Sentrol Advisor X Structural Vibration Detection System

DV1200 Series, Models DV1201, DV1221

Installation Instructions

1.0 Introduction

The Advisor X Structural Vibration Detection System is a seismic detection system designed to detect attempts to break into vaults, safes, night deposit safes, automatic cash dispenser units, and other reinforced physical areas such as data storage and filing cabinets.

To achieve high accuracy, the system analyzes three major parameters: signal strength, signal frequencies, and signal duration before triggering an alarm. These parameters differentiate real break-in attempts from nuisance signals. In general, the signal characteristics of a true break-in attempt include:

2.0 Planning Installation

2.1 What to Avoid

Although the Advisor X System is designed for high immunity against nuisance alarms, some precautions should be considered during installation planning. Do not install detectors close to electric motors, transformers, fans, air conditioners, or other electrical devices that create mechanical vibrations in the protected structure. Avoid mechanical contact between electrical devices and the protected structure's surface, or dampen vibrations using rubber-like insulating materials.

Water Piping

The flow of water through piping in mechanical contact with the protected structure emits a strong signal and may cause nuisance alarms.

Ultrasonic Detectors

Ultrasonic detectors may emit a signal within the frequency range of Advisor X detectors. Avoid placing them closer than six feet to the protected surface.

Bells

Bells may generate overtones in the Advisor X detector's frequency range. Place tape on the bell to suppress overtones, drill a hole in the gong, or relocate the bell.

2.2 Planning Vault Protection

Generally, it is advisable to place one detector on each wall, floor, and ceiling inside the vault, and one detector on or inside the vault door. See the following section on detection range and sensitivity test. Detectors can be mounted with the supplied Mounting Plate, the DV1212 Steel Surface Mounting Plate, or the DV1203 Recessed Mounting Plate. Mount detectors at a height of at least six feet (1.8m) to avoid interference from document cabinets and deposit boxes.

FIGURE 1 - DETECTOR PLACEMENT: Diagram showing a typical vault interior with suggested detector placement.

Special consideration is required for installations seeking a UL certificate (UL 681), including power supply, system test needs, and protection of interconnection cable.

Since the vault door is isolated by its hinges, place one detector inside the vault door. Newer vault doors often have cable channels in the hinges for easy sensor connection.

An optional method for protecting the vault doorway is to mount a detector on the outside of the door. This provides early protection against torch-cutting and thermic bar attack, as the vault door acts as a membrane detecting the signal before surface attack begins. The detector can be mounted directly or with a DV1202 or DV1203 mounting plate (see Section 3.0 for mounting instructions).

The DV1219 Armed Cable Kit and DV1228 Metal Junction Box allow cabling from the door to the frame via the hinge side with armored cable. Exercise caution when drilling into the vault door, as printed circuit board drill protection may exist behind the outer steel plate (consult the vault door manufacturer).

2.3 The Vault Sensitivity Test for Irregularities

If the vault or safe surface shows cracks, gaps, or other irregularities, perform a test to determine if the protection range of each sensor is affected. Additional sensors may be needed for optimal coverage. This test is not necessary for sensors mounted on steel surfaces. For concrete, block, and brick construction, use an electric drill and a 1/4" (6mm) carbide-tipped bit for the following test:

  1. Locate any irregularity in the construction; mortar between bricks and blocks is considered an irregularity.
  2. Install the sensor on one side of the suspected irregularity (see mounting instructions).
  3. Wire the sensor to power and the alarm circuit.
  4. Set the sensor sensitivity to MAX.
  5. Drill into the wall at a point equal to the protection radius (R) based on the construction type (see table below). Check for an alarm.
  6. If no alarm occurs, assume the irregularity inhibits the detector's range. Redrill closer to the sensor until an alarm occurs and identify the proper protection radius for that site.
  7. Account for all irregularities when spacing sensors; additional sensors may be required. Note: The separation between the vault door and frame requires an additional detector on the door to counter potential weakness at this point.
TABLE 1 - ESTIMATING DETECTOR RANGE ON A VAULT
Material Sensitivity Setting Protective Radius (Methods of Attack)
Thermic Lance Diamond Disk Drilling
Concrete K-350 1 13ft.,2in. (4m) 45ft.,11in. (14m) 45ft.,11in. (14m)
Steel 26ft.,3in. (8m) 45ft.,11in. (14m) 45ft.,11in. (14m)
Brick G Max 9ft.,10in. (3m) 26ft.,3in. (8m) 26ft.,3in. (8m)
Concrete K-350 2 9ft.,10in. (3m) 29ft.,7in. (9m) 29ft.,7in. (9m)
Steel 13ft.,2in. (4m) 29ft.,7in. (9m) 29ft.,7in. (9m)
Brick G Ref 3ft.,4in. (1m) 19ft.,8in. (6m) 19ft.,8in. (6m)
Concrete K-350 3 6ft.,7in. (2m) 19ft.,8in. (6m) 19ft.,8in. (6m)
Steel 6ft.,7in. (2m) 19ft.,8in. (6m) 19ft.,8in. (6m)
Brick G Min - 13ft.,2in. (4m) 13ft.,2in. (4m)
Concrete K-350 4 3ft.,4in. (1m) 16ft.,5in. (5m) 16ft.,5in. (5m)
Steel 3ft.,4in. (1m) 16ft.,5in. (5m) 16ft.,5in. (5m)
Brick 9ft.,10in. (3m) 9ft.,10in. (3m) 9ft.,10in. (3m)
Concrete K-350 5 13ft.,2in. (4m) 13ft.,2in. (4m) 13ft.,2in. (4m)
Steel 13ft.,2in. (4m) 13ft.,2in. (4m) 13ft.,2in. (4m)
Brick 6ft.,7in. (2m) 6ft.,7in. (2m) 6ft.,7in. (2m)
TABLE 1: Detector range estimation for various vault materials and attack methods.

2.4 Planning Guidelines

Dos

Don'ts

2.5 Requirements When Using One Sensor (DV1201 or DV1221)

All-steel safes with 1/4" walls*

Safes must have a minimum of 1/4" steel on the body and 1/2" on the door. For this construction, the overall size must not exceed 12 cubic feet or have:

The sensor can be mounted in or on the safe, near the door hinges or on the door itself. Sensitivity settings (Tables 2 and 3) must be adjusted for adequate detection at the lowest setting. Use of the Mounting Plate is optional (see Section 3.0).

All-steel safes with 1" walls*

Safes must have a minimum of 1" steel on the body and door. The overall size must not exceed 52 cubic feet or have:

The DV1201 and DV1221 sensors can be mounted on the safe door or body near the hinges, or inside the safe. Sensitivity settings must be adjusted for adequate detection at the lowest possible setting. Use of the Mounting Plate is optional.

* Control panel must be within visual or audible range for testing.

A concrete-clad safe

The same dimensional rules apply as for an all-steel safe with 1" walls. However, if the safe construction revealed cracks, seams, or other irregularities, always assume two sensors are required, regardless of size.

FIGURE 2 - STRUCTURAL VIBRATION DETECTOR: Diagram of the detector unit, showing external features and internal components.

Removing the cover screws and cover from the base plate [item 2] provides access to the connection terminals [item 10] and the sensitivity adjustment control [item 9]. Inside the unit are located: main mounting holes [items 4, 5], test transmitter areas [items 8, 7], strain relief [item 6], and tamper switch [item 11].

3.0 Installation Instructions

3.1 General Instructions for DV1201/DV1221 Structural Vibration Detector

The DV1201/DV1221 Structural Vibration Detectors have cast aluminum housings measuring 3.1in. x 3.9in. x 1.2in. (8 x 10 x 3cm) and weigh 9 ounces (250gr) each.

The following tools are recommended for mounting the DV1201 and DV1221 on any surface:

FIGURE 3 - MOUNTING PLATE: Diagram of the mounting plate with various hole designations.

3.2 Instructions for Mounting Plate

The mounting plate can be used for mounting the DV1201 and DV1221 on steel and concrete surfaces (see Sections 3.4 and 3.5). It also provides an adaptation hole layout for replacing Securitas SSD70, Cerberus GM31,35 GM550, or Arrowhead 3810 detectors (see figure 3).

3.3 Direct Mounting the DV1201/DV1221 on a Steel Surface

In some cases, it is advisable to mount the detector directly onto a steel surface using the provided bolts and installer-made threaded holes.

Mounting instructions for direct mounting on steel:

  1. Define the exact location of the DV1201/DV1221 when mounted. Hold the mounting plate in position on the steel surface.
  2. Using the felt pen and the mounting plate as a template, mark the location of the three threaded holes (see holes marked "V" in figure 9).
  3. Drill three holes, using a #29 drill, at least 7/16" deep (see drawing) in the marked positions.
  4. After drilling, tap the holes with an 8-32 tap, using cutting oil. Use a 7/16" diam. drill to smooth the surface around the holes and remove burrs.
  5. Mount the detector to the steel surface using the three 8-32 screws provided (see figure 10).
  6. If a DV1215 Test Transmitter is used, it can be mounted in the lower right corner of the detector.
FIGURE 4 - MOUNTING DETECTOR ON A STEEL SURFACE: Diagram illustrating the process of mounting the detector directly onto a steel surface.

3.4 Indirect Mounting of DV1201/DV1221 on a Steel Surface

Indirect mounting may be advisable in some cases:

3.5 Mounting the DV1201/DV1221 on Concrete

Surface mounting requires the mounting plate. Follow the instructions below:

  1. Define the exact location of the DV1201/DV1221 and hold the mounting plate to the wall.
  2. Using the felt pen, mark the location for the expansion plug hole on the wall (see drawing).
  3. Drill a 1/2" diam. hole at the marked spot. Ensure the expansion plug is set flush with or below the wall surface.
  4. Insert the expansion plug into the drilled hole, ensuring its top end does not protrude. Align the mounting plate over the hole and secure it with a bolt. If no test transmitter is used, proceed to step 10.
  5. Before tightening the bolt, position the mounting plate to align the DV1215 drill pattern hole (Section 3.2) for cable routing (usually at the bottom). Check for proper horizontal/vertical alignment of the DV1201/DV1221.
  6. Mark the DV1215 mounting hole with the felt pen. Position the mounting plate so the marked spot is over the DV1215 mounting hole (see Section 3.2 drawing).
  7. Drill a 1/2" diam. hole at the marked spot. Ensure the expansion plug is flush with or below the wall surface.
  8. Insert the DV1215 expansion plug into the hole, ensuring its top end does not protrude. Place the DV1215 test transmitter over the hole and secure with the provided bolt.
  9. Ensure the DV1215 does not touch the mounting plate, then tighten the bolt. To seat the plug properly, tap the bolt's head a few times with a hammer (avoiding the DV1215) and tighten the bolt again. NOTE: At the first service visit, retighten all bolts to compensate for material expansion.
  10. After mounting the plate on concrete, install the DV1201/DV1221 detector as described in 3.3.
FIGURE 5 - MOUNTING THE DETECTOR ON CONCRETE: Diagram illustrating the process of mounting the detector on a concrete surface using a mounting plate and expansion plugs.

2.4 Planning the Protection of an Automatic Cash Dispensing Unit (ATM) and a Night Depository Box

For both units, use the DV1221 to filter out noise generated by normal operation. The DV1221 can be mounted directly on the structure's surface.

Diagram showing a DV1221 detector.
TABLE 2 - RECOMMENDED SENSITIVITY SETTINGS FOR A SAFE WITH ONE DV1201 OR DV1221 DETECTOR
Thickness of Steel Maximum Cubic Ft. Method of Attack
Torch Drilling Mechanical
Over 1/4" but under 1" 12 Cu ft: DV1201 3 3 3
DV1221 2 2 2
Over 1" 52 Cu ft: DV1201 3 3 3
DV1221 1 1 1
Note: These settings are only guidelines. All final settings are to be made following the steps in Section 5.0.
TABLE 3 - RECOMMENDED SENSITIVITY SETTINGS ON A CASH DISPENSING UNIT (ATM) AND NIGHT DEPOSITORY WITH ONE DV1221 DETECTOR
Thickness of Steel Maximum Cubic Ft. Method of Attack
Torch Drilling Mechanical
Over 1/4" but under 1" 12 Cu ft: DV1221 2 2 2
Over 1" 52 Cu ft: DV1221 1 1 1
Note: These settings are only guidelines. All final settings are to be made following the steps in Section 5.0.

4.0 Cable Requirements

TABLE 4 - ADVISOR X SYSTEM CABLE REQUIREMENTS
Feature Stand-alone Number of Conductors (Multi Sensor System with Individ. Indication DV1208)
Power 2 2
Alarm form C 2-4 2-4
Tamper 2 2
Test in 1 1
Test out (LED) - 1 separate home run
TABLE 4: Advisor X System cable requirements for different configurations.

4.1 WS300 Cable Preparation Instructions

The Aritech WS300 High Security Cable is specially designed to provide electrically protected cabling in a UL Complete Mercantile Safe System. The cable consists of double circuit shields enclosing all conductors. When wired per the Wiring Diagrams in Sections 4.0 and 7.0, the WS300 Cable complies with the description of electrically protected cable in UL 681.

The two aluminum shields wrapping the eight-conductor cable are isolated from each other. Each shield is electrically conductive to a drain wire (stranded cable, no insulation). When preparing the cable for connection to the DV1201/DV1221 detector and at the control panel, the shields and corresponding drain wires must be kept isolated. A special cable preparation procedure is described below.

  1. Carefully remove approximately six inches of the PVC jacket. The outside protective shield detaches with the PVC jacket, leaving the drain wire loose.
  2. To isolate this drain wire from the inside protective shield, slide a five-inch piece of wire insulator over the exposed drain wire. Wrap a layer of electrical tape around the insulated drain wire and remaining wires at the cut PVC jacket point.
  3. Remove the mylar wrap isolating the shields and the second (inside) shield. Cut off both shields at the edge of the electrical tape.
  4. Isolate this drain wire with wire insulator and wrap with a second layer of electrical tape.
  5. Make connection to the DV1201/DV1221 sensor as indicated in the Wiring Diagram in Sections 7.0.
FIGURE 6 - INITIAL CABLE PREPARATION: Diagram showing the first steps of preparing the 8-conductor cable, including applying electrical tape.
FIGURE 7 - FINAL CABLE PREPARATION: Diagram showing the final steps of preparing the 8-conductor cable, including applying a second layer of electrical tape.

5.0 Testing

  1. Prior to applying power, recheck all connections and ensure all mounting screws are tight.
  2. Apply power. Connect an ohmmeter to Terminals 5 and 6 of the DV1201 or DV1221. Check for a closed alarm loop.
  3. Connect a DC voltmeter (internal resistance 20 kΩ or more) to Terminal 2 (negative) and the test point TP (positive). Set the voltmeter to the 3V range. Set the sensitivity selector to the maximum sensitivity position (1). Ensure all possible causes for vibrations in the protected area are present and operating. Check the output voltage and adjust accordingly. Reduce the detector's sensitivity until the voltage reading is acceptable, or remove the source of ambient noise.
TABLE 5 - DETECTOR OUTPUT VOLTAGE LEVELS
For DV1201 For DV1221 Status
0.7V 0V OK
1.4V 2V reduce range/remove source
2.5V 3.7V alarm
TABLE 5: Detector output voltage levels for DV1201 and DV1221, indicating OK, reduce range/remove source, or alarm states.
FIGURE 8 - TESTING THE DETECTORS: Diagram showing a multimeter connected to the detector for testing output voltage levels.
  1. The voltage levels should meet the "OK" ranges stated above. If not, locate and remove the source(s) of ambient noise. Only reduce sensitivity settings below recommended levels (Tables 1 and 3) after exhausting all steps to eliminate noise sources. If settings are reduced, verify proper detection is maintained through surface testing.
  2. Perform the following tests:
    • Scratch the surface around the detector with a screwdriver. The detector should trigger an alarm within approximately 30 seconds for the DV1201 and 45 seconds for the DV1221 (circuit opens between Terminals 5 and 6). This simulates attack with a drill, diamond disk, or thermal tool.
    • Knock firmly with a hammer on the protected surface around the detector at two-second intervals. After five blows, the DV1201 alarms. To protect the surface, place a small aluminum plate between the hammer and surface. This test simulates hammer and chisel attack and is valid only for the DV1201.
    • Give one powerful blow near the detector with a hammer. Both DV1201 and DV1221 alarm immediately. This simulates an attack with explosives.
  3. Close the detector cover(s) and check for a closed-loop condition of the tamper loop.
  4. Connect the alarm and tamper loop to the alarm panel and perform a functional test of both alarm and tamper signals per panel specifications.
  5. Confirm proper activation at the system control to ensure correct loop wiring.

6.0 The Advisor X Test System

6.1 General Description

The structural vibration detectors in the Advisor X System can be checked with the Remote Test System. A DV1215 Test Transmitter is mounted inside the detector on the supervised surface. Upon application of 12VDC power, the transmitter's transducer converts supplied oscillations into signals transmitted into the protected surface and picked up by the detector. The detector goes into alarm, and its LED output (Terminal 3) goes out of conductive mode. In the indicator unit, a corresponding LED is activated and remains on as long as the sensor is in alarm.

7.0 Wiring Diagrams

7.1 Wiring the DV1201/DV1221 into Most Security Systems

Diagram showing general wiring for the DV1201/DV1221 into security systems, including terminals for power, LED, alarm, and tamper.

7.2 Connecting the DV1201 to a Four-wire Circuit Type Control in a UL Complete Mercantile Safe System

Diagram illustrating the four-wire connection of the DV1201 to a UL Complete Mercantile Safe System control.

7.3 Connecting the DV1201 to a Two-wire Balanced Loop Type Control in a UL Complete Mercantile Safe System

Diagram illustrating the two-wire balanced loop connection of the DV1201 to a UL Complete Mercantile Safe System control.

8.0 Technical Data

8.1 Technical Data for the DV1201/DV1221

Operating data:

Environmental data:

Physical Data:

8.2 Technical Data for DV1215

Ordering Information

ORDERING INFORMATION
Model Number Description
DV1201 Structural Vibration Detector for Vaults and Safes
DV1221 Structural Vibrator Detector for ATM and Night Deposit Safe
DV1160 Test Transmitter/Generator
DV1208 Eight-Point Remote Annunciator
DV1209 Summed Remote Annunciator
DV1215 Self-Contained Test Transmitter
DV1218 Plastic Insert for Armored Cable
DV1219 Armored Cable Kit (6')
DV1220 Recessed Floor Mounting Box
DV1228 Tampered Junction Box
WS300 High Security Cable
Table listing available models and their descriptions.

Corporate Headquarters

Sentrol, Inc

12345 SW Leveton Dr.
Tualatin, OR 97062

Tel.: 503.692.4052 Fax: 503.691.7566

U.S. & Canada: 800.547.2556

Technical Service: 800.648.7424

FaxBack: 800.483.2495

Sentrol reserves the right to change specifications without notice. ©1997 Sentrol, Inc.

PDF preview unavailable. Download the PDF instead.

PD348255 Acrobat Distiller 4.0 for Macintosh; modified using iText 5.2.0 ©2000-2012 1T3XT BVBA

Related Documents

Preview Sentrol Advisor X DV1200 Series Structural Vibration Detection System Installation Guide
Comprehensive installation instructions for the Sentrol Advisor X DV1200 Series Structural Vibration Detection System (Models DV1201, DV1221). Learn about planning, mounting, wiring, and testing for enhanced security in vaults, safes, ATMs, and more.
Preview Sentrol ZXLCD Control Station User Manual - ZX440F Security System
Comprehensive user manual for the Sentrol ZXLCD Control Station and ZX440F Security Control. Covers system operation, programming, testing, fire detection, and safety precautions.
Preview Sentrol ZXLCD/ZXVFD Security System User Manual
User manual for Sentrol ZXLCD/ZXVFD security control stations (ZX200, ZX210, ZX400, ZX410, ZX440F). Covers operation, programming, testing, and safety for Sentrol alarm systems.
Preview Sentrol Security System ZXLCD/ZXVFD Control Station User Manual
Comprehensive guide on operating and understanding Sentrol ZX200, ZX210, ZX400, ZX410, and ZX440F security systems with ZXLCD/ZXVFD control stations. Covers arming, disarming, features, testing, and troubleshooting.
Preview Sentrol RCR-50 Range-Controlled Radar Detector Installation Manual
Installation instructions and specifications for the Sentrol RCR-50 Range-Controlled Radar Detector, featuring PIR technology for enhanced false alarm immunity. Includes setup, location guidelines, and LED status.
Preview Sentrol RCR Range-Controlled Radar Detector Installation and User Manual
Comprehensive installation and user guide for the Sentrol RCR detector, featuring range-controlled radar (RCR) and passive infrared (PIR) technology for enhanced false alarm immunity. Includes setup, maintenance, specifications, and FCC compliance information.
Preview Sentrol ZX400/ZX410 Security System Control Installation Manual
Installation guide for the Sentrol ZX400/ZX410 Security System Control, covering features, wiring, terminal descriptions, zoning, troubleshooting, specifications, and agency requirements.
Preview Sentrol ZXICON Control Station: User Manual for ZX300/ZX310 Security Systems
Comprehensive user manual for the Sentrol ZXICON Control Station, detailing operation, features, testing, and troubleshooting for ZX300 and ZX310 security systems.