Mircom FA-1000 Series Fire Alarm Control Units
Product Description
Mircom's FA-1000 Series Microprocessor Based Fire Alarm Control Panels are Multi-Zone units designed for maximum flexibility and easy installation and operation. Fully configurable from the front panel using push buttons and DIP switches, the FA-1000 Series enables the user to configure the system to meet their specific requirements. With a large capacity of supervised Class A (Style D) or Class B (Style B) Initiating Circuits and supervised Class A (Style Z) or Class B (Style Y) Indicating Circuits, the FA-1000 Series is designed to meet virtually all applications.
The FA-1000 Series consists of a Main Fire Alarm Chassis which houses and controls all other modules. Additional modules may be installed to configure the system to meet any requirements that the user may have. The FA-1000 Series allows for additional Indicating Circuit, Initiating Circuit and Relay modules to be added to the system. In addition, it allows for optional modules such as the UDACT-300A Digital Communicator and the PR-300 Polarity Reversal/City Tie Module.
Equipped with Configuration DIP Switches on the Main Display Module, the FA-1000 Series Fire Alarm Control Panels are configured through a combination of DIP switch and button settings. Through this configuration method, the user can define the system as a Single Stage or Two Stage operation, as well as perform various functions such as a One Man Walk Test.
Key Features
- Listed to UL 864, 9th edition
- Large system capacity
- Modular design
- Each Indicating Circuit can be configured as Silenceable or Non-Silenceable
- Audibles may be configured as Steady, Temporal Code, California Code or March Time
- Each Initiating Circuit can be configured as Alarm, Supervisory, Waterflow or Trouble
- Two LEDs per Initiating circuit; one for Trouble and one for Status
- Initiating and Indicating Circuits may be individually disconnected by a DIP switch
- Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation and One Man Walk Test
- Subsequent Alarm, Supervisory and Trouble operation
- Two outputs for 4 wire resettable smoke power supply (200 mA Max. each)
- Auxiliary relay contacts for Common Alarm and Common Supervisory as well as a Common Trouble Relay (Each relay contact Form C, 28 VDC @ 1 Amp (resistive))
- RS-485 Interface for RA-1000 Remote Multiplex Annunciators
- Interface for Remote Trouble Indicator
- Easy configuration via push buttons and DIP switches on the front panel
- Fully site or field programmable Indicating Circuits and Auxiliary Relays
- Extensive Transient Protection
- Slide-in labels for zone identification
- 6 Amp or 12 Amp power supplies available
- Removable door for easy installation and servicing
- Removable terminal blocks for easy wiring and servicing
Optional Modules
- UDACT-300A Digital Communicator Module
- PR-300 Polarity Reversal and City Tie Module
System Components
Main Control Units
MCC-1024-6ADS / MCC-1024-12ADS: These Main Control Units come complete with 8 Class B (Style B) or 4 Class A (Style D) Initiating Circuits, 4 Class A/B (Style Z/Y) Indicating circuits, a common control and zone identification display board for up to 24 points. The MCC-1024-6ADS includes a 6 Amp Power Supply which charges 10-24 AH batteries, while the MCC-1024-12ADS is equipped with a 12 Amp Power Supply which charges 17-40 AH batteries. Both models are expandable with up to two adder modules of any type plus one optional module (UDACT-300A or PR-300). Both models mount in a UB-1024DS(R) backbox.
MCC-1024-12XTDS: This Main Control Unit comes complete with 8 Class B (Style B) or 4 Class A (Style D) Initiating Circuits, 4 Class A/B (Style Z/Y) Indicating circuits, a common control and zone identification display board for up to 72 points, and a 12 Amp Power Supply which charges 17-40 AH batteries. It is expandable with up to eight adder modules of any type plus one optional module (UDACT-300A or PR-300). The MCC-1024-12XTDS mounts in a BBX-1024XT(R) enclosure.
Adder Hardwire Modules
- DM-1008A Eight Initiating Circuit Module: Provides 8 Style B (Class B) or 4 Style D (Class A) Initiating Circuits configurable for Alarm, Supervisory, or Trouble zones. Occupies one module slot.
- SGM-1004A Four Notification Appliance Circuit Module: Provides 4 Style Z/Y (Class A/B) Notification Appliance Circuits configurable as Silenceable or Non-Silenceable. Each NAC circuit is rated at 1.7 Amps. Occupies one module slot.
- RM-1008A Eight Relay Circuit Module: Provides eight individual configurable relays per module. Each relay provides one Form C contact rated at 28 VDC @ 1 Amp (resistive load) and a Green LED to indicate activity. Occupies one module slot.
Auxiliary Modules
- UDACT-300A Digital Alarm Communicator Module: Allows transmission of addressable point information to a central station. Occupies one module slot.
- PR-300 Polarity Reversal/City Tie Module: Provides the system with a supervised City Tie and Polarity Reversal connection. Occupies one module slot.
FA-1000 Series Enclosures
- UB-1024DS Universal Backbox: Houses the MCC-1024-6ADS/12ADS and provides space for up to 17 AH batteries. Requires a DOX-1024DS(R) door (ordered separately). Dimensions (minus built-in trim ring): 26"H x 14.5"W x 4.2"D.
- DOX-1024DS(R) Door: Mounts on the UB-1024DS backbox. Features the universal CAT-30 lock. Available in white (DOX-1024DS) or red (DOX-1024DSR) exterior.
- BBX-1024XT(R) Enclosure: Supports one MCC-1024-12XTDS and up to 18 AH Batteries. Features the universal CAT-30 lock and a removable door for easy installation and servicing. Available in white (BBX-1024XT) or red (BBX-1024XTR) exterior. The FA-XT-TRB Semi-Flush Trim Ring is required for semi-flush mounting. Dimensions: 35 ½”H x 14 ½"W x 5 "D.
RA-1000 Series Remote Multiplex Annunciators
- RAM-1032TZDS Main Remote LED Annunciator: Provides common annunciator functions and 32 points of LED annunciation. Includes indicators for A.C. On, Common Trouble, and Signal Silence, plus controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence, and Signal Silence. Occupies one display position in BB-1000 or BB-5000 enclosures.
- RAM-1016TZDS Main Remote LED Annunciator: Provides 16 points of LED annunciation and 16 trouble LEDs. Includes indicators for A.C. On, Common Trouble, and Signal Silence, plus controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence, and Signal Silence. Mounts in a BB-1000 series enclosure.
- RAX-1048TZDS Programmable LED Annunciator Module: Provides 48 programmable bi-colored LEDs. Connects to the main unit or other RAXN-LCD or RAM-1032TZDS modules when mounted remotely. Occupies one display position in FX-2003-12NXTDS, BB-1000, or BB-5000 Series enclosures.
Dimensions for Annunciator Module Enclosures
Model | Dimensions |
---|---|
BB-1001 | 9"H x 12.75"W x 1.2"D |
BB-1002 | 18"H x 12.75"W x 1.2"D |
BB-1003 | 26.4"H x 12.75"W x 1.2"D |
BB-1008 | 33"H x 22.5"W x 1.25"D |
BB-1012 | 45"H x 22.5"W x 1.25"D |
Electrical Ratings
MCC-1024-6ADS
AC Line Voltage | 120V 60Hz / 240V 50 Hz, 2A / 1A primary |
Power Supply Ratings | 6 Amps. max. (secondary) |
For Indicating Circuits | 24VDC unfiltered, 5 Amps maximum |
Charging Capability | 10-24 AH batteries |
Current Consumption (Standby) | 200 mA |
Current Consumption (Alarm) | 350 mA |
MCC-1024-12ADS / MCC-1024-12XTDS
AC Line Voltage | 120V 60Hz / 240V 50 Hz, 4A / 2A primary |
Power Supply Ratings | 6 Amps. max. (secondary) |
For Indicating Circuits | 24VDC unfiltered, 10 Amps maximum |
Charging Capability | 17-40 AH batteries |
Current Consumption (Standby) | 200 mA |
Current Consumption (Alarm) | 350 mA |
Ordering Information
Model | Description |
---|---|
Main Control Unit | |
MCC-1024-6ADS | Main Control Unit, 6 Amps. Mounts in UB-1024DS. |
MCC-1024-12ADS | Main Control Unit, 12 Amps. Mounts in UB-1024DS. |
MCC-1024-12XTDS | Main Control Unit, 12 Amps. Mounts in BBX-1024DS(R). |
Adder Modules | |
DM-1008A | Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module. |
SGM-1004A | Four Class A/B (Style Z/Y) Notification Appliance Circuit Module (Rated at 1.7 Amps per circuit). |
RM-1008A | Eight Relay Circuit Module c/w eight Form C relays (Rated for 28 VDC @ 1 Amp max. per relay). |
Auxiliary Modules | |
UDACT-300A | Digital Alarm Communication Transmitter/Dialer Module. |
PR-300 | Polarity Reversal and City Tie Module. |
Enclosures | |
UB-1024DS | Universal black backbox. Requires DOX-1024DS(R) door. |
DOX-1024DS | White door for UB-1024DS backbox. |
DOX-1024DSR | Red door for UB-1024DS backbox. |
BBX-1024XT | Enclosure for MCC-1024-12XTDS c/w removable white door, black backbox and CAT-30 lock and key. |
BBX-1024XTR | Enclosure for MCC-1024-12XTDS c/w removable red door, black backbox and CAT-30 lock and key. |
FA-XT-TRB | Black Semi-Flush Trim Ring for BBX-1024XT(R) enclosure. |
Remote Annunciators | |
RAM-1032TZDS | Main Remote LED Annunciator c/w 32 Bi-Colored LEDs and 32 Trouble LEDs. |
RAM-1016TZDS | Main Remote LED Annunciator c/w 16 Bi-Colored LEDs and 16 Trouble LEDs. |
RAX-1048TZDS | Programmable LED Annunciator Module c/w 48 Bi-Coloured LEDs and 48 Trouble LEDs. |
BB-1001 | Remote Enclosure. Houses one module. Add suffix "R" for red door. |
BB-1002 | Remote Enclosure. Houses two modules. Add suffix "R" for red door. |
BB-1003 | Remote Enclosure. Houses three modules. Add suffix "R" for red door. |
BB-1008 | Remote Enclosure. Houses eight modules. Add suffix "R" for red door. |
BB-1012 | Remote Enclosure. Houses twelve modules. Add suffix "R" for red door. |