RAB Lighting H17 & H17XL LED High Bay Installation Instructions

RAB Lighting H17 & H17XL Installation Instructions

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

Important Information

⚠️ READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.

RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

⚠️ WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.

Suitable for wet locations. Maximum ambient temperature suitable for use in up to 50° C (122°F).

Hook Mounting

Description: This section details how to mount the fixture using a hook or chain.

  1. Screw the Eye-Bolt into the Fixture (refer to Figure 1). Tighten and secure with the Set Screw (refer to Figure 2).
  2. Hang the Fixture on the Ceiling Hook or chain (provided by others) as shown in Figure 2.
  3. After installation, connect the fixture wires to the power supply. Use appropriate UL approved wire connectors as required by code to complete wiring.

Figure 1: Illustrates the Eye-Bolt being screwed into the fixture.

Figure 2: Shows the fixture hanging from a ceiling hook with the Set Screw securing the Eye-Bolt.

Surface Mounting (with Accessory Kit)

(Accessory ordered separately - Model # H17-SM KIT)

  1. Secure the bracket accessory kit (H17-SM Kit) to the fixture and mounting surface (refer to Figure 3) per H17-SM KIT instructions.
  2. After installation, connect the fixture wires to the power supply. Use appropriate UL approved wire connectors as required by code to complete wiring.
  3. Loosen Pivot Bolts and swivel fixture to the desired angle. The fixture can adjust 50° to the left or right vertically (refer to Figure 4).

Figure 3: Depicts mounting hardware and the bracket (H17-SM KIT) attached to bracket holes.

Figure 4: Shows the fixture with Pivot Bolts allowing for vertical angle adjustment.

Pendant Mounting (with Accessory Kit)

  1. Loosen the Set Screw on the Fixture as shown in Figure 5. Mount the H17-PM KIT into the driver housing using (1) 10x30 Screw (provided) for 120-277V installation. Use (1) 12x30 Screw (provided) for 480V installation. Use the Bolt (provided) to secure the H17-PM Kit to the driver housing.
  2. Insert a 3/4" NPT Pendant Stem (not provided) into the H17-PM KIT and secure with the Bolt (refer to Figure 6). Refer to H17-PM KIT installation instructions.
  3. After installation, connect the fixture wires to the power supply. Use appropriate UL approved wire connectors as required by code to complete wiring.

Figure 5: Illustrates the H17-PM KIT, Set Screw, Bolt, and Driver Housing for pendant mounting.

Figure 6: Shows the 3/4" NPT Pendant Stem being inserted into the H17-PM KIT and secured with a Bolt.

Field-Adjustable CCT & Wattage (120-277V ONLY)

Follow instructions below to change the Fixture Power (W) and/or Color Temperature (CCT) from factory settings:

Factory Settings: H17: 150W and 4000K; H17XL: 200W and 4000K

  1. Locate the Field Adjustable Switches on the Fixture Housing as shown below. Remove the waterproof gasket.
  2. Select Power (W) and/or Color Temperature (CCT) by sliding the respective switch to the desired value (refer to Figure 9). Re-install the waterproof gasket.

Figure 9: Displays the CCT Switch and Power Switch on the fixture housing, indicating how to adjust settings.

Wiring

⚠️ RISK OF FIRE. Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. Units ordered with /480V suffix are 480V only, 50 or 60Hz.

For 0-10V dimming, follow wiring directions as shown in Figure 7.

For non-dimming (on/off), follow the wiring directions as shown in Figure 8.

Figure 7: Wiring diagram for 0-10V dimming, showing connections for LINE, COMMON, (+) DIM V, (-) DIM V, and GROUND to the LIGHT FIXTURE.

Figure 8: Wiring diagram for non-dimming (on/off) operation, showing connections for LINE, COMMON, and GROUND to the LIGHT FIXTURE.

Motion Sensor Installation (Purchased Separately)

  1. Ensure power is off to the fixture to avoid risk of shock.
  2. Be sure to remove the PIR40 Sensor pin protector before installing.
  3. Remove the 1/2" Knockout with a screwdriver and install the Sensor Kit onto the fixture (refer to Figure 10) as per sensor kit instructions.

Figure 10: Illustrates the 1/2" Knockout on the fixture and the Sensor Kit being installed.

Cleaning & Maintenance

⚠️ CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.

  1. Do not open the fixture to clean the LED. Do not touch the LED.
  2. Do not touch the reflector, lens, or trim cone.
  3. Do not clean any fixture surface with wood-base cleaning material such as paper towels or tissues.

Troubleshooting

  1. Check that the line voltage at the fixture is correct. Refer to wiring directions.
  2. Is the fixture grounded properly?

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

Models: H17, H17XL, 150W High Bay Fixtures, H17 150W High Bay Fixtures, High Bay Fixtures, Fixtures

File Info : application/pdf, 3 Pages, 1.05MB

PDF preview unavailable. Download the PDF instead.

h17 field adjustable highbay instructions

References

Adobe PDF Library 17.0 Adobe InDesign 18.1 (Windows)

Related Documents

Preview RAB Lighting H17 & H17XL LED Fixture Installation Guide
Comprehensive installation instructions for RAB Lighting H17 and H17XL LED fixtures, covering hook, ceiling, and pendant mounting, wiring, CCT/wattage adjustment, and maintenance.
Preview RAB Lighting H17 & H17XL Surface Mount Kit Installation Instructions
Comprehensive installation, cleaning, and maintenance guide for RAB Lighting's H17 and H17XL Surface Mount Kits. Includes essential safety warnings, step-by-step mounting instructions, and care recommendations.
Preview H17 Field-Adjustable Installation Instructions - RAB Lighting
Comprehensive installation guide for RAB Lighting's H17 series field-adjustable high-bay fixtures, covering hook mounting, surface mounting, pendant mounting, reflector and lens options, wire guard, motion sensor, and battery backup.
Preview RAB X34 Field-Adjustable LED Fixture Installation Guide
Comprehensive installation instructions for RAB Lighting's X34 series field-adjustable LED fixtures, covering mounting options, wiring, field adjustments for CCT and power, photocell operation, and Lightcloud Blue smart control.
Preview RAB Lighting SWISH FA Island LED Fixture & 19724 Microwave Sensor Installation and Operation Guide
Comprehensive installation, wiring, operation, and troubleshooting guide for RAB Lighting SWISH FA Island LED fixtures, including battery backup models, and the 19724 Microwave Sensor with remote control and DIP switch settings.
Preview RAB Lighting BULLET® Field-Adjustable LED Floodlight Installation Guide
Comprehensive installation, wiring, and adjustment guide for RAB Lighting's BULLET® Field-Adjustable LED floodlights, including sensor operation, mounting, and troubleshooting.
Preview RAB X34 Series Field-Adjustable LED Floodlight Installation Instructions
Comprehensive installation guide for RAB Lighting's X34 series field-adjustable LED floodlights, covering mounting, wiring, field adjustments (CCT, Power, Photocell), and maintenance.
Preview ALED® Field-Adjustable LED Installation Instructions | RAB Lighting
Comprehensive installation guide for RAB Lighting's ALED® field-adjustable LED fixtures (ALEDXXS, ALEDXS). Includes mounting, wiring, field adjustment, and troubleshooting.