Product Overview

Positive Pressure Tested Gasketing Materials for Fire Doors.

Intended for application to listed steel frames and/or classified steel covered composite, hollow metal type fire doors rated up to 3 hours, wood and plastic covered composite type fire doors rated up to 1-1/2 hours, and wood core type fire doors rated up to 20 minutes.

Meets UL10B, UL10C and CAN4-S104-2010 Category J .17L5 9903.

Certifications: CLASSIFIED CUL US.

Visual Description: The product includes diagrams illustrating dimensions of 7/16 inches and 7/32 inches. Another diagram shows the application of gasketing on a door, indicating the 'Lock Side & Head' and 'Hinge Side' of the 'Door'.

Installation Instructions

WARNING: Prior to installation, please ensure the surface is clean, dry, and free of any solvents, dust, grease, or oil. If the door is painted, the paint must be uniformly applied and completely dry. (Beware of quick-drying primers that leave a powdered surface, as this may cause a complete lack of adhesion.)

NOTE: Wood frames that are painted or have other finished surfaces must be non-porous and smooth.

For best application, please test the adhesion on a small doorframe area prior to installation. Adhesive tape sets gradually and is fully set in 24 hours. The strip adheres to most any doorframe surface, but we cannot control the various paints and paint additives that may be used.

  1. Adhesive must be applied on a clean, dry frame with a room temperature of 50°F and 100°F, with end use temperatures between -30°F and 140°F.
  2. Cut one piece of gasketing to fit the top width of the frame. Peel off the backing and press it onto the frame inch by inch, without stretching it.
  3. Cut two pieces of gasketing for the height of the frame and attach as shown for the lock and hinge sides. Peel and press them onto each side inch by inch, again without stretching.
  4. Open and close the door several times to ensure gasketing is adjusted properly and doesn't interfere with the door self-closing or latching. IMPORTANT: Do not overlap or run strips continuously—cut at corners where head and jambs meet.
Models: 9117-BK, 9117-20, 9117-BK Smoke and Draft Control, 9117-BK, Smoke and Draft Control, Draft Control, Control

File Info : application/pdf, 2 Pages, 136.61KB

PDF preview unavailable. Download the PDF instead.

Zero Weatherstripping Model 9117-20 Installation Instructions 016381

References

Adobe PDF Library 17.0

Related Documents

Preview Allegion 9117-BK 17' PSA Smoke & Draft Control Gasketing Installation Guide
Installation instructions and product details for Allegion Zero International 9117-BK 17' PSA Smoke & Draft Control gasketing for fire doors. Covers application, compliance, and installation steps.
Preview Zero International WT9188BK-17PSA Smoke & Draft Control Gasketing Installation
Installation instructions and product details for Zero International WT9188BK-17PSA smoke and draft control gasketing for fire doors. Features positive pressure testing and compliance with UL, UL10B, UL10C, and CAN4-S104 standards.
Preview Allegion 8654 Threshold Installation Instructions
Step-by-step guide for installing the Allegion 8654 threshold, including preparation, fitting, securing, and testing. Details fire door compatibility and compliance standards.
Preview Allegion 8664 Threshold Installation Instructions
Detailed installation guide for the Allegion 8664 threshold, including steps for measuring, cutting, notching, securing, and testing door operation. Features UL classification for fire door applications.
Preview Allegion 9011V Door Shoe Installation Instructions
Comprehensive installation guide for the Allegion 9011V door shoe, detailing steps for measuring, fitting, mounting, and testing for fire door applications. Includes UL classification details.
Preview Allegion 9091V Door Sweep Installation Instructions
Step-by-step installation guide for the Allegion 9091V door sweep, providing instructions for measuring, preparing, attaching, and testing the sweep for optimal door sealing.
Preview Allegion 9016V Zero Rain Drip Installation Instructions
Comprehensive installation guide for the Allegion 9016V Zero Rain Drip door shoe, detailing measurement, trimming, mounting, and testing procedures for fire-rated doors.
Preview Allegion 9003V Door Sweep Installation Instructions
Detailed installation guide for the Allegion 9003V Door Sweep, providing step-by-step instructions for proper fitting and sealing of fire-rated doors.