Schneider Electric TeSys Deca LC1D25 IEC Contactor

Product Data Sheet

Specifications

Product Overview

IEC contactor, TeSys Deca, nonreversing, 25A, 15HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 480VAC 50/60Hz coil, open

Product ID: LC1D25T7

Product availability: Stock - Normally stocked in distribution facility

Main Specifications

Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control, Resistive load
Utilisation category AC-1, AC-3, AC-4, AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz, Power circuit <= 300 V DC
[le] rated operational current 25 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit, 40 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit, 25 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 480 V AC 50/60 Hz

Complementary Specifications

Motor power kW 5.5 kW at 220...230 V AC 50/60 Hz (AC-3), 11 kW at 380...400 V AC 50/60 Hz (AC-3), 11 kW at 415...440 V AC 50/60 Hz (AC-3), 15 kW at 500 V AC 50/60 Hz (AC-3), 15 kW at 660...690 V AC 50/60 Hz (AC-3), 5.5 kW at 400 V AC 50/60 Hz (AC-4), 5.5 kW at 220...230 V AC 50/60 Hz (AC-3e), 11 kW at 380...400 V AC 50/60 Hz (AC-3e), 11 kW at 415...440 V AC 50/60 Hz (AC-3e), 15 kW at 500 V AC 50/60 Hz (AC-3e), 15 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 2 hp at 115 V AC 50/60 Hz for 1 phase motors, 7.5 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 15 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 20 hp at 575/600 V AC 50/60 Hz for 3 phase motors, 7.5 hp at 200/208 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 40 A (at 140 °F (60 °C)) for power circuit, 10 A (at 140 °F (60 °C)) for signalling circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 450 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 450 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 240 A 104 °F (40 °C) - 10 s for power circuit, 380 A 104 °F (40 °C) - 1 s for power circuit, 50 A 104 °F (40 °C) - 10 min for power circuit, 120 A 104 °F (40 °C) - 1 min for power circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1, 63 A gG at <= 690 V coordination type 1 for power circuit, 40 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2 mOhm - Ith 40 A 50 Hz for power circuit
Power dissipation per pole 3.2 W AC-1, 1.25 W AC-3, 1.25 W AC-3e
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1, Power circuit 600 V CSA, Power circuit 600 V UL, Signalling circuit 690 V IEC 60947-1, Signalling circuit 600 V CSA, Signalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 15 Mcycles
Electrical durability 1.65 Mcycles 25 A AC-3 <= 440 V, 1.4 Mcycles 40 A AC-1 <= 440 V, 1.65 Mcycles 25 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40...158 °F (-40...70 °C)): drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40...140 °F (-40...60 °C)): operational AC 50 Hz, 0.85...1.1 Uc (-40...140 °F (-40...60 °C)): operational AC 60 Hz, 1...1.1 Uc (140...158 °F (60...70 °C)): operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)), 70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)), 7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 2...3 W at 50/60 Hz
Operating time 12...22 ms closing, 4...19 ms opening
Maximum operating rate 3600 cyc/h at 60 °C

Connections and Terminals

Connections - terminals Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end, Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end, Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible with cable end, Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end, Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end, Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end, Power circuit: screw clamp terminals 1 0.004...0.02 in² (2.5...10 mm²) - cable stiffness: flexible without cable end, Power circuit: screw clamp terminals 2 0.004...0.02 in² (2.5...10 mm²) - cable stiffness: flexible without cable end, Power circuit: screw clamp terminals 1 0.002...0.02 in² (1...10 mm²) - cable stiffness: flexible with cable end, Power circuit: screw clamp terminals 2 0.002...0.009 in² (1.5...6 mm²) - cable stiffness: flexible with cable end, Power circuit: screw clamp terminals 1 0.002...0.02 in² (1.5...10 mm²) - cable stiffness: solid without cable end, Power circuit: screw clamp terminals 2 0.004...0.02 in² (2.5...10 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm, Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2, Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals flat Ø 6 mm, Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals Philips No 2, Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2, Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1, Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact
Mounting Support Plate, Rail

Environment

Standards CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ, CSA C22.2 No 60947-4-1
Product Certifications UL, CCC, CSA, Marine, UKCA, EAC, CB Scheme
IP degree of protection IP20 front face IEC 60529
Protective treatment TH IEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat, IEC 60947-1 Annex Q category D exposure to damp heat

Dimensions and Weight

Permissible ambient air temperature around the device -40...140 °F (-40...60 °C), 140...158 °F (60...70 °C) with derating
Operating altitude 0...9842.52 ft (0...3000 m)
Fire resistance 1562 °F (850 °C) IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz), Vibrations contactor closed 4 Gn, 5...300 Hz), Shocks contactor closed 15 Gn for 11 ms), Shocks contactor open 8 Gn for 11 ms)
Height 3.3 in (85 mm)
Width 1.8 in (45 mm)
Depth 3.6 in (92 mm)
Product Weight 0.82 lb(US) (0.37 kg)

Ordering and Shipping Details

Category US1011222354
Discount Schedule 0112
GTIN 3389110349726
Returnability Yes
Country of origin ID

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 2.20 in (5.600 cm)
Package 1 Width 3.78 in (9.600 cm)
Package 1 Length 4.69 in (11.900 cm)
Package 1 Weight 14.674 oz (416.000 g)
Unit Type of Package 2 S02
Number of Units in Package 2 20
Package 2 Height 5.91 in (15.000 cm)
Package 2 Width 11.81 in (30.000 cm)
Package 2 Length 15.75 in (40.000 cm)
Package 2 Weight 19.125 lb(US) (8.675 kg)

Contractual Warranty

Warranty 18 months

Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.

Environmental footprint

Materials and Substances

  • Packaging made with recycled cardboard: Yes
  • Packaging without single use plastic: Yes
  • EU RoHS Directive: Compliant
  • REACH Regulation: REACH Declaration
  • California proposition 65: WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • PVC free: Yes

Repack and remanufacture

  • Circularity Profile: End of Life Information
  • Take-back: No
  • WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Technical Illustration

Assembly's dimensions

Diagram:

Side view showing dimensions:

  • Height: 85 mm [3.3 in]
  • Width: 45 mm [1.8 in]
  • Depth: 93 mm [3.7 in]

Front view showing terminal layout and dimensions:

  • Overall width: 45 mm [1.8 in]
  • Terminal height: 42.4 mm [1.7 in]
  • Terminal width: 42.4 mm [1.7 in]

PDF preview unavailable. Download the PDF instead.

Generatepdf.aspx?salesorgid=78&dist=849&lang=42&form=no&documenttype=plain&productid=LC1D25T7 cairo 1.15.12 (http://cairographics.org)

Related Documents

Preview Schneider Electric TeSys Deca LC1D09M7 IEC Contactor - 9A, 3-Phase, 220VAC Coil
Detailed technical data sheet for the Schneider Electric TeSys Deca LC1D09M7 IEC contactor. Features include 9A rated operational current (AC3), 3 poles (3NO), 1 NO + 1 NC auxiliary contacts, and a 220VAC 50/60Hz coil. Specifications cover electrical ratings, complementary components, environmental data, dimensions, and ordering information.
Preview Schneider Electric LC1D1506LE7 TeSys Deca IEC Contactor - Technical Specifications
Detailed technical specifications for the Schneider Electric LC1D1506LE7 TeSys Deca IEC contactor. Includes information on electrical ratings, complementary features, environmental data, and dimensions.
Preview Schneider Electric 8910DPA53V06 Definite Purpose Contactor Data Sheet
Technical data sheet for the Schneider Electric 8910DPA53V06 Definite Purpose Contactor, featuring specifications, dimensions, environmental data, and wiring diagram.
Preview Schneider Electric TeSys Deca Contactor LC1D25AP7 Product Data Sheet
Detailed product data sheet for the Schneider Electric TeSys Deca Contactor, model LC1D25AP7. This document outlines specifications, technical data, environmental information, and packaging details for this 3-pole contactor.
Preview TeSys Deca LX1D8 Contactor Coil 220V AC 50/60Hz - Product Data Sheet
Technical specifications and environmental data for the TeSys Deca LX1D8 contactor coil, designed for 115A and 150A contactors. Includes details on coil voltage, resistance, durability, environmental impact, and packaging.
Preview Schneider Electric TeSys Deca Contactor Installation and Safety Guide
Comprehensive guide for installing and operating Schneider Electric TeSys Deca contactors (CAD32-50A, LC1D09-32A). Includes safety warnings, wiring diagrams, and technical specifications.
Preview Schneider Electric LC1D/LC2D Series Contactors: Technical Specifications and Installation Guide
Comprehensive guide to Schneider Electric's LC1D and LC2D series contactors, covering product specifications, safety warnings, installation procedures, dimensions, wiring, and accessories. Features detailed information for electrical engineers and technicians.
Preview Schneider Electric ATS480 Soft Starter SCCR Ratings & Compatibility Guide
Find detailed Short Circuit Current Ratings (SCCR) and compatible component data for Schneider Electric Altivar ATS480 soft starters, tested per UL60947-4-2 for electrical system safety and performance.