Aurora LumiCS LED Downlight Installation Guide

Model Series: AU-DDLH412CS, AU-DDLH618CS, AU-DDLH818CS, AU-DDLH825CS, AU-DDLH835CS

Important Installation Information

  • Installation must be performed by a qualified electrician in accordance with the latest national wiring regulations.
  • Mains supply voltage: 200-240V AC 50Hz.
  • For indoor use only.
  • Ensure all electrical connections are tight with no loose strands.
  • Class II, Double Insulated: Earth connection is not required.
  • This luminaire is not suitable for covering with insulation material.
  • IP54 rated: Protected against splashing water from all directions when correctly installed. Suitable for installation in locations containing a bath or shower, as defined by the National Wiring Regulations, Zones 1 & 2, EXCEPT where water jets are likely.
  • The light source of this luminaire is not replaceable; when the light source reaches its end of life, the whole luminaire shall be replaced.
  • Aurora Lighting does not recommend mixing LED circuits with products such as extractor fans due to the sensitive nature of LEDs. This is not product specific.
  • Compatibility with PIR sensors may vary; please contact Aurora Lighting sales for compatibility information.
  • Energy efficiency classes: E (AU-DDLH412CS, AU-DDLH818CS, AU-DDLH835CS), D (AU-DDLH618CS, AU-DDLH825CS).

Installation Steps

Step 1: Preparation

Ensure the luminaire's integrated switch is set to the 'OFF' position before commencing installation.

Visual: A switch on the luminaire with 'ON' and 'OFF' positions. The switch should be set to 'OFF'.

Step 2: Ceiling Cutout Dimensions

Refer to the following dimensions for correct ceiling cutout diameter (Ø) and minimum ceiling thickness (t):

  • AU-DDLH412CS: Ø 120-130mm
  • AU-DDLH618CS: Ø 160-170mm
  • AU-DDLH818CS: Ø 200-210mm
  • AU-DDLH825CS: Ø 200-210mm
  • AU-DDLH835CS: Ø 200-210mm
  • Minimum ceiling thickness (t): ≥ 10mm
Visual: Diagram indicating minimum ceiling thickness (t ≥ 10mm) and required cutout diameter (Ø) for specific Aurora LumiCS downlight models.

Step 3: Clearance and Connections

Ensure adequate clearance around the luminaire for ventilation and installation:

  • Minimum void depth: 80mm
  • Minimum side clearance: 25mm

The luminaire connects to a 240V Mains Input via its LED Driver.

Visual: Clearance requirements showing minimum void depth (80mm) and side clearance (25mm). A connection diagram illustrates the 240V mains input feeding into the LED driver.

Step 4: Colour Temperature Selection

Adjust the colour temperature of the downlight using the integrated selection slider. Options available are 3000K (Warm White), 4000K (Cool White), and 6500K (Daylight).

Visual: The luminaire features a slider that allows users to select the desired colour temperature from 3000K, 4000K, or 6500K.

Step 5: Wiring Connections

Connect the mains supply wires to the appropriate terminals on the LED driver:

  • Connect the Brown wire (Live) to the 'L' terminal.
  • Connect the Blue wire (Neutral) to the 'N' terminal.
Visual: Wiring terminals labelled N (Neutral) and L (Live). The Brown wire is shown connecting to the Live terminal, and the Blue wire to the Neutral terminal.

Step 6: Secure Wire Termination

Ensure all wires are securely inserted and terminated into their respective terminals.

Visual: A close-up view of electrical wires being properly inserted and secured into the luminaire's connection terminals.

Step 7: Luminaire Installation

Carefully insert the luminaire into the prepared ceiling cutout, ensuring it fits snugly.

Visual: The Aurora LumiCS downlight is shown being gently pushed into the pre-cut hole in the ceiling.

Step 8: Final Check

Once installed, set the luminaire's integrated switch to the 'ON' position to confirm operation.

Visual: The luminaire's switch is now shown in the 'ON' position, indicating the downlight is operational.

Compliance and Warranty

This product complies with relevant safety and environmental standards. It is marked with the CE and UKCA symbols, indicating conformity. As per WEEE regulations, this product should not be disposed of with general household waste. Please refer to Aurora Lighting for specific warranty terms.

Models: AU-DDLH412CS, AU-DDLH618CS, AU-DDLH818CS, AU-DDLH825CS, AU-DDLH835CS, AU-DDLH412CS Lumics 12W Colour Switchable Dimmable Downlight, Lumics 12W Colour Switchable Dimmable Downlight, 12W Colour Switchable Dimmable Downlight, Colour Switchable Dimmable Downlight, Switchable Dimmable Downlight, Dimmable Downlight, Downlight

PDF preview unavailable. Download the PDF instead.

366379 ?ts=1700265781584 Adobe InDesign 16.2 (Macintosh) Adobe PDF Library 15.0

Related Documents

Preview Aurora AU-ADFRC Installation Guide: Standard and GU10 Versions
Comprehensive installation instructions for Aurora AU-ADFRC downlights, covering both Standard (AU-ADSTxxxx) and GU10 (AU-ADGUSTxxxx) models. Includes essential safety, environmental, and warranty information.
Preview Aurora GLS LED Lamp Declaration of Conformity
Official Declaration of Conformity for Aurora GLS LED Lamps, confirming compliance with key EU directives (LVD, EMC, RoHS, WEEE, RED) and relevant harmonized standards.
Preview Aurora AU-R6CWSBF LED Downlight: Installation Guide and Specifications
This document provides installation instructions for the Aurora AU-R6CWSBF LED downlight. It details safety precautions, wiring, wattage and colour temperature selection, and environmental disposal information. Ensure proper installation by a qualified electrician for optimal performance and safety.
Preview Aurora 12V Constant Voltage 16W LED Driver Installation Guide
Installation and safety guide for Aurora 12V Constant Voltage 16W LED Drivers (AU-LED16IP/AU-LED16T). Covers wiring, parallel connections, IP rating, lamp compatibility, and warranty information.
Preview Aurora AU-A1ZBSCD Zigbee 3.0 LED Strip Controller - Technical Guide
Comprehensive guide for the Aurora AU-A1ZBSCD Zigbee 3.0 LED strip controller, covering specifications, important safety information, app connectivity, installation guidelines, EU declaration, WEEE compliance, and warranty.
Preview Aurora AU-DSPLED 1-10V Dimmer Switch Installation and Wiring Guide
Comprehensive installation instructions and wiring diagrams for the Aurora AU-DSPLED 1-10V Dimmer Switch. Learn how to install and connect this rotary control dimmer for dimmable LED drivers and ballasts in 1-way and 2-way lighting circuits.
Preview Aurora Spryte LED Downlight Installation and Safety Guide
Comprehensive guide for installing Aurora Spryte LED downlights, including safety precautions, electrical connections, dimming compatibility, and warranty information. Covers models EN-DL10160, DDL10160, DDL10260, and DDL1019.
Preview Aurora Lumi-Fit Fixed LED Downlight Installation Manual
Comprehensive installation and user guide for the Aurora Lumi-Fit Fixed LED Downlight (25W, 2600lm). Covers safety precautions, technical specifications, step-by-step installation, maintenance, and warranty information.