Components for system solutions
MCB Miniature circuit breaker
Model: 8530/1-MCB-STA102-C25-500-3 | Art. No.: 267212
Key Features
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Modular design for simple replacement or expansion
- Easy installation: snaps onto the mounting rail in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe operation
- Padlocks (Accessories) for protection against being switched on during maintenance
Product Overview
R. STAHL 8530 series miniature circuit breakers are overcurrent devices offering excellent current limiting for short circuits and high switching capacity (10, 15, or 25 kA). They reduce load on cables and provide high selectivity for upstream fuses. These components feature a modular design and are available in 1- to 4-pole versions for rated currents of 0.5-63 A. The maximum installation capacity is 4.5 subunits.
Technical Data
Explosion Protection
- Application range (zones): 1, 2
- Application range (Zone) note: For use in Zone 21/22 when protected by Ex tb/tc enclosure
- IECEx gas certificate: IECEx FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- ATEX gas certificate: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certificates: ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
- Declaration of conformity: Certificate of conformity (ATEX), China (CCC)
Electrical Data
Rated operational voltage AC | 230/400 V |
Rated operational current | 25 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | Auxiliary contact 1 change-over contact + fault signal contact 1 change-over contact |
1st auxiliary function for AC rated voltage | 230 V |
1st auxiliary function for rated current max. | 2 A |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | C |
No. of poles | 2-pole |
Ambient Conditions
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature note | Deviating ambient temperatures based on current certificates available on request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplast |
Connection cross section min. | 1.5 mm² |
Connection cross-section max. | 25 mm² |
Connection cross-section AWG min. | 16 AWG |
Connection cross-section AWG max. | 4 AWG |
Connection cross-section 2 min. | 1.5 mm² |
Connection cross-section 2 max. | 10 mm² |
Connection cross-section 2 AWG min. | 16 AWG |
Connection cross-section 2 AWG max. | 8 AWG |
Min. aux. cont. con. cr.-sect. | 0.5 mm² |
Max. aux. cont. conn. cr.-sec. | 4 mm² |
Min. aux. co. con. cr.-se. AWG | 18 (unece.unit.AWG) |
Connection cross-section of auxiliary contact AWG max. | 14 (unece.unit.AWG) |
Min. tightening torque | 2 N·m |
Max. tightening torque | 3 N·m |
Connection cross-section note | 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16 / 10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) The permitted combinations of connection cross-sections can be found in the operating instructions. |
Dimensions
Width | 83 mm |
Width, inches | 3.27 in |
Length | 165 mm |
Length in inches | 6.5 in |
Mounting depth | 138.3 mm |
Mounting depth in inches | 5.44 in |
Weight | 1.3 kg |
Weight | 2.867 lb |
Mounting / Installation
Tightening torque | 2–3 N·m |
Tightening torque lbf·in | 17.7 to 26.6 lbf·in |
Tightening torque auxiliary contact | 0.4–0.6 N·m |
Tightening torque auxiliary contact lbf·in | 3.5 to 5.3 lbf·in |
Technical Drawings
Tripping Characteristic C:
Diagram showing tripping time in seconds and minutes versus multiple of rated current for tripping characteristic C for AC and DC.
Dimensional Drawings:
Diagrams illustrating the dimensions of the circuit breaker in mm and inches, including width, length, and mounting depth.
Circuitry Diagram:
Diagram showing the 2-pole configuration with auxiliary contacts and fault signal contacts.
Accessories
4-way locking device
A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks.
- Art. No.: 227232
Cylinder lock
- for closing (bracket Ø 3)
- Art. No.: 107115
Fastening set
A fastening set for fastening the component on the mounting plate without a DIN rail.
- Art. No.: 276618
R. STAHL Schaltgeräte GmbH reserves the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.