System Overview

This document provides the submittal data sheet for the Blueridge Slim Duct Regular System, model series XL1 CDH. It details the system's specifications, performance characteristics, electrical requirements, and installation guidelines.

Efficiency Ratings

Metric Cooling Heating
SEER2 17.0 HSPF2-4: 9.7
EER2 10.0 COP: 3.70

Performance of Cooling

Cooling (Btu/hr)

Conditions:

Performance of Heating

Heating (Btu/hr)

Conditions:

  1. Indoor: 70°F DB / 60°F WB; Outdoor: 47°F DB / 43°F WB
  2. Indoor: 70°F DB / 60°F WB; Outdoor: 17°F DB / 15°F WB
  3. Indoor: 70°F DB / 60°F WB; Outdoor: 5°F DB / 5°F WB

Indoor Unit Specifications

Specification Value
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) 2001.2 / 1706.9 / 1412.6 / 1118.3 / N/A
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) N/A / 52 / 48 / 43 / 42
Indoor static pressure range (in.w.g.) 0-0.8
Dimension (W×D×H) (inch) 55.12 x 31.50 x 14.96
Dimension (W×D×H) (mm) 1400.0×800.0×380.0
Package Dimension (W×D×H) (inch) 62.99 x 36.02 x 17.52
Package Dimension (W×D×H) (mm) 1600×915×445
Net/Gross Weight (lbs) 161.38 / 178.13
Net/Gross Weight (kg) 73.2 / 80.8

Outdoor Unit Specifications

Specification Value
Compressor Type ROTARY
Compressor Model KTQ420D1UMU
Refrigerant R454B
Refrigerant Oil Charge (mL) 1400
Refrigerant Oil 7.0
Outdoor Air Flow (Max) (CFM) 4237.9
Outdoor Noise Level (dBA) 64.0
Dimension (W×D×H) (inch) 37.48 x 16.34 x 52.48
Dimension (W×D×H) (mm) 952.0×415.0×1333.0
Package Dimension (W×D×H) (inch) 43.11 x 19.49 x 58.27
Package Dimension (W×D×H) (mm) 1095×495×1480
Net/Gross Weight (lbs) 209.44 / 240.08
Net/Gross Weight (kg) 95 / 108.9

Electrical Specifications

Specification Value
Power Supply 208/230V, 60Hz, 1Ph
System MCA (A) 42.00
Connection Wiring 14#x3
System MOCP (A) 45
Compressor RLA (A) 25.0
Outdoor Fan Motor RLA (A) 2.2
Outdoor Fan Motor W (HP) 85
Indoor Fan Motor RLA (A) 4.0
Indoor Fan Motor W (HP) 560
System Power Input @ Cooling (W) 5800 (1200 ~ 6780)
System Power Input @ Heating (W) 4750 (775 ~ 5170)

Piping Specifications

Specification Value
Throttle type (Indoor) N/A
Throttle type (Outdoor) EXV + Throttle valve
Liquid Size 9.52mm (3/8in)
Gas Size 19mm (3/4in)
Max. Piping Length (ft/m) 246.00 (75)
Max. Height Difference (ft/m) 98.40 (30)
Max. Pre-charged Length (ft/m) 24.6 (7.5)
Refrigerant Pre-charged Amount (oz/kg) 144.62 (4.10)
Additional Charge of Refrigerant (oz/ft) / (g/m) 0.32 (30)
Connection Method Flared

Indoor Unit Dimensions and Installation

Indoor Unit Dimensions

Technical drawings show the indoor unit's dimensions and connection points. The unit features four hanging brackets at the top. Key connection points include the drain pipe (25mm diameter) and the electric control box. Pipe connections are labeled as liquid side and gas side.

Model A (in/mm) B (in/mm) C (in/mm) D (in/mm)
9K 27-1/2in (700mm) 7-7/8in (200mm) 17-3/4in (450mm) 20in (506mm)
12K 27-1/2in (700mm) 9-5/8in (245mm) 29-1/2in (750mm) 31-1/4in (795mm)
18K~24K 39-3/8in (1000mm) 9-5/8in (245mm) 29-1/2in (750mm) 31-1/4in (795mm)
36K~48K 47-1/8in (1200mm) 11-7/8in (300mm) 29-1/2in (750mm) 31-1/4in (795mm)
60K 55-1/8in (1400mm) 15in (380mm) 31-1/2in (800mm) 33-1/4in (845mm)

Indoor Unit Installation Instructions

The distance between the mounted indoor unit and surrounding structures must meet the specifications illustrated in the diagrams:

1) Ceiling-mounted

2) Wall-mounted

The unit should be mounted at a height between 23.6in (60cm) and 70.9in (180cm) from the floor, with a minimum clearance of 11.8in (30cm) from the floor.

Outdoor Unit Dimensions and Installation

Outdoor Unit Dimensions

Technical drawings provide the external dimensions of the outdoor unit. Detail A shows a close-up of a connection point. The unit has dimensions W×D×H of 37.48 x 16.34 x 52.48 inches (952.0×415.0×1333.0 mm).

Outdoor Unit Required Clearance

Proper clearance around the outdoor unit is essential for optimal performance and maintenance. The following minimum clearances are recommended:

Fan Performance

The following graphs illustrate the fan performance characteristics, showing Air Volume (CFM) versus External Static Pressure (in.WC) for different fan speed settings (SH, H, M, L) across various models (SP1-SP8) and a general constant air volume scenario.

SP1 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

SP2 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

SP3 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

SP4 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

SP5 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

SP6 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

SP7 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

SP8 Fan Performance: Air Volume (CFM) plotted against External Static Pressure (in.WC). Lines for SH, H, M, L speeds are shown.

Constant Air Volume Fan Performance: A graph plotting Air Volume (CFM) against External Static Pressure (in.WC), showing performance across different fan speed settings (SH, H, M, L).

Features

Models: 120N X6W, 120L, BMY18HH20CD Slim Duct Regular System, BMY18HH20CD, Slim Duct Regular System, Duct Regular System, Regular System, System

PDF preview unavailable. Download the PDF instead.

blueridgebxl1a60sc0-60cdhspecificationssheet 345F0651-2A24-4A31-BBE9-39DBAF658731 Google Sheets

Related Documents

Preview Blueridge XS2+Entry High Wall Heat Pump System - 21 SEER2 Submittal Data Sheet
Comprehensive submittal data sheet for the Blueridge XS2+Entry high wall heat pump system, detailing efficiency ratings (21 SEER2), performance specifications for cooling and heating, electrical requirements, piping details, and key features. Includes indoor and outdoor unit dimensions and installation clearance guidelines.
Preview Blueridge BM18MCD Duct Heat Pump Air Handler Submittal Data Sheet
Technical specifications and dimensions for the Blueridge BM18MCD Duct Heat Pump Air Handler indoor unit, including airflow, noise levels, and physical measurements.
Preview Blueridge 19 SEER Single Zone Ductless Mini-Split Specifications | BM09Y18, BM12Y19, BM18Y19, BM24Y17
Detailed specifications for Blueridge Standard Single Zone 19 SEER Ductless Mini-Split systems, covering model numbers, cooling and heating capacities, operating temperatures, dimensions, electrical requirements, and component details.
Preview Blueridge BMKH09M-LM Split-type Inverter Technical Specifications | Indoor Unit Details
Detailed technical specifications for the Blueridge BMKH09M-LM split-type inverter indoor unit. This document outlines key parameters including model number, fan specifications, evaporator details, motor specifications, temperature ranges, dimensions, and weight.
Preview Blueridge Standard Single Zone Ductless Mini-Split HVAC Specifications
Detailed specifications sheet for Blueridge Standard Single Zone Ductless Mini-Split HVAC systems, covering models BM09Y17 to BM36Y16, including capacity, dimensions, electrical, refrigerant, and performance data.
Preview Blueridge BMKH1824 Series Mini-Split Heat Pump: Specifications, Ratings, and Certifications
Detailed specifications, performance data, what's in the box, and certifications for the Blueridge BMKH1824 series mini-split heat pump systems. Includes AHRI and ENERGY STAR ratings, unit dimensions, and installation clearances.
Preview Blueridge XS5 CC 4-Way Cassette Heat Pump System Submittal Data Sheet
Comprehensive submittal data sheet for the Blueridge XS5 CC 4-Way Cassette Heat Pump System, featuring R454B refrigerant. Includes detailed specifications, performance data for cooling and heating, electrical requirements, piping information, and installation clearance guidelines.
Preview Blueridge BMKH2420LM Series: Specifications and Certifications
Comprehensive technical specifications, performance data, dimensions, and installation clearances for the Blueridge BMKH2420LM series of ductless mini-split heat pump systems.