Blueridge XL1 CDH Slim Duct Regular System Submittal Data Sheet
System Overview
This document provides the submittal data sheet for the Blueridge Slim Duct Regular System, model series XL1 CDH. It details the system's specifications, performance characteristics, electrical requirements, and installation guidelines.
Efficiency Ratings
Metric | Cooling | Heating |
---|---|---|
SEER2 | 17.0 | HSPF2-4: 9.7 |
EER2 | 10.0 | COP: 3.70 |
Performance of Cooling
Cooling (Btu/hr)
- Rated Capacity: 58000
- Min/Max Capacity: 14600~63000
- Moisture Removal (L/h): 5.24
- Standard Operating Range (°F/°C): -13~122 (-25~50)
Conditions:
- Indoor: 80°F DB / 67°F WB
- Outdoor: 95°F DB / 75°F WB
Performance of Heating
Heating (Btu/hr)
- 1. @ 47°F Rated Capacity: 60000
- 1. @ 47°F Min/Max Capacity: 11800~67000
- 2. @ 17°F Rated Capacity: 40000
- 3. @ 5°F Rated Capacity / COP: 40000 / 2.20
- 3. @ 5°F Max Capacity: 40000
- Standard Operating Range (°F/°C): -13~75 (-25~24)
Conditions:
- Indoor: 70°F DB / 60°F WB; Outdoor: 47°F DB / 43°F WB
- Indoor: 70°F DB / 60°F WB; Outdoor: 17°F DB / 15°F WB
- Indoor: 70°F DB / 60°F WB; Outdoor: 5°F DB / 5°F WB
Indoor Unit Specifications
Specification | Value |
---|---|
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 2001.2 / 1706.9 / 1412.6 / 1118.3 / N/A |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | N/A / 52 / 48 / 43 / 42 |
Indoor static pressure range (in.w.g.) | 0-0.8 |
Dimension (W×D×H) (inch) | 55.12 x 31.50 x 14.96 |
Dimension (W×D×H) (mm) | 1400.0×800.0×380.0 |
Package Dimension (W×D×H) (inch) | 62.99 x 36.02 x 17.52 |
Package Dimension (W×D×H) (mm) | 1600×915×445 |
Net/Gross Weight (lbs) | 161.38 / 178.13 |
Net/Gross Weight (kg) | 73.2 / 80.8 |
Outdoor Unit Specifications
Specification | Value |
---|---|
Compressor Type | ROTARY |
Compressor Model | KTQ420D1UMU |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1400 |
Refrigerant Oil | 7.0 |
Outdoor Air Flow (Max) (CFM) | 4237.9 |
Outdoor Noise Level (dBA) | 64.0 |
Dimension (W×D×H) (inch) | 37.48 x 16.34 x 52.48 |
Dimension (W×D×H) (mm) | 952.0×415.0×1333.0 |
Package Dimension (W×D×H) (inch) | 43.11 x 19.49 x 58.27 |
Package Dimension (W×D×H) (mm) | 1095×495×1480 |
Net/Gross Weight (lbs) | 209.44 / 240.08 |
Net/Gross Weight (kg) | 95 / 108.9 |
Electrical Specifications
Specification | Value |
---|---|
Power Supply | 208/230V, 60Hz, 1Ph |
System MCA (A) | 42.00 |
Connection Wiring | 14#x3 |
System MOCP (A) | 45 |
Compressor RLA (A) | 25.0 |
Outdoor Fan Motor RLA (A) | 2.2 |
Outdoor Fan Motor W (HP) | 85 |
Indoor Fan Motor RLA (A) | 4.0 |
Indoor Fan Motor W (HP) | 560 |
System Power Input @ Cooling (W) | 5800 (1200 ~ 6780) |
System Power Input @ Heating (W) | 4750 (775 ~ 5170) |
Piping Specifications
Specification | Value |
---|---|
Throttle type (Indoor) | N/A |
Throttle type (Outdoor) | EXV + Throttle valve |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 246.00 (75) |
Max. Height Difference (ft/m) | 98.40 (30) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 144.62 (4.10) |
Additional Charge of Refrigerant (oz/ft) / (g/m) | 0.32 (30) |
Connection Method | Flared |
Indoor Unit Dimensions and Installation
Indoor Unit Dimensions
Technical drawings show the indoor unit's dimensions and connection points. The unit features four hanging brackets at the top. Key connection points include the drain pipe (25mm diameter) and the electric control box. Pipe connections are labeled as liquid side and gas side.
Model | A (in/mm) | B (in/mm) | C (in/mm) | D (in/mm) |
---|---|---|---|---|
9K | 27-1/2in (700mm) | 7-7/8in (200mm) | 17-3/4in (450mm) | 20in (506mm) |
12K | 27-1/2in (700mm) | 9-5/8in (245mm) | 29-1/2in (750mm) | 31-1/4in (795mm) |
18K~24K | 39-3/8in (1000mm) | 9-5/8in (245mm) | 29-1/2in (750mm) | 31-1/4in (795mm) |
36K~48K | 47-1/8in (1200mm) | 11-7/8in (300mm) | 29-1/2in (750mm) | 31-1/4in (795mm) |
60K | 55-1/8in (1400mm) | 15in (380mm) | 31-1/2in (800mm) | 33-1/4in (845mm) |
Indoor Unit Installation Instructions
The distance between the mounted indoor unit and surrounding structures must meet the specifications illustrated in the diagrams:
1) Ceiling-mounted
- Clearance from left side: >90.6in (230cm)
- Clearance from right side: >7.9in (20cm)
- Clearance for service access: >11.8in (30cm)
- Clearance from floor: >15.7in (40cm)
- Clearance from ceiling: >0.8in (2cm)
2) Wall-mounted
The unit should be mounted at a height between 23.6in (60cm) and 70.9in (180cm) from the floor, with a minimum clearance of 11.8in (30cm) from the floor.
Outdoor Unit Dimensions and Installation
Outdoor Unit Dimensions
Technical drawings provide the external dimensions of the outdoor unit. Detail A shows a close-up of a connection point. The unit has dimensions W×D×H of 37.48 x 16.34 x 52.48 inches (952.0×415.0×1333.0 mm).
Outdoor Unit Required Clearance
Proper clearance around the outdoor unit is essential for optimal performance and maintenance. The following minimum clearances are recommended:
- Front: 20 inches (500mm) or more when front and sides are clear.
- Sides (Left/Right): 4 inches (100mm) or more.
- Rear: 14 inches (350mm) or more.
- When any 2 sides (left, right, and rear) are clear, the front clearance should be 20 inches (500mm) or more, and the other sides require 4 inches (100mm) or more.
Fan Performance
The following graphs illustrate the fan performance characteristics, showing Air Volume (CFM) versus External Static Pressure (in.WC) for different fan speed settings (SH, H, M, L) across various models (SP1-SP8) and a general constant air volume scenario.
SP1 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
SP2 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
SP3 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
SP4 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
SP5 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
SP6 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
SP7 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
SP8 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.
Constant Air Volume Fan Performance: A graph plotting Air Volume (CFM) against External Static Pressure (in.WC), showing performance across different fan speed settings (SH, H, M, L).
Features
- Compatible with both horizontal and vertical installation.
- Static pressure capability up to 0.8 in.w.g. (for all models).
- Static pressure setting stages: 8.
- Refrigerant leakage detection sensor.
- Constant airflow.
- Built-in pump.
- i-clean function.
- Fan speed stages: 1~100%.
- WiFi capability: Available through a wired controller with built-in WiFi.
- OTA updates: Supported via the wired controller 120N(X6W).
- Control Options:
- 2-pin connector (HA/HB) for programmable wired controller.
- Multiple control options available:
- Two-way communication wired controller: 120N(X6).
- Two-way communication wired controller with built-in WiFi: 120N(X6W).
- Infrared wired controller: 120L.
- Wireless remote controller.
- Third-Party 24V Thermostat* (requires 24V interface).