Circutor -logoCircutor CVM C4 Multi Function Panel Mount Multimeter-CVM-C4
POWER ANALYZER

CVM-C4 Multi Function Panel Mount Multimeter

Circutor -icon

 Terminal connections designations
1 L/+,  Power supply
2 N/-,  Power supply
4 I1 S1, Current input L1
5 I1 S2,  Current input L1
6 I2 S1,  Current input L2
7 I2 S2,  Current input L2
8 I3 S1,  Current input L3
9 I3 S2,  Current input L3
11 U1,  Voltage input L1
12 U2,  Voltage input L2
13 U3,  Voltage input L3
14 UN / U2, Voltage input N/L2
15 RO1,  Relay output 1 (Common)
16  Relay output 1 (NO) / Relay output 2 (Common)
17 RO2,  Relay output 2 (NO)
47 +,  Impulse output
48 -, Impulse output
49 +,  Impulse output
50 -, Impulse output
58 A, RS-485
59 B, RS-485
70 C, Common digital inputs
71 DI1,  Digital input 1
72 DI2,  Digital input 2

Connections

Measuring three-phase networks with a 4-wire connection.

Circutor CVM C4 Multi Function Panel Mount Multimeter-fig1

Measuring three-phase networks with a 3-wire connection.

Circutor CVM C4 Multi Function Panel Mount Multimeter-fig2

Circutor CVM C4 Multi Function Panel Mount Multimeter-fig3

Circutor CVM C4 Multi Function Panel Mount Multimeter-fig4

This manual is a CVM-C4 installation guide. For further information, please download the full manual from the CIRCUTOR web site: www.circutor.com

Warning icon IMPORTANT!
The device must be disconnected from its power supply sources (power supply and measurement) before undertaking any installation, repair or handling operations on the device’s connections. Contact the after-sales service if you suspect that there is an operational fault in the device The device has been designed for easy replacement in case of malfunction.
The manufacturer of the device is not responsible for any damage resulting from failure by the user or installer to heed the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of non-original products or accessories or those made by other manufacturers.

DESCRIPTION

The CVM-C4 is a device that measures, calculates and displays the main electrical parameters in single-phase and three-phase mains.
The device has RS-485 communications, relay outputs, impulse outputs and digital inputs.
Current measurement is indirectly carried out by /5A or /1A transformers.

INSTALLATION

The device should be installed inside an electric panel or enclosure, and panel-mounted.

Warning icon IMPORTANT!
Take into account that when the device is connected, the terminals may be hazardous to the touch, and opening the covers or removing elements may provide access to parts that are dangerous to the touch. Do not use the device until it is fully installed

To install it, take the following steps:

  1. Make a cut in the panel, according to the dimensions in Figure 1.
  2. From outside, insert the device into the panel cut-out (Figure 2).
  3. Fully insert the device and fasten it securely by using the spring (Figure 3)

CONNECTION

The device should be connected to a power circuit protected by a fuse with a maximum rated current of 0.25 A.
If the voltage to be measured is higher than the rated input voltage, a voltage transformer must be connected to the device.
If more than one device is connected to the current transformer, they must be connected in series.
Before disconnecting the current measurement connection cables, be sure to disconnect the transformer’s primary cables and bridge the secondary.
The device can operate in three-wire, three-phase mode or four-wire, three-phase mode, the user selecting the corresponding connection mode according to the installation. An incorrect type of connection or an error in phase sequence may cause measurement errors.

Technical features

AC Power supply”
Rated voltage 80 … 270 V –
Frequency 50/60 Hz
Consumption 6 … 18 VA
Installation category CAT III 300V
DC Power supply'”
Rated voltage 80 270 V …=_ 18 … 36 V
Consumption 1.5 1.8 W 1.8 … 2.2 W
Installation category CAT III 300V
Voltage measurement circuit
Rated voltage (Un) 100 277 V, vc, – t 8%
Frequency measurement margin 45 … 65 Hz
Overload 1.2Un continuo / continuous,
2Un instantaneo / instantaneous (1min)
Consumption < 0.2 VA (por fase / per phase)
Impedance > 1.7 MO
Installation category CAT III 300V
Current measurement circuit
Rated current (In) 1 A/ 5 A –
Frequency measurement margin 45 … 65 Hz
Overload 1.2In continuo / continuous,
10In ins tantaneo / instantaneous (55)
Consumption < 0.2 VA (por fase / per phase)
Impedance < 20 mO
Installation category CAT III 300V
Accu racy
Voltage measurement 0.2 % t 1 digito / digit
Current measurement 0.2 % t 1 digito / digit
Active and Reactive Power measurement 0.5 % t 2 digitos / digits
Relays outputs
Quantity 2
Contact capacity (resistive) CA/AC: 5A / 250V – , CC/DC: 5A / 30V -=
Max. voltage open contacts 277V – / 30V _..=
Maximum current 5 A
Maximum switching power 1385 VA/ 150 W
Electrical life (250V -/ 5A) 11105
Digital inputs
Quantity 2
Type Contacto libre de potencial / Potential free contact
Insulation 3.5 kV rms
Maximum short-circuit current 4 mA
Maximum voltage in open circuit 30 V
Impulse output
Type Pulso pasivo / Passive pulse
Maximum voltage 27 V
Maximum current 27 mA
Maximum frequency 10 Hz
Minimum pulse width 80 mA
RS-485 communications
Communications protocol Mod bus RTU
Baud rate 2400- 4800 – 9600 -19200 bps
Data bits 8
Stop bits 1- 2
Parity sin, par, impar /without, even, odd
User interface
Display LCD
Keyboard 3 teclas / keys
Environmental features
Operating temperature -10°C… +60°C
Storage temperature -20°C … +70°C
Relative humidity 5 … 95%
Maximum altitude 2000 m
Protection degree Frontal / Front: IP54, Posterior/ Rear case: IP20
Pollution degree
Mechanical features
filthening II Circutor -icon1 Circutor -icon2 Circutor -icon3
1,2, 4 … 9,11 …18, 47 …50, 58, 59,70 … 72 2.5 mm? 0.5 Nm Plano / Flat (SZS 0.6×3.5)
Dimensions 96 x 96 x 41.5 mm
Weight 265 g.
Enclosure pc + abs

Standers
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61010-1

Depending on model: 

 Key
Circutor -icon4 Previous screen
Circutor -icon5 Next screen
Circutor -icon6 Long keystroke ( >3s): Enter in configuration menu

Note: Device images are for illustrative purposes only and may differ from the actual device.

Technical service

CIRCUTOR SAT: 902 449 459 (SPAIN) / (+34) 937 452 919 (out of Spain)
Vial Sant Jordi, s/n
08232 – Viladecavalls (Barcelona)
Tel: (+34) 937 452 900 – Fax: (+34) 937 452 914
e-mail : sat@circutor.com
M267A01-60-21B