CVM-C4
DAYA ANALYZER
CVM-C4 Multi Fungsi Panel Mount Multimeter
Jeneng sambungan terminal | |
1 | L/+, sumber daya |
2 | N/-, sumber daya |
4 | I1 S1, Input saiki L1 |
5 | I1 S2, Input saiki L1 |
6 | I2 S1, Input saiki L2 |
7 | I2 S2, Input saiki L2 |
8 | I3 S1, Input saiki L3 |
9 | I3 S2, Input saiki L3 |
11 | U1, Voltage input L1 |
12 | U2, Voltage input L2 |
13 | U3, Voltage input L3 |
14 | UN/U2, Voltage input N/L2 |
15 | RO1, Output relay 1 (Umum) |
16 | Output relay 1 (NO) / Output relay 2 (Umum) |
17 | RO2, Output relay 2 (NO) |
47 | +, Output impuls |
48 | -, Output impuls |
49 | +, Output impuls |
50 | -, Output impuls |
58 | A, RS-485 |
59 | B, RS-485 |
70 | C, Input digital umum |
71 | DI1, Input digital 1 |
72 | DI2, Input digital 2 |
Sambungan
Ngukur jaringan telung fase kanthi sambungan 4 kabel.
Ngukur jaringan telung fase kanthi sambungan 3 kabel.
Manual iki minangka pandhuan instalasi CVM-C4. Kanggo informasi luwih lengkap, mangga download manual lengkap saka CIRCUTOR web situs: www.circutor.com
PENTING!
Piranti kasebut kudu dicopot saka sumber daya (sumber daya lan pangukuran) sadurunge nindakake operasi instalasi, ndandani utawa nangani sambungan piranti. Hubungi layanan sawise-sales yen sampeyan ngira yen ana kesalahan operasional ing piranti Piranti kasebut wis dirancang supaya gampang diganti yen ana kerusakan.
Produsen piranti ora tanggung jawab kanggo karusakan apa wae amarga gagal pangguna utawa installer kanggo ngrungokake bebaya lan/utawa rekomendasi sing ditetepake ing manual iki, utawa kanggo karusakan amarga panggunaan produk utawa aksesoris sing ora asli utawa sing digawe. dening manufaktur liyane.
DESKRIPSI
CVM-C4 minangka piranti sing ngukur, ngetung lan nampilake paramèter listrik utama ing fase siji lan telung fase.
Piranti kasebut nduweni komunikasi RS-485, output relay, output impuls lan input digital.
Pangukuran saiki ora langsung ditindakake dening trafo /5A utawa /1A.
INSTALASI
Piranti kasebut kudu dipasang ing panel listrik utawa pager, lan dipasang ing panel.
PENTING!
Elinga yen nalika piranti disambungake, terminal bisa mbebayani kanggo nutul, lan mbukak tutup utawa mbusak unsur bisa nyedhiyakake akses menyang bagean sing mbebayani kanggo tutul. Aja nggunakake piranti nganti diinstal kanthi lengkap
Kanggo nginstal, tindakake langkah ing ngisor iki:
- Gawe potongan ing panel, miturut dimensi ing Gambar 1.
- Saka njaba, lebokake piranti menyang panel cut-out (Gambar 2).
- Lebokake piranti kanthi lengkap lan kenceng kanthi aman kanthi nggunakake spring (Gambar 3)
SAMBUNGAN
Piranti kasebut kudu disambungake menyang sirkuit daya sing dilindhungi dening sekring kanthi arus maksimum 0.25 A.
Yen voltage sing bakal diukur luwih dhuwur tinimbang nilai input voltage, lan voltage trafo kudu disambungake menyang piranti.
Yen luwih saka siji piranti disambungake menyang trafo saiki, padha kudu disambungake ing seri.
Sadurunge medhot kabel sambungan pangukuran saiki, dadi manawa kanggo medhot kabel utami trafo lan jembatan sekunder.
Piranti kasebut bisa digunakake ing mode telung kabel, telung fase utawa papat kabel, mode telung fase, pangguna milih mode sambungan sing cocog miturut instalasi. Jinis sambungan sing salah utawa kesalahan ing urutan fase bisa nyebabake kesalahan pangukuran.
Fitur teknis
Sumber Daya AC” | |||
Dinilai voltage | 80 … 270 V – | ||
Frekuensi | 50/60 Hz | ||
Konsumsi | 6 ... 18 VA | ||
Kategori instalasi | CAT III 300 V | ||
Sumber Daya DC" | |||
Dinilai voltage | 80 270 V …=_ | 18… 36 V | |
Konsumsi | 1.5 1.8 W | 1.8 … 2.2 W | |
Kategori instalasi | CAT III 300 V | ||
Voltage sirkuit pengukuran | |||
Dinilai voltage (Un) | 100 277 V, vc, – t 8% | ||
Margin pangukuran frekuensi | 45 … 65 Hz | ||
Kakehan beban | 1.2 Un continuo / continuo, 2 Un instantaneo / instantaneous (1 menit) |
||
Konsumsi | <0.2 VA (por fase / per phase) | ||
Impedansi | > 1.7 MO | ||
Kategori instalasi | CAT III 300 V | ||
Sirkuit pangukuran saiki | |||
Rated saiki (Ing) | 1 A/5 A – | ||
Margin pangukuran frekuensi | 45 … 65 Hz | ||
Kakehan beban | 1.2 Terus-terusan / terus-terusan, 10Ins tantaneo / instan (55) |
||
Konsumsi | <0.2 VA (por fase / per phase) | ||
Impedansi | < 20 mO | ||
Kategori instalasi | CAT III 300 V | ||
Aku racy | |||
Voltage pangukuran | 0.2 % t 1 digit / digit | ||
Pangukuran saiki | 0.2 % t 1 digit / digit | ||
Pangukuran Daya Aktif lan Reaktif | 0.5 % t 2 digit / digit | ||
Relay output | |||
Jumlah | 2 | ||
Kapasitas kontak (resistif) | CA/AC: 5A / 250V – , CC/DC: 5A / 30V -= | ||
Maks. voltage mbukak kontak | 277V – / 30V _..= | ||
Saiki maksimum | 5 A | ||
daya ngoper maksimum | 1385 VA / 150 W | ||
Daya listrik (250V -/5A) | 11105 | ||
Input digital | |||
Jumlah | 2 | ||
Jinis | Kontak gratis potensial / Potensi kontak gratis | ||
Isolasi | 3.5 kV rms | ||
Maksimum short-circuit saiki | 4 mA | ||
Vol maksimumtage ing sirkuit mbukak | 30 V | ||
Output impuls | |||
Jinis | Pulso pasivo / pulsa pasif | ||
Vol maksimumtage | 27 V | ||
Saiki maksimum | 27 mA | ||
Frekuensi maksimum | 10 Hz | ||
Jembar pulsa minimal | 80 mA | ||
Komunikasi RS-485 | |||
Protokol komunikasi | Mod bus RTU | ||
Baud rate | 2400- 4800 - 9600 - 19200 bps | ||
Bit data | 8 | ||
Mungkasi bit | 1-2 | ||
Paritas | dosa, par, impar / tanpa, genap, ganjil | ||
antarmuka panganggo | |||
Tampilan | LCD | ||
Papan ketik | 3 teclas / tombol | ||
Fitur lingkungan | |||
Suhu operasi | -10°C… +60°C | ||
Suhu panyimpenan | -20 ° C… + 70 ° C | ||
Kelembapan relatif | 5… 95% | ||
Dhuwur maksimal | 2000 m | ||
Gelar pangayoman | Ngarep / Ngarep: IP54, Posterior / Kasus mburi: IP20 | ||
Gelar polusi | |||
Fitur mekanik | |||
reresik II | ![]() |
![]() ![]() |
|
1,2, 4 … 9,11 …18, 47 …50, 58, 59,70 … 72 | 2.5 mm? | 0.5 Nm Plano / Flat (SZS 0.6×3.5) | |
ukuran | 96 x 96 x 41.5 mm | ||
Bobot | 265 g. | ||
Enclosure | pc + abs |
standers
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61010-1-XNUMX XNUMX-XNUMX
Gumantung model:
Kunci | |
![]() |
Layar sadurunge |
![]() |
Layar sabanjuré |
![]() |
Ketukan tombol dawa (>3s): Ketik ing menu konfigurasi |
Cathetan: Gambar piranti mung kanggo ilustrasi lan bisa uga beda karo piranti sing nyata.
Layanan teknis
SIRKUTOR SAT: 902 449 459 (SPAIN) / (+34) 937 452 919 (metu saka Spanyol)
Vial Sant Jordi, s/n
08232 – Viladecavalls (Barcelona)
Telpon: (+34) 937 452 900 – Fax: (+34) 937 452 914
e-mail: sat@circutor.com