Submittal Data Sheet: Air Handler Heat Pump System
General Information
Location: [Not Specified]
Engineer: [Not Specified]
Submitted to: [Not Specified]
Submitted by: [Not Specified]
Reference: [Not Specified]
Approval: [Not Specified]
Date: [Not Specified]
Construction: [Not Specified]
Unit #: [Not Specified]
Drawing #: [Not Specified]
Efficiency Ratings
Rating | Value | Rating | Value |
---|---|---|---|
SEER2 | 16.0 | HSPF2-4 | 10.0 |
EER2 | 10.0 | COP | 3.37 |
Performance of Cooling
Metric | Value |
---|---|
Rated Capacity (Btu/hr) | 29,000 |
Min/Max Capacity (Btu/hr) | 13,900~37,900 |
Moisture Removal (L/h) | 3.7 |
Standard Operating Range (°F/°C) | -22~122 (-30~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
Condition | Value (Btu/hr) |
---|---|
1. @ 47°F Rated | 32,000 |
2. @ 47°F Min/Max Capacity | 13,000~40,000 |
3. @ 17°F Rated | 25,000 |
4. @ 5°F Rated: Capacity / COP | 33,000 / 1.9 |
5. @ 5°F Max: Capacity | 33,000 |
Standard Operating Range (°F/°C) | -22~75 (-30~24) |
1. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Indoor Unit Specifications
Specification | Value (inch) | Value (mm) |
---|---|---|
Dimension (W×D×H) | 17-1/2 x 21 x 23-1/2 | 445 x 533 x 599 |
Package Dimension (W×D×H) | 20-1/2 x 26-1/8 x 26-3/8 | 520 x 665 x 670 |
Net/Gross Weight | 59.5 lbs / 27 kg | 68 lbs / 30.9 kg |
Outdoor Unit Specifications
Specification | Value |
---|---|
Compressor Type | ROTARY |
Compressor Model | MTH356UKRC8FQL |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1300 |
Refrigerant Oil | HAF68D1A |
Outdoor Air Flow (Max) (CFM) | 3,002 |
Outdoor Noise Level (dBA) | 64 |
Dimension (W×D×H) | 37-1/4 x 16-1/8 x 31-7/8 inch (946 x 410 x 810 mm) |
Package Dimension (W×D×H) | 42-7/8 x 19-5/8 x 34-7/8 inch (1090 x 500 x 885 mm) |
Net/Gross Weight | 164 lbs / 74.4 kg |
175 lbs / 79.2 kg |
Electrical Specifications
Specification | Value |
---|---|
Indoor Power Supply | 24V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | / |
Indoor MOP | / |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 29.5 A |
Outdoor MOP | 30 A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 22.4 A |
Outdoor Fan Motor RLA | 1.5 A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | / |
Indoor Fan Motor W | / |
System Power Input @ Cooling (W) | 2900 (1,160 ~ 3,740) |
System Power Input @ Heating (W) | 2780 (1,088 ~ 3,482) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping Specifications
Specification | Value |
---|---|
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 164 ft (50 m) |
Max. Height Difference (ft/m) | 82 ft (25 m) |
Max. Pre-charged Length (ft) | 25 ft |
Refrigerant Pre-charged Amount (oz/kg) | 105.82 (3) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared |
Indoor Unit Dimensional Drawings
The indoor unit dimensions are illustrated with labels A through F corresponding to specific measurements. The diagram shows the unit from the front and side, indicating connection points for refrigerant lines, drain, and power.
Dimension Label | Description | Model MVBM-24B18T3N10 (inch/mm) | Model MVBM-24A18T3N10 (inch/mm) | Model MVBM-36A24T4N10 (inch/mm) | Model MVBM-36B24T4N10 (inch/mm) | Model MVBM-36C24T4N10 (inch/mm) | Model MVBM-60D28T6N10 (inch/mm) |
---|---|---|---|---|---|---|---|
A | Model Height | 18 / 457 | 18 / 457 | 23-5/16 / 592 | 23-9/16 / 599 | 24 / 611 | 28 / 711 |
B | Model Width | 17-1/2 / 445 | 14-1/2 / 368 | 14-1/2 / 368 | 17-1/2 / 445 | 21 / 534 | 24-1/2 / 622 |
C | Supply Air Opening Width | 16-3/16 / 411 | 13-1/4 / 336 | 13-1/4 / 336 | 16-3/16 / 411 | 19-3/4 / 502 | 23-1/4 / 591 |
D | Return Air Opening Width | 14-15/16 / 380 | 11-15/16 / 303 | 11-15/16 / 303 | 14-15/16 / 380 | 19-1/2 / 498 | 23-1/8 / 587 |
E | Condensate Drains Height | 1-7/16 / 38 | 1-7/16 / 38 | 1-7/16 / 38 | 1-7/16 / 38 | 2-3/16 / 55 | 2-3/16 / 55 |
F | Liquid Line Height | 11-3/8 / 290 | 11-3/8 / 290 | 17-15/16 / 455 | 16-3/8 / 417 | 17-1/2 / 445 | 21-7/16 / 545 |
Outdoor Unit Dimensional Drawings
The outdoor unit dimensions are provided, showing the unit's width, depth, and height in both inches and millimeters. The diagram displays the unit from the front, side, and top views, highlighting key measurements.
Overall Dimensions (approximate): Width: 40-1/2 inches (1030 mm), Depth: 16-1/8 inches (410 mm), Height: 31-7/8 inches (810 mm).
Outdoor Unit Installation Clearance Requirements
The installation instructions specify required clearances around the outdoor unit for proper operation and maintenance. These clearances are indicated by arrows in a diagram:
- Front and Sides: 20 inches (500 mm) or more when front and sides of the unit are clear.
- Left, Right, and Rear: 20 inches (500 mm) or more when any 2 sides of left, right, and rear of the unit are clear.
- Sides: 4 inches (100 mm) or more.
- Rear: 14 inches (350 mm) or more.
The document confirms: "Meets all spatial requirements shown in Installation Clearance Requirements above."
Features
- Multi-position installation: horizontal (left or right), vertical (up or down).
- Aluminum Coil.
- R454B refrigerant sensor.
- Easy Maintenance.
- Multiple control options available:
- Two-way communication wired controller with built-in WiFi: 120N(X6W).
- Third-Party 24V Thermostat.