Sentrol ZX400/ZX410 Security System Control Installation

New Features

  • 12 Zones with Sentrol's unique "2 in 1" Zoning™
  • Plus one 2-wire fire zone
  • Expandable to 28 zones, plus two 2-wire fire zones
  • Integrated Sentrol Series 4000 Wireless
  • Two truly independent partitions
  • Up to 50 user codes with 15 levels of authority
  • 75 event log
  • Four interchangeable Control Stations to choose from
  • Customized scheduling with special supervisory report
  • Ideal for residential, commercial, and industrial applications
  • Control Station programming in less than 2 minutes with factory defaults

The Sentrol ZX400/ZX410 Security Control features ease of installation and programming. It can be programmed using any of four Control Stations (LCD, LED, SSD, or VFD). Remote programming is possible via PC and modem using Sentrol's RPM2PRO software and PRO400 panel support module. Control Stations offer features like cross-zoning, delay-before-dialing, and an audible mute function.

The control is pre-programmed with twelve burglar zones (one delay, two interior, nine instant) and one 2-wire smoke detector zone. The twelve burglar zones are configured in a 'paralleled' condition using Sentrol's "2 in 1" Zoning™. A zone expander can add another 2-wire smoke detector zone and up to 16 additional zones with "2 in 1" Zoning™.

Sentrol Series 4000 RF Gateway receivers and sensors enable overcoming installation obstacles. Wireless sensors are engineered for long-term stability. The Series 4000 Wireless System allows expansion of the ZX400/ZX410 to include up to 16 wireless zones.

The control's on-board RAM retains data without power. A "Watchdog" timer monitors the microprocessor for operational integrity. The ZX400/ZX410 Control Board includes one low current programmable output (PGO1) and one high current bell output (BELL) for alarms. Two ZXODMs (Output Driver Modules) can add 20 more programmable low current outputs.

The ZX400 Security Control is available as the ZX410 pre-configured package, which includes the ZX400 Control Board in an EX1414 enclosure. The ZX410 is for Commercial and Industrial UL Listed applications. For UL Listed Commercial Fire applications, the ZX440F is available, featuring the ZX400 Control Board in a red EX1414 enclosure with a ZXCFM (Commercial Fire Module), CR860 dual battery harness, and cabling.

ZX400/ZX410 Wiring Diagrams

This section details the wiring configurations for the ZX400/ZX410 Security Control.

Figure 1: Suggested UL Household Burglar Alarm and/or Fire (ff) Alarm Hookup

This diagram illustrates the primary wiring connections for the control panel. It shows connections for the AC transformer (Basler BE 116235, 16.5VAC/35VA, U.L. Class II), a 12V sealed lead-acid battery (Yuasa B-1270), control stations, a signaling device (Ademco AB12M), a smoke detector (Sentrol 2-wire or 4-wire models), a motion detector, a commercial burglar audible, and telephone line supervision (RJ31/33/45 cord). It emphasizes power-limited connections and the use of End-of-Line (EOL) resistors (CR853, CR854) for zone supervision. The diagram also indicates connections for zone expanders and printer interfaces.

Figure 2: Programmable Output And Telco Supervision Wiring Diagram

This diagram shows the wiring for the MPI-206 module, which can be used for a programmable output (PG01) or Telco Supervision. It details connections to terminals 10 (for PG01) and 20 (for PG01), and terminals 7 and 4 (for Telco Supervision) on the main control board. The MPI-206 module itself has terminals for +12V, NEG, TG+, TG-, COM, and NC.

ZX400/ZX410 Terminal Descriptions

The following table describes the function of each terminal on the ZX400/ZX410 control panel:

TERMINALFUNCTIONDESCRIPTION
1, 2AC InputConnects to a UL Class II transformer (18 gauge minimum 2-conductor wire, max 50 ft). Uses a 16.5 VAC 35 VA or 16.5 VAC 20 VA transformer. Must be connected to a 120 VAC, 24-hour outlet not controlled by a switch.
3Switched Negative(-) Current limited 100 mA terminal. Used for 4-wire smoke detectors, glass break detectors, and devices requiring resettable power.
4Auxiliary Power(+)12 VDC 500 mA continuous power, overcurrent protected at 1.35 amps (PTC4). Powers motion detectors, 4-wire smoke detectors, glass break detectors, and accessories. (Use terminals 4 and 10 for total current drain calculation).
5Supervised Bell Output (power-limited)(+)12 VDC. Combined alarm current should not exceed 1.5 amps, overcurrent protected at 1.85 amps (PTC2). Requires a 1500 Ohm EOL resistor (CR854) between terminals 5 and 7.
6Two Wire Smoke (Zone 30) (power-limited)(+)12VDC for two-wire smoke detectors. Requires a 1500 Ohm EOL resistor (CR854) between terminals 6 and 7, regardless of detector use. Maximum series resistance is 60 Ohms.
7, 11Common Negative (power-limited)(-)12 VDC. Negative connection for Control Stations, zone expanders, printer interfaces, RF Gateways, ODMs, 2-wire smoke detectors, and motion detectors.
8Local Data Bus In (A)GREEN WIRE. Connects to Control Stations, zone expander, printer interface, RF Gateway, and ODMs. Use 22 gauge wire up to 1000 ft, or 18 gauge up to 2000 ft.
9Local Data Bus Out (B)WHITE WIRE. Connects to Control Stations, zone expander, printer interface, RF Gateway, and ODMs. Use 22 gauge wire up to 1000 ft, or 18 gauge up to 2000 ft.
10Control Station Power (power-limited)RED WIRE. (+)12 VDC 500 mA continuous power for control stations, zone expanders, printer interfaces, RF Gateways, and ODMs. Overcurrent protected at 1.35 amps (PTC4). (Use terminals 4 and 10 for total current drain calculation).
12Zone 1/7 Loop (+)Each loop requires a 1500 Ohm end-of-line resistor (P/N CR854) for the primary zone, and an 825 Ohm end-of-line resistor (P/N CR853) for the secondary zone. A common negative is shared among all zones. EOL resistors may be eliminated on Burglar zones via programming. See Figure 1 for "2 in 1" Zoning™ wiring examples.
13Zone 2/8 Loop (+)
14Common Negative
15Zone 3/9 Loop (+)
16Zone 4/10 Loop (+)
17Common Negative
18Zone 5/11 Loop (+)
19Zone 6/12 Loop (+)
20Common Negative
PGO1Programmable Output 1Use PGO1 as a +12V, 40 mA programmable output (see Figure 2).
TEL SUPVTelephone SupervisionUse TEL SUPV as a telephone line trouble input (see Figure 2).
J4Telco JackRJ-31X connection.

"2 in 1" Zoning™

Note: If a Normally Open Device (e.g., 4-wire smoke detector) is used with "2 in 1" Zoning™, a short will occur across both zone loops when the device alarms. It is recommended to use such devices with Conventional Zone wiring only.

"2 in 1" Zoning™ is an innovative wiring method that saves time and wire costs by allowing two separate zones to be wired in parallel to a single set of terminals. Each zone is identified by its End-of-Line (EOL) resistor: a 1500 Ohm resistor for the Primary Zone (zones 1-6) and an 825 Ohm resistor for the Secondary Zone (zones 7-12). These zones function independently for reporting, programming, and display.

The maximum total loop wire and contact resistance (excluding EOLs) must not exceed 100 Ohms for proper loop function. Zones can be configured for Form A, Form B, or Form C sensors.

Method 1: Wires one zone loop back to the control, with a second zone loop added in parallel. This method is suitable for retrofits, expansions, or cost savings.

Figure 3: "2 in 1" Zoning™ Wiring - Method 1

This diagram shows Method 1 wiring, illustrating a primary zone loop and a secondary zone loop connected in parallel, each using a specified EOL resistor (1500 Ohm for primary, 825 Ohm for secondary).

Method 2: Wires two separate zone loops into one set of terminals. The panel distinguishes loops by their EOL resistor values (1500 Ohm for Primary, 825 Ohm for Secondary). This method is ideal for pre-wiring or existing wiring.

Figure 4: "2 in 1" Zoning™ Wiring - Method 2

This diagram illustrates Method 2 wiring, showing two distinct zone loops terminating at the same set of terminals, differentiated by their EOL resistors.

Note: The resistors used (1500 Ohm and 825 Ohm) are 1% tolerance. The 1500 ohm resistor is color-coded Brown-Green-Black-Brown-Brown. The 825 ohm resistor is color-coded Gray-Red-Green-Black-Brown.

All zones sense five different voltage levels, allowing one zone to function as two. Troubleshooting is simplified by using a voltmeter at the control to monitor voltage levels, which indicate whether a zone is normal, open, or shorted.

TABLE 1 "2 in 1" Zoning™ Troubleshooting Chart
CONDITIONNOMINAL LOOP RESISTANCEVOLTAGE READING
Primary Zone and Secondary Zone Open Contacts; Loop Cut or OpenInfinite Ohms5.24 - 8.25 V
Secondary Zone Open Contact, Primary Zone Normal1500 Ohms4.24 - 5.23 V
Primary Zone Open Contact, Secondary Zone Normal825 Ohms3.24 - 4.23 V
Primary Zone and Secondary Zone Normal825 Ohms in parallel with 1500 Ohms = 532 Ohms2.00 - 3.23 V
Primary Zone and Secondary Zone Shorted0 Ohms0 - 1.99 V

Conventional Methods of Wiring

Class 'B' End-Of-Line Resistor Supervised Zones

A Class 'B' zone requires supervision with a 1500 Ohm 1/2 Watt EOL resistor (P/N CR854) installed at the furthest point from the control. This configuration is mandatory for Form A and Form B devices and provides enhanced protection. The control monitors the voltage across the Primary zone to determine its status (normal, open, or shorted), using the voltage levels from Table 1. Zone operation is programmable. Maximum total loop wire and contact resistance (excluding EOLs) must not exceed 100 Ohms.

Non-Supervised Closed Circuit Loop (No EOL Resistor Supervision)

EOL resistors are not required for Burglar zones. A closed circuit loop can be connected directly to a primary zone, resulting in either a short or open condition. Fire zones cannot be unsupervised. Only Burglar zones can be wired non-supervised. "2 in 1" Zoning™ is not permitted for non-supervised zones.

Figure 5: Conventional Zone Wiring Method

This diagram shows a conventional zone wiring method with a normally open or normally closed contact and a 1500 Ohm EOL resistor for the primary zone.

Note: For UL Listed systems, EOL Supervision is required.

Control Station Addressing and Supervision

All Control Stations are shipped as supervised Control Station #1. They can be set to different addresses and to unsupervised mode.

A supervised Control Station is reported as missing if the system loses communication. Each supervised station requires a unique address for supervision.

An unsupervised Control Station can be removed from the system without detection. This allows for more Control Stations to be added, limited only by power supply capacity. For UL listed systems, unsupervised Control Stations are not permitted.

SSD, LCD, and VFD Control Stations

These stations use a four-position DIP switch to set the address and supervision. Move DIP switch 4 to the ON position to unsupervise. DIP switch settings for addressing are shown in Figure 6.

Figure 6: Control Station DIP Switch Settings

This figure displays various DIP switch configurations (1-6) with ON/OFF positions for setting addresses.

Note: When using unsupervised stations: LED stations must be addressed as 1 or 2; SSD stations as 3 or 4; LCD/VFD stations as 5 or 6. Supervised and unsupervised stations cannot share the same address.

LED Control Stations

These stations use two jumpers (JP1, JP2) for address and supervision. Removing JP1 unsupervises the station. Removing JP2 sets it as keypad 2.

Figure 7: LED Control Station Jumpers

This figure shows the location of jumpers JP1 and JP2 on the LED Control Station board, with labels indicating their function (unsupervise, keypad 2).

Control Station Troubleshooting

Incorrect wiring of a Control Station will prevent keystroke entries. Symptoms include:

SYMPTOMCONDITION
No Control Station LED's or displayBlack or Red Wire removed or cut
No response from key pressesGreen Wire removed or cut or two supervised Control Stations at the same address
LED's flash and may display "No Communication From Control" codeWhite Wire removed or cut
Green/White Wires reversed
Green & White Wires shorted together

Nominal voltages at the control with a single Control Station connected:

  • From Common Negative (Terminal 7 or 11) to Data A (Terminal 8): ~ 11.5 VDC
  • From Common Negative (Terminal 7 or 11) to Data B (Terminal 9): ~ 7.7 VDC
  • From Common Negative (Terminal 7 or 11) to Control Station Power (Terminal 10): ~13.8 VDC

Clearing Trouble Messages

Most trouble conditions clear automatically when the cause is resolved. Three specific trouble conditions (Memory Error, Smoke Trouble, and Missing Keypad) can be cleared manually by pressing and holding the Clear key for three seconds. This action also turns off the Duress output and triggers an "Installer Off Premises" event.

A Bell Silenced trouble condition requires a smoke reset operation to clear.

12 VDC Outputs & Additional Outputs

12 VDC Outputs

The ZX400/ZX410 control provides one switched negative output, one Control Station power output, one auxiliary power output, one 2-wire smoke power terminal, one bell output, and one programmable low current output (PGO1).

Additional Outputs

Additional outputs can be added using ZXODM Output Driver Modules. Each module provides ten programmable outputs (+12 VDC on activation, limited to 40 mA draw). ODM1 and ODM2 are available. Multiple ODMs can be used at an address if power restrictions are met. ODMs default to ODM1; changing to ODM2 involves removing power, cutting resistor R29, and reapplying power. ODMs connect to the control via a 12-wire cable.

Output conditions are programmable. Refer to the ZX400/ZX410 Programming Manual for details.

ZXODM modules can be mounted in the control enclosure using provided tape. For UL Certified installations requiring rigid mounting, they can be mounted in a ZX410 enclosure using stand-offs (ZEM/ODM Mounting Hardware Pack, P/N 13000515).

Note: Outputs have limited transient immunity and should remain within the enclosure.

Figure 8: ZXODM Mounting

This diagram shows the physical placement of a ZXODM module within the ZX400/ZX410 enclosure.

Data Bus Connection

REDGREENWHITEBLACK
Connect to Control terminal 10Connect to Control terminal 8Connect to Control terminal 9Connect to Control terminal 7

Figure 9: ZXODM Wiring Diagram

This diagram details the ZXODM module's connections. It shows the data bus connections and the J3 connector pinout for the ten programmable outputs, listing wire color, default function, and description for each output (e.g., Tan wire for Burglar output).

12 VDC Outputs & Additional Outputs (Continued)

Outputs can be wired to indicator devices or relay module triggers, provided the 40 mA current draw limit is not exceeded.

Figure 10: Output Connected to a Relay

This diagram illustrates wiring ODM 1 Output 2 to trigger a relay, showing connections via the 12-wire cable and trigger input.

Figure 11: Output Connected to an LED

This diagram shows wiring ODM 1 Output 1 to trigger an LED, including a 470 Ohm current-limiting resistor.

Note: The LED and 470 Ohm resistor are not supplied.

Note: Do not exceed 250 mA total current through the Red (+12V) and Black wires of the twelve-wire cable. For higher current drains, use 18-gauge wire from the control panel terminals.

Expansion Zones

Zones 13-28 are expansion zones that can reside on zone expansion devices like ZXEXP, ZEM, or RF Gateway 1/2. Zone assignment is done through programming (refer to the ZX400/ZX410 Programming Manual).

TABLE 2 ZX400 Zone ID Assignments

ZONEON-BOARDZXEXP ZONERF ZONEZEM ZONE
1On-Board Zone 1 Primary
2On-Board Zone 2 Primary
3On-Board Zone 3 Primary
4On-Board Zone 4 Primary
5On-Board Zone 5 Primary
6On-Board Zone 6 Primary
7On-board Zone 1 Secondary
8On-Board Zone 2 Secondary
9On-Board Zone 3 Secondary
10On-Board Zone 4 Secondary
11On-Board Zone 5 Secondary
12On-Board Zone 6 Secondary
13ZXEXP1 Zone 1 PrimaryRF Device 13ZEM1 Zone 1
14ZXEXP1 Zone 2 PrimaryRF Device 14ZEM1 Zone 2
15ZXEXP1 Zone 3 PrimaryRF Device 15ZEM1 Zone 3
16ZXEXP1 Zone 4 PrimaryRF Device 16ZEM1 Zone 4
17ZXEXP1 Zone 5 PrimaryRF Device 17ZEM2 Zone 1
18ZXEXP1 Zone 6 PrimaryRF Device 18ZEM2 Zone 2
19ZXEXP1 Zone 7 PrimaryRF Device 19ZEM2 Zone 3
20ZXEXP1 Zone 8 PrimaryRF Device 20ZEM2 Zone 4
21ZXEXP1 Zone 1 SecondaryRF Device 21ZEM3 Zone 1
22ZXEXP1 Zone 2 SecondaryRF Device 22ZEM3 Zone 2
23ZXEXP1 Zone 3 SecondaryRF Device 23ZEM3 Zone 3
24ZXEXP1 Zone 4 SecondaryRF Device 24ZEM3 Zone 4
25ZXEXP1 Zone 5 SecondaryRF Device 25ZEM4 Zone 1
26ZXEXP1 Zone 6 SecondaryRF Device 26ZEM4 Zone 2
27ZXEXP1 Zone 7 SecondaryRF Device 27ZEM4 Zone 3
28ZXEXP1 Zone 8 SecondaryRF Device 28ZEM4 Zone 4
29ZXEXP1 2-Wire Smoke Zone
30On-Board 2-Wire Smoke Zone

ZXEXP Zone Expander Module

This module adds 8 zones (or 16 with "2 in 1" Zoning™) to the ZX400/ZX410. It also provides an additional Two-Wire Smoke loop (Zone 29). A maximum of 10 detectors can be installed on the Zone Expander. Fast zones are not supported.

Ten programmable outputs are available, similar to ODM2. Outputs require careful connection, observing power and negative restrictions. They have limited transient protection and should be buffered.

Installation:

  1. Remove the lid, choose a mounting location, and secure the module with screws. Mounting in an enclosure like EB1511 is recommended for environmental protection.
  2. Connect the ZXEXP to the ZX400/ZX410 local data bus. For UL Household Fire Systems, the ZXEXP must be within 500 ft. of the control, with maximum Smoke Zone resistance of 20 Ohms.
  3. Wire initiating devices to the ZXEXP zone terminals, following the control zone wiring guidelines.
  4. Use the 12-wire cable to connect outputs as described in the ZXODM section.
  5. The "Active" LED indicates communication with the control.

Data Bus Connection:

REDGREENWHITEBLACK
Connect to Control terminal 10Connect to Control terminal 8Connect to Control terminal 9Connect to Control terminal 7

Figure 12: ZXEXP Zone Expander Module

This diagram shows the ZXEXP module, its zone terminals (Z1-Z8, SMK), programmable outputs, and data bus connections. It notes that primary zones require 1500 Ohm resistors and secondary zones require 825 Ohm resistors. It also mentions the use of "2 in 1" Zoning™ and four-wire smoke circuits.

Wireless Devices

The ZX400/ZX410 supports Wireless (RF) Devices, including RF Zone Devices (contacts, glassbreaks, PIRs, smoke detectors) and RF User Devices (handhelds). These require one or two RF Gateways (model 4710 or 4720).

  • 4710 RF Gateway: Supports up to 8 RF Zone Devices and 12 RF User Devices. Usable only as RF Gateway 1, providing zones 13-20.
  • 4720 RF Gateway: Supports up to 16 RF Zone Devices and 12 RF User Devices. Can be addressed as RF Gateway 1 or 2, providing zones 13-28.

If two gateways are used, one must be RF Gateway 1 and the other RF Gateway 2. Mount the RF Gateway and wire its local data bus (terminals: +12V - RED; DATA A - GREEN; DATA B - WHITE; NEG - BLACK).

All RF Devices must be programmed into an RF Gateway and mapped to a panel zone or user passcode. RF User Devices on Gateway 1 are independent of Gateway 2. Up to 24 RF User Devices can be used with two 4720 RF Gateways.

Temporarily mount RF Gateways and devices for testing. Reorient or move them as needed for optimal reception.

Testing Received Signal Strength: From the Control Station, press "8", Installer Code (9632), "6", then the RF Zone Device Number (13-28). The station displays signal strength.

  • Strong Signal (HOT / 5 beeps): Good location for transmitter and receiver.
  • Acceptable (ACC / 3 beeps): Normal RF signal level; good location.
  • Low Signal (LOW / 1 beep): Low or unacceptable RF signal. Relocate transmitter/receiver. Make multiple test transmissions, minimizing obstructions.
  • No Signal (NO / 1 long beep): No RF signal detected. Bring transmitter to RF Gateway; check LED. If blinking, transmitter works. If still no signal, check programming. If signal is STRONG or ACCEPTABLE, relocate devices. Power down control to clear signal strength levels before re-testing.

After testing, permanently mount RF Gateways and devices. Note: Series 4000 RF Gateways and transmitters not UL labeled are not allowed in UL Certificated installations.

Fire Zone Modules

ZEM Zone Expansion Module

The ZX400/ZX410 can add Class B Fire zones using ZEM Fire Zone Expansion Modules. Available models: 2502-ZEM (Two Class B Zones) and 2504-ZEM (Four Class B Zones).

A ZEM can be mounted in a ZX410 enclosure or an EX1414 enclosure (P/N 13000421), using the ZEM/ODM Mounting Hardware Pack (P/N 13000515). Connect the ZEM to the ZX400/ZX410 local data bus using one of its two data bus connectors. The second connector can link to another ZEM.

Figure 13: ZEM Mounting

Diagram showing ZEM module mounting within a ZX400/ZX410 enclosure.

Figure 14: ZEM Module Connection

Diagram illustrating ZEM module connections, including data bus connectors and terminals for zones and power. It shows how to connect to the control panel and potentially daisy-chain another ZEM.

Up to four ZEMs can be connected. Address switches (S1-S4) on each ZEM must be set uniquely.

TABLE 3 ZEM Address Switch Settings

ZEM #S1S2S3S4ZONES
1ONOFFOFFOFF13 & 14 OR 13 - 16
2OFFONOFFOFF17 & 18 OR 17 - 20
3ONONOFFOFF21 & 22 OR 21 - 24
4OFFOFFONOFF25 & 26 OR 25 - 28

Initiating devices connect to the ZEM (see figures below).

Figure 15: Class B Connection (ZEM 2502)

Diagram showing Class B wiring for a ZEM 2502 module, illustrating connections for Zone 1 and Zone 2 with 2.7K Ohm EOL resistors for 2-wire detectors.

Figure 16: Class B Connection (ZEM 2504)

Diagram showing Class B wiring for a ZEM 2504 module, illustrating connections for Zones 1-4. It shows 2-wire detectors for Zone 1 and 2-wire heat detectors and pull stations for Zone 4, each with 2.7K Ohm EOL resistors.

ZRM Zone Relay Module

The ZRM Zone Relay Module follows its corresponding zone on a ZEM. It plugs directly into a ZEM and requires wiring for NO, COM, and NC terminals. Each relay has dry, Form "C" contacts rated 2A @ 30 VDC resistive.

Note: Circuits connected to a ZRM must be power-limited.

ZXCFK Fire Module Kit

This kit provides hardware to upgrade a ZX410 for UL Listed commercial fire system requirements per UL 864/NFPA 72. Refer to the ZX440F Installation/Programming Manual (P/N 64812853) for upgrade instructions.

Figure 17: Mounting ZRM to ZEM Module

Diagram showing a ZRM module plugging into a ZEM module, illustrating the physical connection and relay terminals.

Power Issues

Optional Battery Configurations

To meet UL985 & CSFM standby requirements (24 hours at 400 mA), install a minimum of two 12 VDC, 7 Ah sealed lead-acid batteries using the Dual Battery Harness (Figure 18).

Figure 18: Connection of the Dual Battery Harness

Diagram showing the connection of two batteries (BATTERY A, BATTERY B) to the control panel via a dual battery harness.

ZX400/ZX410 Power Worksheet

This worksheet is provided to calculate system power requirements, including standby and alarm current, and required battery capacity based on NFPA 72 standards.

Auxiliary Power Supply Installation

A HCP-12SULC Power Supply can be added to increase available current, providing an additional 450 mA and utilizing at least one 12 Ah battery. The HCP-12SULC offers a 12 VDC output rated at 2.0 A continuous when AC power is present, switching to battery power if AC is lost.

For listed systems, a duplex utility cover is required for the primary power outlet. Conduit or other raceway should be used between junction boxes and enclosures.

Use only recommended batteries and transformers. Refer to "Optional Battery Configurations" for details on connecting additional batteries.

Note: The HCP-12SULC must not be connected to a load exceeding 2.0A continuous demand.

Figure 19: HCP-12SULC Power Supply Installation

Diagram illustrating the installation of the HCP-12SULC auxiliary power supply, showing connections for the transformer, power output terminals, and battery.

ZXPTR Printer Interface Module

The optional ZXPTR Printer Interface Module connects to the local data bus for real-time or on-command event printing. It interfaces with any Centronics-style parallel printer; only one printer per system is supported. The printer connection is not supervised.

Installation:

  1. Choose a suitable location within 25 feet of the printer.
  2. Remove the cover and mount the base.
  3. Attach the printer cable to the ZXPTR port.
  4. Wire the local data bus to the terminals: +12V (red), Data A (green), Data B (white), NEG (black).
  5. Reinstall the circuit board and cover.
  6. The "Active" LED indicates communication with the control.

Specifications And Features

Control Board

  • Six (6) two-wire zones, each supervised with a 1500 Ohm EOL resistor.
  • "2 in 1" Zoning™ provides twelve (12) programmable zones with 1500 and 825 Ohm resistors.
  • System expandable to 28 programmable zones via ZXEXP Zone Expander Module.
  • On/Off power switch.
  • One assignable high current alarm output (Supervised Bell Output).
  • One programmable low current output (40 mA).
  • Fast zone loop response time: 80 msec (zones 1-6), 20 msec (zones 7-12).
  • Dedicated two-wire smoke detector zones on control (zone 30) and zone expander (zone 29).
  • Three (3) Control Station activated panic zones.
  • Nominal current drain for control board only: 126-154 mA.
  • Watchdog microprocessor monitoring.
  • Superior six (6) stage lightning/transient protection.
  • One switched negative output (100 mA).
  • Expandable to twenty-one (21) programmable low current outputs via two output driver modules and/or a zone expander.
  • Continuous battery monitoring.
  • Low voltage detection monitoring @ 11.3 volts threshold.
  • Automatic system shutdown if voltage falls below 9.8V.
  • Operating temperature range: 32°F to 122°F (0°C to +50°C).
  • Two and four-wire smoke zones available.
  • Control Station Programmable.
  • Upload/Download via RPM/2 Pro.
  • Loop response time: 320 msec (hardwired zones), 1600 msec (two-wire smoke zones).

Power Supply

  • Fully regulated 13.8 volt 900 mA supply with a 16.5 VAC 35 VA transformer.
  • Optional 16.5 VAC 20 VA transformer provides 450 mA power (not UL Listed).
  • Reverse polarity protection on battery inputs.
  • Float charging circuit: 13.8 volts DC.

Recommended Battery

  • Rechargeable 12 VDC 7 Ah sealed lead acid: Use two (2) batteries for CSFM and Household Fire 24-hour standby at 450 mA.
  • Rechargeable 12 VDC 17.2 Ah sealed lead acid: Use one (1) battery for CSFM 24-hour standby at 450 mA.

Recommended Transformer

  • UL Listed Class II plug-in; 16.5 VAC 35 VA secondary; 120 V 60 Hz primary connected to a 24-hour unswitched outlet.
  • Optional UL Listed Class II plug-in 16.5 VAC 20 VA secondary; 120 V 60 Hz primary connected to a 24-hour unswitched outlet.

Enclosure

  • Twenty (20) gauge metal cabinet (9"W x 10"H x 2.875"D).
  • Optional EX1414 locking metal cabinet (14"W x 14"H x 3.5"D).
  • TC1100 Tamper Resistant Enclosure (uses EX1414 option).

Digital Communicator

  • DTMF Touchtone™ or Rotary (pulse) dialing.
  • Rotary speed: 10pps (selectable U.S. or International).
  • Ringer equivalence: 0.0B.
  • Transmission formats: Contact ID, 20/40 baud Pulse, Hexadecimal Reporting, Non-Telco Contact ID, Pager.
  • Reports to most major Central Station receivers.
  • Primary/Secondary phone numbers up to 20 digits each.
  • Two pager phone numbers up to 20 digits each.
  • Remote programming phone number up to 20 digits.
  • Reporting capabilities: account codes, zone reports, opening/closing, force arm/bypass, restoral, trouble, low battery, AC failure/restoral.
  • Dual and split reporting capability.
  • Pager capability with 16-digit programmable message and 2-digit codes.
  • Sentrol communication defaults for quick programming.
  • Disable call waiting.

Control Stations

  • Color-coded four-wire data bus connection.
  • 19-Button Control Station with audible feedback.
  • Three (3) Control Station panic button zones.
  • Surface mountable to standard single/double gang boxes.
  • Built-in piezo sounder.
  • Backlit LEDs for AWAY, STAY, NIGHT arming levels.
  • Backlit keys with door.
  • Unsupervised Control Stations allow up to 12 stations.

ZXLCD Control Station

  • Backlit display, two lines x 16 characters LCD.
  • Area assignable/Multi-area.
  • Addressable with DIP switches, supervised/unsupervised.
  • Plain English display.
  • Nominal current drain: 20mA - 110mA.
  • Up to six (6) supervised stations per system.
  • Size: 5.33"H x 6.08"W x 1.024"D.
  • Optional red plastic for Commercial Fire applications.

ZXVFD Control Station

  • Two lines x 16 characters VFD display.
  • Area assignable/Multi-area.
  • Addressable with DIP switches, supervised/unsupervised.
  • Plain English display.
  • Nominal current drain: 20 - 170 mA.
  • Up to six (6) supervised stations per system.
  • Size: 5.33"H x 6.08"W x 1.024"D.

ZXLED12 Control Station

  • Thirteen (13) LEDs for general purpose zones 1-12 and Two-Wire Fire zone.
  • Ready & trouble LEDs.
  • Addressable as Control Station #1 or #2; jumper change for unsupervised.
  • Area assignable/Single area.
  • Nominal Current Drain: 23 - 31mA.
  • Size: 5.0"H x 4.5"W x 1.0"D.

ZXSSD Control Station

  • Three 0.56" (14.2 mm) seven segment display digits.
  • Ready & trouble LEDs.
  • Up to six (6) supervised stations per system.
  • Area assignable/Multi-area.
  • Addressable with DIP switches, supervised/unsupervised.
  • Nominal Current Drain: 23 - 116 mA.
  • Size: 5.0"H x 4.5"W x 1.0"D.

Optional Accessories

  • ZXEXP Zone Expander Module: Expands control to 8/16 additional zones, adds a two-wire smoke zone (max. 10 detectors), and provides 10 programmable outputs. Nominal current drain: 60 - 72 mA (no outputs connected).
  • ZXODM: Output Driver Module: Provides ten (10) programmable 40 mA +12 VDC outputs. Nominal current drain: 10 - 13 mA (no outputs connected).
  • ZXPTR Printer Interface Module: Connects a standard parallel printer. Nominal current drain: 45 - 55 mA (without printer).
  • ZX410 - ZX400 Control board: Mounted in EX1414 enclosure (required for Burglary applications).
  • ZX440F - ZX400 Control board: Mounted in EX1414F enclosure with ZXCFM Fire Module (required for Commercial Fire applications).
  • F2600 Transformer Enclosure: Secures AC plug-in transformer to wall outlet (required for Commercial Fire applications).
  • T-1635 Transformer: UL Listed Class II plug-in 16.5 VAC 35 VA secondary.
  • T-1620 Optional Transformer: UL Listed Class II plug-in 16.5 VAC 20 VA secondary.
  • T1850 Transformer: UL Listed Class II plug-in 18 VAC 50 VA secondary.
  • HCP-12SULC Power Supply: Provides 12 or 24 VDC power-limited output (2.0 A continuous) while AC is present.
  • CR860 Dual Battery Harness: Allows connection of an additional 12 VDC 7 Ah battery.
  • CR862 Battery Harness: Allows connection of a 12 VDC 17.2 Ah battery.
  • EB1511 Auxiliary Enclosure: 15" x 11" x 4" enclosure with cam lock.
  • EX1414 Optional Larger Enclosure: 14" x 14" x 3.5".
  • EX1414F Larger Red Enclosure for Fire: 14" x 14" x 3.5".
  • AE912 Raucous Sounder: Current consumption: 28 mA @ 12 VDC.
  • MPI-266 Battery Cut-Off Module: Disconnects battery from deep discharges.
  • MPI-267 Power Disconnect Module: Disconnects battery from deep discharges.
  • MPI-268 Earth Ground Fault Detector: Current consumption: less than 20 mA.
  • MPI-206 General Purpose Relay Module.
  • 4710 RF Gateway: (8 RF Zone Devices, 6 RF User Devices). Nominal Current Drain: 80mA.
  • 4720 RF Gateway: (16 RF Zone Devices, 12 RF User Devices). Nominal Current Drain: 80mA.
  • 4110 Universal Transmitter and battery.
  • 4545 Shatter Pro Glassbreak Detector with Transmitter and batteries.
  • 4655 Sharpshooter PIR with Transmitter and battery.
  • 4004 Four Button Wireless Key Transmitter and Battery.
  • 4310S, ST, SLT Wireless Smoke Detectors (UL 217) with Transmitter and Battery.
  • 4330S, ST, SLT, SLTM Wireless Smoke Detectors (UL 268) with Transmitter and Battery.
  • 4113 Three Point Universal Transmitter and Battery.
  • 4010 Single Button Panic Transmitter and Battery.
  • 4011 Dual Button Panic/Medical Transmitter and Battery.
  • ZEM Fire Zone Expansion Modules: 2502-ZEM (Two Class B Zones), 2504-ZEM (Four Class B Zones). Current Drain: 40 - 60 mA. Max. Line Resistance: 100 Ohms (Class B).
  • ZRM Zone Relay Modules: ZRM-2 (2 Zones), ZRM-4 (4 Zones). Contact Rating: 5 A @ 12 VDC, 120 VAC resistive.
  • ZXIRR01 Security System Remote Control with Keyfob Transmitter.
  • ZXLCDD1 LCD Keypad Demonstrator. (Demo Unit Only).
  • ZXVFDD1 VFD Keypad Demonstrator. (Demo Unit Only).
  • TC1100 Tamper Enclosure.
  • ZXCVR-Red Tamper Enclosure with two 3025T Tamper Switches.

Output Provisions

  • Low Current Trigger Outputs: 40 mA each. One on the main board, expandable to 21 with ZXODM or ZXEXP. Maximum combined continuous current drain at Terminals 4, 5, 6, 10, and PG01 is 0.9 amps with a 16.5 VAC 35 VA transformer.
  • Current Limits: Bell Output Terminal 5 limited to 1.85 amps (PTC2). 12V Auxiliary limited by PTC4 to 1.35 amps. Reverse battery protection limited to 1.85 amps (PTC3).

Compatible Accessories

List Of Compatible Accessories

ESL Two-Wire Smoke Detectors

  • 429 AT, C, CT, CRT, CST: Standby Current: 70 µA max. (Max. 20 detectors per zone)
  • 521 B, BXT, CRXT: Standby Current: 70 µA max. (Max. 20 detectors per zone)
  • 711U, 712U, 713-5U, 713-6U: Standby Current: 70 µA max. (Max. 20 detectors per zone)
  • 721U, 721UT, 721UD, 722U, 722UD: Standby Current: 70µA max. (Max. 20 detectors per zone)
  • 731U, 732U: Standby Current: 70 µA max. (Max. 20 detectors per zone)

ESL Four-Wire Smoke Detectors

  • 445 AT: Standby Current: 500 µA @ 6 V; 1.5 mA @ 15 V
  • 445 C, CR, CRT, CS, CSH, CST, CSR, CSRT: Standby Current: 40 µA @12 V; 100 µA @ 24 V
  • 449 CTE: Standby Current: 10 µA max
  • 449 C, CT, CRT, CST, CSRT, CSRH, CSST: Standby Current: 70 µA max

System Sensors Two-Wire Smoke Detectors

  • 1100 Ionization
  • 1400 Ionization
  • 1400TH Ionization
  • 2100 Photoelectric
  • 2100T Photoelectric
  • 2400 Photoelectric
  • 2400AT Photoelectric
  • 2400TH Photoelectric (Max. 6 detectors per zone)

System Sensors Four-Wire Smoke Detectors

  • 1112, 1112 Ionization
  • 1412B Ionization
  • 1451 Ionization
  • 2112, 212 Photoelectric
  • 2112, 2124T Photoelectric
  • 2112, 2124TSR Photoelectric
  • 2412B Photoelectric
  • 2412THB Photoelectric
  • 2412AT Photoelectric
  • 2451 Photoelectric
  • 2451TH Photoelectric

Wheelock

  • 34T-12R Horn: Input voltage: 9-15.6 VDC; Rated Current: 0.125 A
  • EH-DL1-R Electronic Horn: Input voltage 12/24 VDC; Input Current; (@ 12 VDC) 0.015 A/(@24 VDC) 0.017 A
  • EH-DL2-R Electronic Horn: Input voltage: 12 VDC; Input Current: 0.047 A.
  • EH-EL1-R Electronic Horn: Input voltage: 12/24 VDC; Input Current: (@12 VDC) 0.015 A/(@ 24 VDC) 0.017 A
  • EH-EL2-R Electronic Horn: Input voltage: 12 VDC; Input Current: 0.047 A
  • AES-DL2-R Multi-tone Electronic Signal: voltage: 12 VDC; Current (High): 0.050 A; Current (Low): 0.025 A
  • AES-EL2-R Multi-tone Electronic Signal: voltage: 12VDC; Current (High): 0.0100 A; Current (Low): 0.050 A
  • MIZ-12-R Mini horn: voltage: 12 VDC; Current: 0.010 A
  • MIZ-12-W Mini-horn: voltage: 12 VDC; Current 0.010 A
  • CH-BF2-R Fire Chime: Input voltage: 12 VDC; Input Current: 0.020 A
  • CH-CF2-W Fire Chime: Input voltage: 12 VDC; Input Current: 0.020 A
  • CH-DF2-R Fire Chime: Input voltage: 12 VDC; Input Current: 0.020 A
  • 46T-G4-12-R DC Vibrating Bells: Shell Size: 4 Inches; Input voltage: 12 VDC; Input Current: 0.125 A
  • 46T-G6-12-R DC Vibrating Bells: Shell Size: 6 Inches; Input voltage: 12 VDC; Input Current: 0.125 A
  • 46T-G10-12-R DC Vibrating Bells: Shell Size: 10 Inches; Input voltage: 12 VDC; Input Current: 0.080 A

Compatible Central Station Receivers

UL permits communication with the following UL Listed Central Station receivers (see the ZX400/ZX410 Programming Guide, P/N 64812702, for format):

ManufacturerModel Number
Ademco685
Fire Burglary InstrumentsCP-220
Osborne-HoffmanQuick Alert II
Radionics6000
Radionics6500
Silent Knight9000
Sur-GardMLR2-DG

Agency Requirements

UL has established requirements for the installation, use, and programming of this equipment. Local Authorities Having Jurisdiction (AHJ) and/or UL may have additional requirements. The installing dealer is responsible for checking with the AHJ and/or UL.

TABLE 4 Agency Power and Configuration Requirement

ApplicationListingMaximum Continuous Current Drain Standby (milliamps) w/ 7 AH BatteryMinimum Battery Time In HoursLCD or LED Control StationsSSD or VFD Control StationsSmoke Detector ESL 429 & 700 series, System Sensors 1400 & 2400 seriesAuxiliary Equipment Required
Home Health CareUL 1637400464N/AUL listed signaling device
Household BurglaryUL 1023
Household FireCSFM UL 9854002464RequiredUL listed signaling device
Household Burglary/ Fire CombinationUL 1023 UL 985400464RequiredUL listed signaling device
Central Station Burglary (Grade C)UL 1610 UL 1635400464N/ATC1100 Tamper Resistant cover with a ZX410
Central Station (Grade B)UL 1610 UL 1635400464N/ATC1100 Tamper Burglary Resistant cover with a ZX410 and a UL listed audible device (AB12M recommended)
Local Burglary (Grade A)UL 609400464N/ATC1100 Tamper Resistant cover with a ZX410 and a UL listed audible device (AB12M recommended)
Police Station Connection (Grade A)UL 365400464N/ATC1100 Tamper Burglary Resistant cover with a ZX410 and a UL listed audible device (AB12M recommended)

Maximum combined continuous current drain (standby) refers to terminals 4, 5, 6, 10, and PGO1. Under alarm conditions, the combined output current drain should not exceed 950 mA with a 16.5 VAC 35 VA transformer. For 24 hr standby, UL Household Fire & CSFM, two 7 Ah batteries are required.

TABLE 5 UL and ULC Listings

APPLICATIONLISTING
Household BurglaryUL 1023
Household FireUL 985
Household Burglary/Household Fire CombinationUL 1023/UL 985
Local Burglar Alarm Grades A, B and C Central StationUL 609
Police Station Connect Burglar Alarm UnitUL 365
Digital Alarm Communicator SystemUL 1635
Home Health Care Signal SystemUL 1637
Central Station Burglar Alarm UnitUL 1610
California State Fire Marshal7167-1459:109
Residential Burglar SystemULC 5310
Local Burglar AlarmULC 5303
Central StationULC 5301
Commercial BurglaryULC 5302
Burglar Alarm Units Central & MonitoringULC 5304

National Fire Protection Association (NFPA) Rules

The National Fire and Burglar Alarm Association (NFPA) has established rules for fire prevention and fire detection equipment installation.

Smoke Detector Locations

For residential applications, install smoke detectors in each bedroom and outside each sleeping area, on each story (including basements, excluding crawl spaces/unfinished attics). In new construction, install in each sleeping area. For split levels, one detector per adjacent lower level is sufficient if there's no intervening door. For commercial applications, install in each work area, hallways, and storage areas.

Install ceiling-mounted detectors in the center of the room/hall, at least 4 inches from any wall. Wall-mounted detectors should have the top 4 to 12 inches from the ceiling.

Do not install smoke detectors where ambient temperatures exceed 100°F (37.8°C).

Avoid placing detectors in front of air conditioners, heating registers, ceiling fans, or areas with strong air circulation that could prevent smoke entry.

Heat rises and spreads across ceilings. Corners where ceilings meet walls create dead air spaces (approx. 4 inches along ceiling, 4 inches down wall) that heat/smoke may have difficulty penetrating. Do not place detectors in these dead air spaces.

Testing

This system should be tested weekly. All components must be UL Listed devices. Installation must comply with National Fire Protection Association Standard No. 72. Control panel specifications are subject to change.

Consult smoke detector specifications and local/national codes for coverage details.

Figure 20: Smoke Detector Placement

This diagram illustrates recommended smoke detector placement in residential settings. It shows ceiling and wall mounting guidelines (e.g., minimum 4 inches from walls/ceiling edges) and indicates required vs. optional detector locations based on room type and layout. It also notes that detectors should be on each story and in each sleeping area.

System Troubleshooting

When a trouble condition is detected, it's displayed on the Control Station(s) and a trouble tone sounds. The tone silences when the condition is resolved or manually cleared. The display remains until the condition is cleared.

TROUBLEDESCRIPTION
AC FAILUREIndicates loss of AC power or insufficient AC voltage.
ALARM SILENCEDIndicates an Auxiliary or Holdup Alarm is present and has been manually silenced.
BELL 1 FAULTIndicates an open in wiring or missing EOL on the Bell.
BELL SILENCEDIndicates a Fire Alarm is present and the Fire Bell has been manually silenced. Requires a manual Smoke Reset.
CALL RPM FAILIndicates an installer-initiated call to the Remote Programming computer was unsuccessful.
COMM FAILUREIndicates an event was not successfully communicated to the Central Station. Can be cleared by disabling both phone lines.
FIRE TROUBLEIndicates a wiring problem on a Fire zone, a Fire Alarm condition, or the Fire Bell(s) manually silenced. Requires a manual Smoke Reset.
KEYPAD MISSINGIndicates a supervised keypad is not responding. Causes: keypad removed/address changed, faulty data bus wiring, multiple supervised keypads at same address. Cleared by holding CLEAR key for 3 seconds.
LOW/NO BATTERYIndicates low or no battery voltage.
MEMORY ERRORIndicates corruption of Function Map data. Cleared by holding CLEAR key for 3 seconds.
NO COMMUNICATION FROM CONTROLIndicates keypad not receiving commands. Causes: faulty data bus wiring, bad keypad address, control panel failure, or shutdown due to low voltage.
NON-TELCO FAILIndicates Non-Telco reporting selected, but interface is not functioning.
PHONE LINE 1 FAILIndicates Phone Line Monitoring enabled for Phone Line 1, but a fault is detected or no monitor is connected. Cleared by disabling monitoring.
RF JAMMINGRF Gateway detects noise affecting RF transmissions. If jamming persists for 90 seconds, RF Burglar Zones will fault.
RF LOW BATTERYRF Point or RF User Device battery needs replacement.
RF NOT REPORTINGRF Point is no longer transmitting to RF Gateway.
RF SENSOR TAMPERCover removed from RF Point.
SMOKE TROUBLEIndicates a Smoke Detector needs cleaning. Clears automatically after cleaning or via Smoke Reset/CLEAR key.
SUPERVISORY TROUBLEIndicates a wiring problem on a Fire Supervisory zone or a Supervisory Alarm condition is present and manually silenced.
ZONE MISSINGIndicates zone's expansion device is not responding.
ZONE TROUBLEIndicates a wiring problem on the zone or a Burglar Tamper condition exists and has been silenced.

FCC Compliance

Part 68 Notification

This equipment complies with FCC Part 68 rules. Connections to the telephone network must use standard plugs/jacks (RJ-31X or equivalent) for easy disconnection. Unplugging the cord should not interfere with other connected equipment.

The FCC registration number and Ringer Equivalence Number (REN) are on the inside label. The REN helps determine the number of devices that can be connected to a phone line without affecting ringing. The sum of RENs should not exceed 5.0.

If the equipment malfunctions, disconnect it from the phone jack to isolate the problem. Leave disconnected until repaired or replaced.

If the equipment causes harm to the telephone network, the phone company may temporarily discontinue service, with or without advance notice. The subscriber will be notified and given an opportunity to correct the situation. Complaints can be filed with the FCC.

The telephone company may change its facilities, affecting equipment operation. Advance notice will be provided for such changes.

Notify the telephone company if the equipment is removed and the phone jack is no longer needed.

Part 15 Notification

This equipment has been tested and complies with Class B digital device limits (FCC Part 15) to provide reasonable protection against harmful interference in residential environments. It generates, uses, and can radiate RF energy. Improper installation may cause interference. If interference occurs:

  • Reorient or relocate the receiving antenna.
  • Increase separation between equipment and receiver.
  • Connect to a different circuit outlet.
  • Consult dealer or experienced radio/TV technician.

Caution: Changes or modifications not expressly approved by the manufacturer may void the user's authority to operate the equipment.

Canadian Notice

Canadian Department of Communications certification ensures compliance with telecommunications network requirements. The Department does not guarantee user satisfaction. Users must ensure compliance with local telecommunications company connection methods. Repairs should be done by authorized facilities. Unauthorized alterations may cause the company to request disconnection. Ensure proper electrical ground connections.

Caution: Do not attempt connections yourself; contact an appropriate authority or electrician.

The LOAD NUMBER (LN) indicates the percentage of total load on a telephone loop. The total LN for the system is 2.

This equipment is a Class B Digital apparatus compliant with CRC c. 1374.

Limitations

The ZX400/ZX410 is designed to warn against unauthorized entry or other situations but is not a guarantee of protection. Alarm systems can be compromised or fail. Unauthorized access is possible. Sensing devices require power. Telephone lines can be disrupted. Smoke detectors have limitations and cannot detect all fire types or smoke outside their range.

All Rights Reserved

No part of this publication may be reproduced, stored, or transmitted without prior written permission. Material is for informational purposes and subject to change without notice. Manufacturer assumes no responsibility for errors. Printed in USA.

Special Note: Use of this control for fire detection may not be permitted in all jurisdictions. The installing company must verify local AHJ or State Fire Marshal's office approval.

This Product is Listed by UNDERWRITERS LABORATORIES INC. and Bears the Mark: UL

Contact Information

SENTROL CONTROLS GROUP

PO Box 2904, 1510 Tate Blvd. SE
Hickory, NC 28603

Tel.: 503.692.4052 Fax: 503.691.7566
U.S. & Canada: 800.547.2556
Technical Service: 800.800.2027
FaxBack: 800.483.2495

Sentrol reserves the right to change specifications without notice. ©1997 Sentrol

PDF preview unavailable. Download the PDF instead.

Sentrol ZX400 ZX410 Install 1997 Acrobat Distiller 3.01 for Power Macintosh PageMaker 6.5

Related Documents

Preview Sentrol ZXLCD/ZXVFD Security System User Manual
User manual for Sentrol ZXLCD/ZXVFD security control stations (ZX200, ZX210, ZX400, ZX410, ZX440F). Covers operation, programming, testing, and safety for Sentrol alarm systems.
Preview Sentrol Security System ZXLCD/ZXVFD User Manual: Operation Guide
This user manual provides comprehensive instructions for operating the Sentrol ZXLCD/ZXVFD, ZX200, ZX210, ZX400, ZX410, and ZX440F security control stations. Learn how to arm, disarm, manage alarms, and utilize advanced features for your home or business security.
Preview Sentrol Security System ZXLCD/ZXVFD Control Station User Manual
Comprehensive guide on operating and understanding Sentrol ZX200, ZX210, ZX400, ZX410, and ZX440F security systems with ZXLCD/ZXVFD control stations. Covers arming, disarming, features, testing, and troubleshooting.
Preview Sentrol ZX400/ZX410 Programming Manual: Security System Guide
This manual provides comprehensive instructions for programming the Sentrol ZX400/ZX410 security system, covering installation, control station operation, and advanced configuration options.
Preview Sentrol ZXLCD Control Station User Manual - ZX440F Security System
Comprehensive user manual for the Sentrol ZXLCD Control Station and ZX440F Security Control. Covers system operation, programming, testing, fire detection, and safety precautions.
Preview Sentrol ZXICON Control Station: User Manual for ZX300/ZX310 Security Systems
Comprehensive user manual for the Sentrol ZXICON Control Station, detailing operation, features, testing, and troubleshooting for ZX300 and ZX310 security systems.
Preview Sentrol Advisor X DV1200 Series Structural Vibration Detection System Installation Guide
Comprehensive installation instructions for the Sentrol Advisor X DV1200 Series Structural Vibration Detection System (Models DV1201, DV1221). Learn about planning, mounting, wiring, and testing for enhanced security in vaults, safes, ATMs, and more.
Preview SafeAir Carbon Monoxide Alarm Installation Instructions
Comprehensive installation, operation, and safety guide for the SafeAir Carbon Monoxide Alarm (Model 240-CO) by Sentrol. It covers safety precautions, CO poisoning symptoms, sources, and limitations of CO detection.