (every 30-60 sec.)Chirps following each LED flashTroubleThere is a problem with the alarm. Investigate and replace if necessary.

General Limitations of CO Alarms

CO alarms require power. Verify the green LED is always on. This unit is powered by a UL Listed fire/burglary alarm control panel; it may not operate during a power failure or if the control panel is disabled.

[WARNING] This device may not alarm at low CO levels. OSHA established that continuous exposure to 50 ppm over 8 hours should not be exceeded. This alarm has not been investigated for CO levels below 70 ppm.

Individuals with special medical conditions should consider devices with under 30 ppm alarming capabilities.

[CAUTION] This alarm indicates CO at the sensor. CO may be present elsewhere. Closed doors can delay or prevent alarm activation. Install a sensor in each bedroom and in hallways.

CO alarms are not smoke alarms. They detect CO from combustion sources, not smoke, fire, or other gases.

CO alarms may not be heard by sound sleepers or individuals under the influence of drugs or alcohol, especially if located outside a bedroom. Normal noise or closed doors can block sound. This unit is not designed for the hearing impaired.

CO alarms are not a substitute for life insurance. While they warn of increasing CO levels, they do not guarantee protection against CO poisoning. They are part of a comprehensive safety program. Homeowners and renters must ensure their own safety.

Replacement Information

This product is designed to work reliably for 5 years after installation. Contact your local distributor for replacement after 5 years.

Installation Date: _________________________

Distributor: _________________________

Contact Information

Sentrol
12345 SW Leveton Dr., Tualatin, OR 97062
Tel: 503.692.4052 | Fax: 503.691.7566
http://www.sentrol.com
U.S. & Canada: 800.547.2556
Technical Service: 800.648.7424
FaxBack: 1.800.483.2495

Sentrol reserves the right to change specifications without notice. ©1999 Sentrol E-3536-1198 15876 Rev A

PDF preview unavailable. Download the PDF instead.

240-CO COSafeAir Carbon Monoxide Installation Guide Acrobat Distiller 3.01 for Power Macintosh

Related Documents

Preview Sentrol ZX400/ZX410 Security System Control Installation Manual
Installation guide for the Sentrol ZX400/ZX410 Security System Control, covering features, wiring, terminal descriptions, zoning, troubleshooting, specifications, and agency requirements.
Preview Sentrol 4300 Series Wireless Smoke Detector Installation and Maintenance Guide
This document provides comprehensive instructions for the Sentrol 4300 Series wireless smoke detector, covering installation, testing procedures, maintenance, fire safety, troubleshooting, warranty information, specifications, and product ordering details.
Preview Sentrol 4010 & 4011 Pendant Transmitter User Manual | Wireless Security
Official user manual for Sentrol 4010 Single Button and 4011 Dual Button Pendant Transmitters. Learn about installation, programming, testing, and specifications for this wireless security device.
Preview Sentrol ZXICON Control Station: User Manual for ZX300/ZX310 Security Systems
Comprehensive user manual for the Sentrol ZXICON Control Station, detailing operation, features, testing, and troubleshooting for ZX300 and ZX310 security systems.
Preview Sentrol 1078CT Series Steel Door Magnetic Contacts: Specifications & Installation
Detailed specifications and installation instructions for Sentrol 1078CT Series 3/4" diameter steel door magnetic contacts, including gap distances, electrical configurations, and UL/ULC ratings.
Preview Sentrol Security System ZXLCD/ZXVFD Control Station User Manual
Comprehensive guide on operating and understanding Sentrol ZX200, ZX210, ZX400, ZX410, and ZX440F security systems with ZXLCD/ZXVFD control stations. Covers arming, disarming, features, testing, and troubleshooting.
Preview Sentrol Security System ZXLCD/ZXVFD User Manual: Operation Guide
This user manual provides comprehensive instructions for operating the Sentrol ZXLCD/ZXVFD, ZX200, ZX210, ZX400, ZX410, and ZX440F security control stations. Learn how to arm, disarm, manage alarms, and utilize advanced features for your home or business security.
Preview Sentrol ZXLCD Control Station User Manual - ZX440F Security System
Comprehensive user manual for the Sentrol ZXLCD Control Station and ZX440F Security Control. Covers system operation, programming, testing, fire detection, and safety precautions.