R. STAHL 8530/1-MCB-STA102-C25-500-3 Circuit Breaker
Article No.: 267212
Product Overview
The R. STAHL 8530 series circuit breakers offer excellent current limitation in case of short circuits and high breaking capacities of 10, 15, or 25 kA. This results in reduced stress on electrical lines and high selectivity with respect to upstream fuses. The modules are designed with a modular structure, available in 1 to 4 pole versions, and for nominal currents from 0.5–63 A. The maximum mounting width is 4.5 division units.
Key features include:
- Switch disconnector according to EN 60947-2
- Energy limitation class 3
- Simple replacement or expansion of installations thanks to the modular design of the protection switch.
- Easy mounting by clipping onto a DIN mounting rail in Ex e enclosures.
- Thermally and magnetically tripped with fixed settings.
- Ergonomic operating lever ensures safe connection and disconnection.
- Protection against reconnection during maintenance using padlocks (accessories).
Model: MY R. STAHL 8530A Certifications: Ex
Technical Data
Explosion Protection
Applications (zones) | Applications (zones) Note | IECEX gas | IECEx Protection against gas explosions | ATEX gas | ATEX protection against gas explosions |
---|---|---|---|---|---|
1, 2 | Can be used in zones 21/22 with Ex tb/tc enclosure protection | IECEX FMG 19.0029U | Ex db eb IIC Gb | FM19ATEX0191U | II 2 G Ex db eb IIC Gb |
Certifications
- Certifications: ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
- Certificate of conformity: Certificate of conformity (ATEX), China (CCC)
Electrical Data
Rated operating voltage AC | Rated operating current | Frequency | Rated switching capacity | Electrical service life | Mechanical service life |
---|---|---|---|---|---|
230/400 V | 25 A | 50/60 Hz | 10 kA | 2 x 104 | 2 x 104 |
Auxiliary Functions
1st auxiliary function | Voltage 1st auxiliary function AC | Max. current 1st auxiliary function | 2nd auxiliary function | Max. voltage 2nd aux. function CC |
---|---|---|---|---|
Auxiliary contact 1 changeover + Signal contact 1 changeover | 230 V | 2 A | (none) | (none) |
Tripping Characteristic
Tripping characteristic: C
Number of poles
Number of poles: 2-pole
Environmental Conditions
Ambient temperature | Ambient temperature | Ambient temperature | Ambient temperature | Ambient temperature Note |
---|---|---|---|---|
-40 °C ... 70 °C | -40 °C ... 70 °C | -40 °F ... 158 °F | -40°F ... +158°F | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | Enclosure material | Minimum connection cross-section | Maximum connection cross-section | Minimum AWG connection cross-section | Maximum AWG connection cross-section | Minimum connection cross-section 2 | Maximum connection cross-section 2 | Minimum AWG connection cross-section 2 | Maximum AWG connection cross-section 2 | Minimum HIKO connection cross-section | Maximum HIKO connection cross-section | Minimum HIKO AWG connection cross-section | Maximum HIKO AWG connection cross-section |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
IP2X | Thermoplastic | 1.5 mm² | 25 mm² | 16 AWG | 4 AWG | 1.5 mm² | 10 mm² | 16 AWG | 8 AWG | 0.5 mm² | 4 mm² | 18 (unece.unit.AWG) | 14 (unece.unit.AWG) |
Torque Settings
Minimum tightening torque | Maximum tightening torque | Note on connection cross-section |
---|---|---|
2 N·m | 3 N·m | 2 conductor connections (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (only one cross-section difference of the upper and lower chamber can be wired). Permitted connection cross-section combinations are listed in the operating instructions. |
Dimensions
Width | Mounting width in inches | Length | Length in inches | Installation depth | Installation depth in inches | Weight | Weight |
---|---|---|---|---|---|---|---|
83 mm | 3.27 in | 165 mm | 6.5 in | 138.3 mm | 5.44 in | 1.3 kg | 2.867 lb |
Mounting / Installation
Tightening torque | Tightening torque lbf in | Tightening torque auxiliary contact | Tightening torque auxiliary contact lbf in |
---|---|---|---|
2–3 N·m | 17.7 ... 26.6 lbf-in | 0.4–0.6 Nm | 3.5 ... 5.3 lbf in |
Technical Diagrams
Characteristic Curve: The document includes a tripping characteristic curve showing the relationship between multiples of the rated current (I/In) and time in seconds/minutes for different tripping characteristics (e.g., C). This curve illustrates the time delay before the circuit breaker trips under various overload conditions.
Dimensional Drawings: Detailed drawings show the physical dimensions of the circuit breaker, including width, height, depth, and mounting dimensions, with measurements provided in both millimeters and inches. These diagrams are crucial for installation planning and ensuring compatibility with existing systems.
Accessories
Cylinder Lock
Description: Padlock for individual component locking (up to Ø 3 mm shackle).
Article No.: 107115
Quadruple Immobilization Device
Description: Lockout/tagout tongs for individual component locking using up to 4 cylinder locks.
Article No.: 227232
Fixing Kit
Description: A set of fixings for mounting the component onto a mounting plate without a top hat rail.
Article No.: 276618