Schneider Electric TeSys Deca Contactor LC1D25AP7
Product Data Sheet
Main Specifications
Range of product: TeSys Deca
Product or component type: Contactor
Device short name: LC1D
Contactor application: Motor control
Utilisation category: AC-1, AC-3, AC-3e, AC-4
Poles description: 3P (3 NO)
Rated operational voltage [Ue]: Power circuit: ≤ 690 V AC 25...400 Hz; Power circuit: ≤ 300 V DC
Rated operational current [le]: 25 A (at ≤ 60 °C) at ≤ 440 V AC-3 for power circuit; 25 A (at ≤ 60 °C) at ≤ 440 V AC-3e for power circuit; 40 A (at ≤ 60 °C) at ≤ 440 V AC-1 for power circuit
Control circuit voltage [Uc]: 230 V AC 50/60 Hz
Complementary Specifications
Motor power kW: 5.5 kW at 220...230 V AC 50/60 Hz (AC-3); 11 kW at 380...400 V AC 50/60 Hz (AC-3); 11 kW at 415...440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3); 15 kW at 660...690 V AC 50/60 Hz (AC-3); 5.5 kW at 400 V AC 50/60 Hz (AC-4); 5.5 kW at 220...230 V AC 50/60 Hz (AC-3e); 11 kW at 380...400 V AC 50/60 Hz (AC-3e); 11 kW at 415...440 V AC 50/60 Hz (AC-3e); 15 kW at 500 V AC 50/60 Hz (AC-3e); 15 kW at 660...690 V AC 50/60 Hz (AC-3e)
Compatibility code: LC1D
Pole contact composition: 3 NO
Protective cover: With
Conventional free air thermal current [Ith]: 40 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit
Irms rated making capacity: 450 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity: 450 A at 440 V for power circuit conforming to IEC 60947
Rated short-time withstand current [Icw]: 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 50 A 40 °C -10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at ≤ 690 V coordination type 1 for power circuit; 40 A gG at ≤ 690 V coordination type 2 for power circuit
Average impedance: 2 mΩ - Ith 40 A 50 Hz for power circuit
Power dissipation per pole: 1.25 W AC-3; 1.25 W AC-3e; 3.2 W AC-1
Rated insulation voltage [Ui]: Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1
Overvoltage category: III
Pollution degree: 3
Rated impulse withstand voltage [Uimp]: 6 kV conforming to IEC 60947
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 15 Mcycles
Electrical durability: 1.4 Mcycles 40 A AC-1 at Ue ≤ 440 V; 1.65 Mcycles 25 A AC-3 at Ue ≤ 440 V; 1.65 Mcycles 25 A AC-3e at Ue ≤ 440 V
Control circuit type: AC at 50/60 Hz standard
Coil technology: Without built-in suppressor module
Control circuit voltage limits: 0.3...0.6 Uc (drop-out AC 50/60 Hz); 0.8...1.1 Uc (operational AC 50 Hz); 0.85...1.1 Uc (operational AC 60 Hz); 1...1.1 Uc (operational AC 50/60 Hz)
Inrush power in VA: 70 VA 60 Hz cos φ 0.75 (at 20 °C); 70 VA 50 Hz cos φ 0.75 (at 20 °C)
Hold-in power consumption in VA: 7.5 VA 60 Hz cos φ 0.3 (at 20 °C); 7 VA 50 Hz cos φ 0.3 (at 20 °C)
Heat dissipation: 2...3 W at 50/60 Hz
Operating time: 12...22 ms closing; 4...19 ms opening
Maximum operating rate: 3600 cyc/h at 60 °C
Connections - Terminals
Control circuit: snap-in terminal 1 0.5...4 mm² - flexible without cable end; snap-in terminal 2 0.5...4 mm² - flexible without cable end; snap-in terminal 1 0.5...2.5 mm² - flexible with cable end; snap-in terminal 2 0.5...2.5 mm² - flexible with cable end; snap-in terminal 1 0.5...2.5 mm² - solid without cable end; snap-in terminal 2 0.5...2.5 mm² - solid without cable end
Power circuit: snap-in terminal 1 0.75...6 mm² - flexible without cable end; snap-in terminal 2 0.75...6 mm² - flexible without cable end; snap-in terminal 1 0.75...4 mm² - flexible with cable end; snap-in terminal 2 0.75...4 mm² - flexible with cable end; snap-in terminal 1 0.75...4 mm² - solid without cable end; snap-in terminal 2 0.75...4 mm² - solid without cable end
Auxiliary contact composition: 1 NO + 1 NC
Auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency: 25...400 Hz
Minimum switching voltage: 17 V for signalling circuit
Minimum switching current: 5 mA for signalling circuit
Insulation resistance: > 10 MOhm for signalling circuit
Non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Mounting support: Plate, Rail
Environment
Standards: EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ
Product certifications: CB Scheme, CCC
IP degree of protection: IP20 front face conforming to IEC 60529
Protective treatment: TH conforming to IEC 60068-2-30
Climatic withstand: conforming to IACS E10 exposure to damp heat; conforming to IEC 60947 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device: -40...60 °C; 60...70 °C with derating
Operating altitude: 0...3000 m
Fire resistance: 850 °C conforming to IEC 60695-2-1
Mechanical robustness: Vibrations contactor open (2 Gn, 5...300 Hz); Vibrations contactor closed (4 Gn, 5...300 Hz); Shocks contactor closed (15 Gn for 11 ms); Shocks contactor open (8 Gn for 11 ms)
Height: 110 mm
Width: 45 mm
Depth: 92 mm
Product weight: 454 g
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 5 cm
Package 1 Width: 10.5 cm
Package 1 Length: 11.5 cm
Package 1 Weight: 474 g
Unit Type of Package 2: S02
Number of Units in Package 2: 15
Package 2 Height: 15 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 7.425 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 240
Package 3 Height: 75 cm
Package 3 Width: 60 cm
Package 3 Length: 80 cm
Package 3 Weight: 127.3 kg
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.
Environmental footprint: Carbon footprint (kg.eq.CO2 per CR, Total Life cycle): 126
Materials and Substances: Packaging made with recycled cardboard: Yes; Packaging without single use plastic: Yes
EU RoHS Directive: Compliant
REACH Regulation: REACH Declaration
California proposition 65: WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Repack and remanufacture: Circularity Profile: End of Life Information; Take-back: No
Technical Illustration
Assembly's dimensions:
Height: 110 mm [4.3 in]
Width: 45 mm [1.8 in]
Depth: 92 mm [3.6 in]