CONVECTOR Submittal Specification

FWG-A Front Outlet Cabinet Recessed Convector

Model Series: FWG-A

Product Overview

The Vulcan FWG-A is a front outlet, recessed convector cabinet designed with a 4-sided overlap. It features stamped louvers and a pencil-proof design.

Key Specifications

Front and Liner

  • Style: Front Outlet
  • Outlet: Stamped Louvers, Pencil Proof

Element/Coil

Bronze Header 3/4" NPT with Copper Tube/Alum Fins (Mechanically Expanded).

Lengths

Available in 20" through 64" in 4" increments.

Materials

Cabinet Front and Liner:

  • 18 Ga./20 Ga. CRS (Standard) [*]
  • 18 Ga./18 Ga. CRS [Optional]
  • 16 Ga./20 Ga. CRS [Optional] [*]
  • 16 Ga./18 Ga. CRS [Optional]
  • 16 Ga./16 Ga. CRS [Optional]
  • 14 Ga./20 Ga. CRS [Optional] [*]
  • 14 Ga./18 Ga. CRS [Optional]
  • 14 Ga./16 Ga. CRS [Optional]
  • 14 Ga./14 Ga. CRS [Optional]
  • Liner is Galvannealed Steel [*]

Stainless Steel (SS) options are also available for various gauges [Optional].

Finishes

  • Baked Powder Prime
  • Baked Powder Color [Optional]
  • Stainless Steel (SS) options available for 18 Ga./20 Ga., 18 Ga./18 Ga., 16 Ga./20 Ga., 16 Ga./18 Ga., 16 Ga./16 Ga. [Optional]

Optional Accessories

  • Damper: Damper Blades Factory Installed, Knob Damper [Optional], Tamper Resistant [Optional].
  • Access Doors: [Optional].
  • Insulation: Back Only [Optional], Back, Sides, Top [Optional].
  • Piping Knockout: [Optional].
  • 4" End Pockets: LH [Optional], RH [Optional], Both Ends [Optional].
  • Perforated Front: Consult Factory, 16 Ga. [Optional], 14 Ga. [Optional].

Header Connections

  • Single Header Both Ends (Standard)
  • Single Inlet 1 End / Dual Inlet 1 End [Optional]
  • Dual Inlet Both Ends [Optional]

Model Dimensions and Ratings

Type FWG-A Model Table

The following table provides dimensional data (D, L, H, B, J) for various FWG-A models (e.g., 4xx-18, 6xx-20, 8xx-24) and their corresponding lengths.

MODEL D L H B J
4xx-181820,24,28, 32,36,40,20
4xx-202044,48,52,242-1/84
4xx-244-13/1656,60,64,26
4xx-2632
4xx-32
6xx-181820,24,28, 32,36,40,20
6xx-202044,48,52,243-1/86
6xx-246-13/1656,60,64,26
6xx-2632
6xx-32
8xx-181820,24,28, 32,36,40,20
8xx-202044,48,52,244-1/88
8xx-248-13/1656,60,64,26
8xx-2632
8xx-32

Note: When adding end pockets, liner and front length increase.

Steam Ratings Summary

The document provides detailed Steam Ratings in BTU/H for various convector depths, lengths, and front outlet widths (18", 20", 24", 26", 32") at specific conditions (215°F water temperature, 65°F entering air temperature). Due to the extensive nature of these tables, precise ratings and selection assistance are best obtained using the manufacturer's online specifier tool.

Performance Correction Factors

The following tables provide correction factors to adjust BTU performance based on varying operating conditions:

Table 3: Convector BTU Correction Factors

This table details correction factors based on Average Water Temperature (°F) and Entering Air Temperature (°F). These are used to adjust BTU performance from standard conditions.

Table 4: Correction Factors for Steam Pressures

Provides correction factors for steam pressures other than 1 PSI Gauge, up to 50 PSI Gauge. It notes a maximum recommended operating pressure of 150 PSIG.

Table 5: Correction Factors for Access Doors

Lists derating factors for units with access doors, categorized by door location (Free Standing, Non-Recessed vs. Semi-Recessed or Fully Recessed) and number of doors.

Table 6: Pressure Loss

Shows pressure loss in feet of water for different water flow rates (GPM) across 4-inch, 6-inch, and 8-inch convector models. This data is used for determining pressure head requirements.

Table 7: Gallons Per Minute of Hot Water Required

A graphical representation illustrating the relationship between Gallons Per Minute (GPM) and thousands of BTU per hour (MBH) for various water temperature drops (10°F, 20°F, 30°F, 40°F).

Table 8: Output-Flow Rate Corrections

Details MBH values based on specific water temperature drops (TD) and minimum water flow rates (GPM) required to maintain turbulent flow within element tubes.

Diagram Descriptions

Convector Coil Diagram

Illustrates the construction of the convector coil, showing details such as the number of tubes per element (2, 3, or 4 tubes), tube diameter, fin height (2-1/2"), fin spacing (6 fins per inch), and header type (e.g., 3/4" NPT typical, dual inlet header). It also indicates the relationship between end-to-end length and liner length, and riser center dimensions.

Note: When ordering convectors with end pockets, the overall physical length increases by 4" for each end pocket, while the coil length remains standard.

PDF preview unavailable. Download the PDF instead.

FWG-A (8 25) 1 Adobe InDesign 14.0 (Macintosh) Adobe PDF Library 15.0

Related Documents

Preview Vulcan RF-A/RFG-A Convector Submittal Specification
Detailed submittal specification for Vulcan RF-A and RFG-A series recessed flat top convectors, including features, materials, dimensions, and performance data.
Preview Vulcan SR-A/SRG-A Convector Submittal Specification
Vulcan SR-A and SRG-A convector submittal specification document detailing flat top, semi-recessed cabinets. Covers materials, finishes, coil specifications, optional accessories, header connections, insulation, and comprehensive performance data including steam ratings, correction factors, and pressure loss charts.
Preview Vulcan PW-A/PWG-A Convector Specification | Submittal Data
Detailed submittal specification for Vulcan PW-A and PWG-A convector heaters, including BTU ratings, dimensions, materials, correction factors, and pressure loss data.
Preview Vulcan FS-A/FSG-A Convector Submittal Specification and Ratings
Detailed submittal specification for Vulcan FS-A and FSG-A flat top convector cabinets, including dimensions, materials, finishes, optional accessories, steam ratings, and correction factors for various operating conditions. Suitable for wall or floor mounting.
Preview Vulcan Convector Heaters: Product Catalog, Specifications, and Selection Guide
Comprehensive guide to Vulcan Convector Heaters, including Sterling Convectors. Features product types, specifications, installation data, capacity tables, and selection tools for HVAC professionals.
Preview LINOVECTOR II: Copper/Aluminum and Steel Finned Tube Unit Specifications and Design Data
Comprehensive submittal specification and design data for Vulcan LINOVECTOR II finned tube units, detailing enclosure options, element specifications, performance ratings, correction factors, and technical data for HVAC applications.
Preview Vulcan 'J' Classic Commercial Finned Tube Radiation Installation Instructions
Comprehensive installation guide for Vulcan's 'J' Classic Commercial Finned Tube Radiation models JV3/JV4-ARS, covering mounting, assembly, and maintenance procedures.
Preview Vulcan VC55G Series Double Deck Gas Convection Oven: Spec Sheet & Installation Guide
Detailed specifications and installation instructions for the Vulcan VC55G Series Double Deck Gas Convection Oven, featuring removable doors, ENERGY STAR certification, and robust commercial-grade performance.