CONVECTOR

Submittal Specification

PW-A / PWG-A Flat Top Cabinet Semi-Recessed 4 Sided Overlap

Product Features and Specifications

This document outlines the specifications for the Vulcan PW-A and PWG-A convector units, designed for flat top cabinet applications, available in semi-recessed configurations with a 4-sided overlap.

Available Models and Options

Inlet Options:

Construction and Materials

Front and Liner:

Coil and Connections

Element/Coil: Bronze Header 3/4" NPT with Copper Tube/Aluminum Fins, mechanically expanded.

Header Connections:

Optional Accessories

Note: When adding end pockets, the liner and front length increase. The overall physical length will increase by 4" for each end pocket, while the coil length remains the standard size.

Model Dimensions and Ratings

Type PW-A / PWG-A Model Dimensions

The following table details the dimensions (D, L, H, B, J) for various PW-A/PWG-A models.

MODEL D L H B J
4xx-1818"20,24,28,
32,36,40,
44,48,52,
56,60,64,
24"2-1/8"2"
4xx-2020"26"
4xx-244-1/4"28"
4xx-26
4xx-28
6xx-1818"20,24,28,
32,36,40,
44,48,52,
56,60,64,
24"3-1/8"4"
6xx-2020"26"
6xx-246-1/4"28"
6xx-26
6xx-28
8xx-1818"20,24,28,
32,36,40,
44,48,52,
56,60,64,
24"4-1/8"6"
8xx-2020"26"
8xx-248-1/4"28"
8xx-26
8xx-28

Steam Ratings (BTU/H)

The following tables provide steam ratings in BTU/H for units operating at 215°F entering water and 65°F entering air (EAT).

Type PW-A Ratings

DEPTH
INCHES
FRONT OUTLET, NOMINAL LINER HEIGHT *TYPE PW-A
18"20"24"26"28"
2022302495283029303120
2427603145362537203985
2833103815434544654775
3238654490511052555665
3643705160588060256505
4048955810660067907320
4454256480739075608160
4859507105811083508975
5265507800885590709745
56703084509625986510630
6076559120103451061011400
6481359790111351140012290
2032403625425043904850
2440304560537555706170
2848505520648066707370
3256156480761078708690
3664307390869090259935
407250837598151020011230
4480659290109201135012480
48888010250120251245513705
52974511185131051353514905
561051012145142301473516225
601140013055153101584017425
641219014040164401706518770
2040304535504051355570
2451105760636065757105
2863856960768078958520
32756081859025931010055
3687109385103901070511545
40986510630117601207013055
441104011830130551344014545
481195012935144001481016080
521346514230156701610517425
561461515505170901757019010
601577016655183351884020375
641677517880197502033021960

Type PWG-A Ratings

DEPTH
INCHES
FRONT OUTLET, NOMINAL LINER HEIGHT *TYPE PWG-A
18"20"24"26"28"
2021632420277328713089
2426773051355336463945
2832113701425843764727
3237494355500851505608
3642395005576259056440
4047485636646866547247
4452626286724274098078
4857726892794881838885
5263547566867888899648
56681981979433966810524
6074258846101381039811286
6478919496109121117212167
2030463408403841714753
2437884286510652926047
2845595189615663377223
3252786091723074778516
3660446947825685749736
40681578739324969011005
4475818733103741078312230
4883479635114241183213431
52916010514124501285814607
56987911416135191399815901
601071612272145451504817077
641145913198156181621218395
2036674127468747765403
2446505242591561156892
2858106334714273428264
3268807448839386589753
36792685409663995611199
4089779673109371122512663
441004610765121411249914109
481087511771133921377315598
521225312949145731497816902
561330014110158941634018440
601435115156170521752119764
641526516271183681890721301

Correction Factors and Performance Data

Convector BTU Correction Factors (Table 3)

Correction factors based on ASHRAE HVAC Systems and Equipment, Section 35.4, for varying Average Water Temperatures and Entering Air Temperatures (Standard conditions).

AVERAGE WATER TEMPERATURE (°F) ENTERING AIR TEMPERATURE (°F) (STD)
55°60°65°70°75°
100°0.170.140.120.090.07
110°0.230.200.170.140.12
120°0.290.260.230.200.17
130°0.350.320.290.260.23
140°0.430.390.350.320.29
150°0.500.460.430.390.35
160°0.580.540.510.470.43
170°0.670.630.580.540.51
180°0.760.710.670.630.58
190°0.850.810.760.710.67
200°0.950.900.850.810.76
210°1.051.000.950.900.85
215° (STD)1.101.051.000.950.90
220°1.151.101.051.000.95
230°1.261.201.151.101.05
240°1.371.321.261.211.15
250°1.471.431.371.321.27

Correction Factors for Steam Pressures (Table 4)

Correction factors for steam pressures other than 1 PSI Gauge. Maximum recommended operating pressure is 150 PSIG (365.9°F).

Table 4: Correction Factors for Steam Pressures Other Than 1 PSI Gauge

Pressure PSI Gauge: 5, 10, 15, 20, 25, 50

Factor: 1.12, 1.25, 1.36, 1.46, 1.56, 1.93

Note: Apply factors shown above to the ratings shown on the 215°F ratings page. For conversion from steam to hot water, use correction factors shown in Table 3.

Note: Maximum Recommended operating pressure 150 PSIG, (365.9°F).

Correction Factors for Access Doors (Table 5)

Correction factors for units with access doors, categorized by door location and unit configuration.

Length Free Standing, Non-Recessed Non-Standard Access Door Locations Semi-Recessed or Fully Recessed Non-Standard Access Door Locations
3 or 43 & 45 or 65 & 6 3 or 43 & 45 or 65 & 6
20"0.9400.8800.8200.6500.9750.9500.9250.850
24"0.9500.9100.8600.7200.9800.9600.9400.880
28"0.9600.9200.8900.7700.9820.9680.9480.902
32"0.9700.9400.8900.8000.9850.9720.9550.918
36"0.9700.9400.9200.8300.9880.9750.9620.925
40"0.9700.9500.9200.8500.9900.9780.9700.932
44"0.9800.9500.9300.8600.9900.9800.9700.940
48"0.9800.9600.9400.8800.9900.9820.9700.948
52"0.9800.9600.9500.8900.9920.9850.9780.955
56"0.9800.9600.9500.8900.9920.9850.9780.955
60"0.9800.9700.9500.9000.9920.9850.9780.955
64"0.9800.9700.9500.9100.9920.9880.9780.962

Note: Derating factors do not apply to units with end pockets.

Pressure Loss (Table 6)

Pressure loss in feet of water for convector units with forced hot water, based on 64" length units but applicable to shorter units as most loss is due to headers.

WATER FLOW IN GPM 4 INCH MODELS 6 INCH MODELS 8 INCH MODELS
.250.044----
.500.1600.0700.046
10.5970.2700.167
22.2201.0470.616
3--2.2601.367
4--3.7932.380
5----3.673

Charted figures showing pressure drop through Convectors with forced hot water. Used for determining pressure head requirement. Based on 64" length units, but applicable to shorter units, as most loss is due to headers.

Output-Flow Rate Corrections (Table 7 & 8)

Table 7: Gallons Per Minute of Hot Water Required

This chart illustrates the relationship between Gallons Per Minute (GPM) and thousands of BTU per hour (MBH) for different temperature drops.

Table 8: Output-Flow Rate Corrections

This table shows MBH which result at specific water temperature drops and minimum water flow rates required to maintain turbulent flow within element tubes.

Convector Depth Tubes per Element GPM (Min. Flow Rate 0.25 Ft./Sec.) MBH Based on T.D. & Min. Flow Rate
10TD20TD30TD40TD
4"20.150.7501,5002,2503,000
6"30.2251.1252,2503,3754,500
8"40.301.5003,0004,5006,000

Component Details

Convector Coil Diagram

The convector coil is constructed with a Bronze Header and 3/4" NPT connections. It features Copper Tube elements with Aluminum Fins, mechanically expanded. The coil is available in different configurations:

The end-to-end length of the coil is the liner length minus 1/2 inch. Riser centers are the liner length minus 2 1/2 inches.

Coil fins are 2-1/2 inches high and are bonded to the copper tube at 6 fins per inch.

A Vent Plug is typically located on the coil assembly, and a 3-position hanger is welded to the liner for mounting.

Note: When ordering convectors with end pockets, always refer to the standard unit length. The overall physical length will increase by 4" for each end pocket. The coil length will remain the standard size.

PDF preview unavailable. Download the PDF instead.

PW-A PWG-A (8 25) Adobe InDesign 14.0 (Macintosh) Adobe PDF Library 15.0

Related Documents

Preview Vulcan SR-A/SRG-A Convector Submittal Specification
Vulcan SR-A and SRG-A convector submittal specification document detailing flat top, semi-recessed cabinets. Covers materials, finishes, coil specifications, optional accessories, header connections, insulation, and comprehensive performance data including steam ratings, correction factors, and pressure loss charts.
Preview Vulcan RF-A/RFG-A Convector Submittal Specification
Detailed submittal specification for Vulcan RF-A and RFG-A series recessed flat top convectors, including features, materials, dimensions, and performance data.
Preview Vulcan FWG-A Louvered Inlet Convector Specification Sheet
Detailed specifications, performance data, and correction factors for the Vulcan FWG-A Front Outlet Recessed Louvered Inlet Convector. Includes material, finish, and accessory options.
Preview Vulcan Convector Heaters: Product Catalog, Specifications, and Selection Guide
Comprehensive guide to Vulcan Convector Heaters, including Sterling Convectors. Features product types, specifications, installation data, capacity tables, and selection tools for HVAC professionals.
Preview Vulcan FS-A/FSG-A Convector Submittal Specification and Ratings
Detailed submittal specification for Vulcan FS-A and FSG-A flat top convector cabinets, including dimensions, materials, finishes, optional accessories, steam ratings, and correction factors for various operating conditions. Suitable for wall or floor mounting.
Preview LINOVECTOR II: Copper/Aluminum and Steel Finned Tube Unit Specifications and Design Data
Comprehensive submittal specification and design data for Vulcan LINOVECTOR II finned tube units, detailing enclosure options, element specifications, performance ratings, correction factors, and technical data for HVAC applications.
Preview Vulcan V Series HDR Gas Ranges Operations Manual
Comprehensive operations, installation, and maintenance manual for Vulcan V Series HDR Gas Ranges. Includes safety guidelines, configuration details, troubleshooting, and cleaning procedures.
Preview Vulcan V Series HDR Gas Ranges Operations Manual
Comprehensive operations manual for Vulcan V Series HDR Gas Ranges, covering installation, operation, cleaning, maintenance, and troubleshooting for commercial kitchen environments.