CONVECTOR Submittal Specification

SR-A / SRG-A Flat Top Cabinet Semi-Recessed 3 Sided Overlap

Brand: Vulcan

General Specifications

Model Types

Front and Liner

Style: Front Outlet

Outlet: Stamped Louvers, Pencil Proof

Lengths

20" through 64" in 4" Increments

Materials

Cabinet Front and Liner:

Finish

Coil Specifications

Element: Bronze Header 3/4" NPT w/Copper Tube/Alum Fins (Mechanically Expanded).

Header Connections

Optional Accessories

Damper

Access Doors

(Opt'l)

Insulation

Piping Knockout

(Opt'l)

4" End Pockets

Perforated Front

Consult Factory

16 Ga. (Opt'l)

14 Ga. (Opt'l)

Model Dimensions (Type SR-A / SRG-A)

MODELDLHBJ
4xx-161620,24,28, 32,36,40, 44,48,52, 56,60,64,162-1/82
4xx-181818
4xx-224-1/422
4xx-242424
4xx-303030
6xx-161620,24,28, 32,36,40, 44,48,52, 56,60,64,163-1/84
6xx-181818
6xx-226-1/422
6xx-242424
6xx-303030
8xx-161620,24,28, 32,36,40, 44,48,52, 56,60,64,164-1/86
8xx-181818
8xx-228-1/422
8xx-242424
8xx-303030

Note: When adding end pockets, liner and front length increase.

Diagram: Convector Outline

A diagram illustrates the convector's profile, showing the relationship between 'D' (depth), 'L' (length), and 'H' (height). It indicates a wall mounting configuration with a damper, adjustable field settings, and louvers. Key dimensions are labeled, including the overall length ('L'), depth ('D'), and height ('H'). The diagram also shows the placement of the outlet louvers and the base/floor.

Steam Ratings in BTU/H (215°F at 65°F EAT)

Type SR-A

DEPTH INCHES LENGTH INCHES FRONT OUTLET, NOMINAL LINER HEIGHT *TYPE SR-A
16"18"22"24"30"
2022302495283029303120
2427603145362537203985
2833103815434544654775
3238654490511052555665
3643705160588060256505
4048955810660067907320
4454256480739075608160
4859507105811083508975
5265507800885590709745
56703084509625986510630
6076559120103451061011400
6481359790111351140012290
2032403625425043904850
2440304560537555706170
2848505520648066707370
3256156480761078708690
3664307390869090259935
407250837598151020011230
4480659290109201135012480
48888010250120251245513705
52974511185131051353514905
561051012145142301473516225
601140013055153101584017425
641219014040164401706518770
2040304535504051355570
2451105760636065757105
2863856960768078958520
32756081859025931010055
3687109385103901070511545
40986510630117601207013055
441104011830130551344014545
481195012935144001481016080
521346514230156701610517425
561461515505170901757019010
601577016655183351884020375
641677517880197502033021960

Type SRG-A

DEPTH INCHES LENGTH INCHES FRONT OUTLET, NOMINAL LINER HEIGHT *TYPE SRG-A
16"18"22"24"30"
2021632420277328713089
2426773051355336463945
2832113701425843764727
3237494355500851505608
3642395005576259056440
4047485636646866547247
4452626286724274098078
4857726892794881838885
5263547566867888899648
56681981979433966810524
6074258846101381039811286
6478919496109121117212167
2030463408403841714753
2437884286510652926047
2845595189615663377223
3252786091723074778516
3660446947825685749736
40681578739324969011005
4475818733103741078312230
4883479635114241183213431
52916010514124501285814607
56987911416135191399815901
601071612272145451504817077
641145913198156181621218395
2036674127468747765403
2446505242591561156892
2858106334714273428264
3268807448839386589753
36792685409663995611199
4089779673109371122512663
441004610765121411249914109
481087511771133921377315598
521225312949145731497816902
561330014110158941634018440
601435115156170521752119764
641526516271183681890721301

Correction factors for BTU performance at different Average Water Temperatures are available in Table 3. For other applicable correction factors, see the Correction Factors page. For assistance with ratings and selection, please use the online Specifier tool.

Correction Factors

Table 3: Convector BTU Correction Factors

Based on Section 35.4 ASHRAE HVAC Systems and Equipment

AVERAGE WATER TEMPERATURE (°F) ENTERING AIR TEMPERATURE (°F)
55°60°65°70°75°
100°0.170.140.120.090.07
110°0.230.200.170.140.12
120°0.290.260.230.200.17
130°0.350.320.290.260.23
140°0.430.390.350.320.29
150°0.500.460.430.390.35
160°0.580.540.510.470.43
170°0.670.630.580.540.51
180°0.760.710.670.630.58
190°0.850.810.760.710.67
200°0.950.900.850.810.76
210°1.051.000.950.900.85
215° (STD)1.101.051.000.950.90
220°1.151.101.051.000.95
230°1.261.201.151.101.05
240°1.371.321.261.211.15
250°1.471.431.371.321.27

Table 4: Correction Factors for Steam Pressures Other Than 1 PSI GAUGE*

FACTOR PRESSURE PSI GAUGE
51015202550
1.121.251.361.461.561.93

*Apply factors shown above to the ratings shown on the 215°F ratings page.

Note: Maximum Recommended operating pressure 150 PSIG, (365.9°F). For conversion from steam to hot water, use correction factors shown in Table 3.

Table 5: Correction Factors for Access Doors

Length Free Standing, Non-Recessed Non-Standard Access Door Locations Semi-Recessed or Fully Recessed Non-Standard Access Door Locations
3 or 43 & 45 or 65 & 6 3 or 43 & 45 or 65 & 6
20"0.9400.8800.8200.6500.9750.9500.9250.850
24"0.9500.9100.8600.7200.9800.9600.9400.880
28"0.9600.9200.8900.7700.9820.9680.9480.902
32"0.9700.9400.8900.8000.9850.9720.9550.918
36"0.9700.9400.9200.8300.9880.9750.9620.925
40"0.9700.9500.9200.8500.9900.9780.9700.932
44"0.9800.9500.9300.8600.9900.9800.9700.940
48"0.9800.9600.9400.8800.9900.9820.9700.948
52"0.9800.9600.9500.8900.9920.9850.9780.955
56"0.9800.9600.9500.8900.9920.9850.9780.955
60"0.9800.9700.9500.9000.9920.9850.9780.955
64"0.9800.9700.9500.9100.9920.9880.9780.962

Note: Derating factors do not apply to units with end pockets.

Table 6: Pressure Loss in Feet of Water

Charted figures showing pressure drop through Convectors with forced hot water. Used for determining pressure head requirement. Based on 64" length units, but applicable to shorter units, as most loss is due to headers.

WATER FLOW IN GPM 4 INCH MODELS 6 INCH MODELS 8 INCH MODELS
.250.044----
.500.1600.0700.046
10.5970.2700.167
22.2201.0470.616
3--2.2601.367
4--3.7932.380
5----3.673

Table 7: Gallons Per Minute of Hot Water Required

This is a graph illustrating the relationship between MBH (Thousands of BTU per Hour) on the x-axis and GPM (Gallons Per Minute) on the y-axis. It shows different lines representing various temperature drops (10°F, 20°F, 30°F, 40°F) for hot water flow.

Table 8: Output-Flow Rate Corrections

Convector Depth Tubes per Element GPM MBH Based on T.D. & Min. Flow Rate
Min. Flow Rate (0.25 Ft./Sec.) 10TD 20TD 30TD 40TD
4"20.150.7501,5002,2503,000
6"30.2251.1252,2503,3754,500
8"40.301.5003,0004,5006,000

Note: Table 8 shows MBH which result at specific water temperature drops and minimum water flow rates which are required to maintain turbulent flow within element tubes.

Diagram: Convector Coil

A diagram details the convector coil construction. It specifies coil sizes based on the number of tubes: 4" depth has a 2-tube element (3 3/4" width), 6" depth has a 3-tube element (5 3/4" width), and 8" depth has a 4-tube element (7 3/4" width). The diagram shows the end-to-end length being the liner length less 1/2", and riser centers being the liner length less 2 1/2". It also indicates a 3/4" NPT typical connection, a vent plug, and a 3-position hanger welded to the liner. A note clarifies that when ordering with end pockets, the overall physical length increases by 4" per pocket, while the coil length remains standard. Coil fins are 2-1/2" high and mechanically bonded to copper tubes at 6 fins per inch.

Contact Information

Vulcan

260 North Elm St., Westfield, MA 01085

(413) 568-9571

www.vulcanrad.com

Project: [Project Name Placeholder]

Location: [Location Placeholder]

Architect: [Architect Placeholder]

Engineer: [Engineer Placeholder]

Contractor: [Contractor Placeholder]

PO Number: [PO Number Placeholder]

Date: [Date Placeholder]

PDF preview unavailable. Download the PDF instead.

SR-A SRG-A (8 25) Adobe InDesign 14.0 (Macintosh) Adobe PDF Library 15.0

Related Documents

Preview Vulcan RF-A/RFG-A Convector Submittal Specification
Detailed submittal specification for Vulcan RF-A and RFG-A series recessed flat top convectors, including features, materials, dimensions, and performance data.
Preview Vulcan PW-A/PWG-A Convector Specification | Submittal Data
Detailed submittal specification for Vulcan PW-A and PWG-A convector heaters, including BTU ratings, dimensions, materials, correction factors, and pressure loss data.
Preview Vulcan FWG-A Louvered Inlet Convector Specification Sheet
Detailed specifications, performance data, and correction factors for the Vulcan FWG-A Front Outlet Recessed Louvered Inlet Convector. Includes material, finish, and accessory options.
Preview Vulcan Convector Heaters: Product Catalog, Specifications, and Selection Guide
Comprehensive guide to Vulcan Convector Heaters, including Sterling Convectors. Features product types, specifications, installation data, capacity tables, and selection tools for HVAC professionals.
Preview Vulcan FS-A/FSG-A Convector Submittal Specification and Ratings
Detailed submittal specification for Vulcan FS-A and FSG-A flat top convector cabinets, including dimensions, materials, finishes, optional accessories, steam ratings, and correction factors for various operating conditions. Suitable for wall or floor mounting.
Preview LINOVECTOR II: Copper/Aluminum and Steel Finned Tube Unit Specifications and Design Data
Comprehensive submittal specification and design data for Vulcan LINOVECTOR II finned tube units, detailing enclosure options, element specifications, performance ratings, correction factors, and technical data for HVAC applications.
Preview Vulcan V Series HDR Gas Ranges Operations Manual
Comprehensive operations, installation, and maintenance manual for Vulcan V Series HDR Gas Ranges. Includes safety guidelines, configuration details, troubleshooting, and cleaning procedures.
Preview Vulcan VFRY18 Series Heavy Duty Range Match Fryer: Specifications & Installation
Comprehensive specifications, standard and optional features, and installation instructions for the Vulcan VFRY18 Series Heavy Duty Range Match Fryer. This commercial-grade gas fryer offers a 45-50 lb capacity and is designed for professional kitchens.