Logo Altronix KabSeri ACMS 12
Sub-Majelis
Akses Kontrol Daya
Guide Instalasi

ACMS12 Series Sub Majelis Akses Pengontrol Daya

Model kalebu:
ACMS12
– Rolas (12) Fuse Protected Output
ACMS12CB
– Rolas (12) PTC Protected Output

Swaraview:

Altronix ACMS12 / ACMS12CB minangka sub-assemblies sing dirancang kanggo digunakake ing Altronix BC300, BC400, Trove1, Trove2 lan Trove3 enclosures lan unit daya maksimal. Desain input dual Akses Power Controller ngidini daya setir saka rong (2) vol rendah independentage 12 utawa 24VDC Altronix daya Penyetor kanggo rolas (12) sekring kontrol independen (ACMS12) utawa PTC (ACMS12CB) output dilindhungi. Output diaktifake dening sink kolektor mbukak, biasane mbukak (NO), biasane ditutup (NC) input pemicu garing, utawa output udan saka Sistem Kontrol Akses, Card Reader, Keypad, Push Button, PIR, etc. ACMS12(CB) bakal daya rute kanggo macem-macem piranti hardware kontrol akses kalebu Mag Kunci, Electric Strikes, Magnetic Door Holders, etc Output bakal operate ing mode Gagal-Aman utawa Gagal-Aman. Antarmuka FACP mbisakake Egress Darurat, Pemantauan Alarm, utawa bisa digunakake kanggo micu piranti tambahan liyane. Fitur pedhot weker geni bisa dipilih kanthi individu kanggo salah siji utawa kabeh saka rolas (12) output. Konektor spade ngijini sampeyan kanggo daya chain daisy kanggo sawetara ACMS12 (CB) modul. Fitur iki ngidini sampeyan nyebarake daya liwat output liyane kanggo sistem sing luwih gedhe.

Spesifikasi:

Vol inputtage:

  • Input 1: 12 utawa 24VDC Altronix sumber daya.
  • Input 2: 12 utawa 24VDC Altronix sumber daya utawa salah siji 5 utawa 12VDC saka VR6 Regulator.
  • Input saiki:
    ACMS12: Total 20A
    ACMS12CB: total 16A.
  • Rolas (12) input pemicu sing bisa dipilih kanthi mandiri:
    a) Input biasane mbukak (NO) (kontak garing).
    b) Input normally closed (NC) (kontak kering).
    c) Input sink kolektor terbuka.
    d) Wet Input (5VDC - 24VDC) karo 10K resistor
    e) Sembarang kombinasi saka ndhuwur.

Output:

  • ACMS12: Output sing dilindhungi sekring dirating @ 2.5A saben output, ora winates daya.
    Total output maks. 20A
    Waca Input/Output Voltage Rating, p. 7.
    ACMS12CB: Output sing dilindhungi PTC dirating @ 2A saben output, Kelas 2 winates daya.
    Total output maks. 16A
    Aja ngluwihi rating sumber daya individu.
    Waca Input/Output Voltage Rating, p. 7.
    Total arus output ngirim ora ngluwihi max. rating saiki saka sumber daya dipunginaaken ing saben input.
    Waca Output Maksimum saka Altronix Power Supplies.
  • Rolas (12) output daya Gagal-Aman utawa Gagal-Aman sing bisa dipilih kanthi mandiri.
  • Output individu bisa disetel menyang posisi OFF kanggo servis (jumper output disetel menyang posisi tengah).
  • Output bisa dipilih kanggo tindakake daya Input 1 utawa Input 2. Output voltage saben output padha karo vol inputtage saka input sing dipilih.
    Waca Input/Output Voltage Rating, p. 7.
  • Penindasan mundhak.

Putus Alarm Kebakaran:

  • Pedhot Alarm Kebakaran (latching utawa non-latching) bisa dipilih kanthi individu kanggo salah siji utawa kabeh saka rolas (12) output.
    Opsi input pedhot Alarm Kebakaran:
    a) Biasane mbukak [NO] utawa biasane ditutup [NC] input kontak garing. Input pembalikan polaritas saka sirkuit sinyal FACP.
  • Input FACP WET dirating 5-30VDC 7mA.
  • FACP input EOL mbutuhake 10K end of line resistor.
  • Relay output FACP [NC]:
    Salah siji FACP garing NC output utawa
    Sambungan EOL internal menyang ACMS12 (CB) sabanjure.

ACMS12 Fuse Rating:

  • Sekring input utama dirating 15A / 32V saben.
  • Sekring output dirating 3A / 32V.

ACMS12CB PTC Rating:

  • PTC input utama dirating 9A saben.
  • Output PTC dirating 2.5A.

Indikator LED:

  • LED biru nuduhake pedhot FACP dipicu.
  • individu voltage LED nuduhake 12VDC (Ijo) utawa 24VDC (Abang).

lingkungan:

  • Suhu operasi: 0ºC nganti 49ºC lingkungan.
  • Kelembapan: 20 nganti 93%, non-kondensasi.

Mekanik:

  • Ukuran Papan (W x L x H kira-kira): 7.3" x 4.1" x 1.25" (185.4mm x 104.1mm x 31.8mm)
  • Bobot produk (kira-kira): 0.7 lb. (0.32 kg).
  • Bobot pangiriman (kira-kira): 0.95 lb. (0.43 kg).

Instruksi Instalasi:

Cara pengkabelan kudu sesuai karo Kode Listrik Nasional NFPA 70/NFPA 72/ ANSI / Kode Listrik Kanada / CAN/ULC-S524/ULC-S527/ULC-S537, lan kabeh kode lan panguwasa lokal sing nduweni yurisdiksi. Produk kasebut mung kanggo panggunaan garing ing njero ruangan.
Waca Instruksi Instalasi Sub-Majelis kanggo masang Rev. MS050913.
Kasebut kanthi teliti manehview:

Diagnostik LED (kaca 5) Diagram Aplikasi Khas (kaca 6)
Tabel Identifikasi Terminal (kaca 5) Diagram Hook-up (kaca 9-10)

Instalasi:

  1. Pasang ACMS12/ACMS12CB ing lokasi sing dikarepake. Nalika masang ACMS12 / ACMS12CB piyambak, gunakake spacer wadon / wadon (kasedhiya). Nalika soyo tambah karo pilihan VR6 voltage regulator, nggunakake spacer wadon / wadon (kasedhiya) antarane ACMS12 / ACMS12CB lan VR6 (Fig. 6, pg. 6).
    Pasang ACMS12/ACMS12CB menyang spacer nggunakake 5/16 "sekrup sirah pan (kasedhiya).
    Sambungan:
  2. Priksa manawa kabeh jumper output [OUT1] – [OUT12] diselehake ing posisi OFF (tengah).
  3. Sambungake vol rendahtage Sumber daya DC menyang terminal sing ditandhani [+ PWR1 –], [+ PWR2 –]
  4. Setel saben output [OUT1] – [OUT12] kanggo rute daya saka Power Supply 1 utawa 2 (Fig. 1, pg. 3).Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - SambunganCathetan: Ukur output voltage sadurunge nyambungake piranti.
    Iki mbantu nyegah karusakan potensial.
  5. Pateni daya sadurunge nyambungake piranti.
    Operasi:
    penting: Input / Output lan ngalih sing diklompokaké (Fig. 3, pg. 4).
  6. Pilihan Output: ACMS12(CB) bakal nyedhiyakake nganti rolas (12) output daya sing diuripake
    Output Daya Ngalih:
    Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - OutputSambungake input piranti sing didhukung menyang terminal sing ditandhani [– Output1 +] liwat [– Output12 +] kanthi ati-ati ngamati polaritas.
    • Kanggo operasi Gagal-Aman geser output kontrol logika DIP ngalih ditandhani [Output] kanggo input cocog menyang posisi ON (Fig. 3, tengen).
    • Kanggo operasi Gagal-Aman geser output kontrol logika DIP ngalih ditandhani [Output] kanggo input cocog menyang posisi OFF (Fig. 3, tengen).
  7. Uripake daya utama sawise kabeh piranti disambungake.
    penting: Input / Output lan ngalih sing diklompokaké (Fig. 3, pg. 4).
  8. Pilihan Pemicu Input:
    Cathetan: Yen pedhot Fire Alarm ora digunakake, sambungake resistor 10K Ohm menyang terminal sing ditandhani [GND lan EOL], plus sambungake jumper menyang terminal sing ditandhani [GND, RST].
    Input Normally Open (NO):
    Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - Logika INPGeser input kontrol logika ngalih DIP ditandhani [NO-NC] kanggo input cocog menyang posisi OFF (Fig. 4, tengen). Sambungake kabel menyang terminal sing ditandhani [+ INP1 –] menyang [+ INP12 ].
    Input Biasane Ditutup (NC):
    Geser input logika kontrol DIP ngalih ditandhani [NO-NC] kanggo input cocog menyang posisi ON (Fig. 4, tengen). Sambungake kabel menyang terminal sing ditandhani [+ INP1 –] menyang [+ INP12 –].
    Bukak Kolektor Sink Input:
    Sambungake input sink kolektor mbukak menyang terminal sing ditandhani [+ INP1 -] menyang [+ INP12 -].
    Wetan (Voltage) Konfigurasi Input:
    Kasebut kanthi teliti, mirsani polaritas, sambungake voltagkabel pemicu input lan resistor 10K sing diwenehake menyang terminal sing ditandhani [+ INP1 –] kanggo [+ INP12 –].
    Yen nglamar voltage kanggo pemicu input - nyetel saklar INP Logic sing cocog menyang posisi "ON".
    Yen njabut voltage kanggo pemicu input - nyetel saklar INP Logic sing cocog menyang posisi "OFF".
    Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - Konfigurasi Input
  9. Pilihan Antarmuka Alarm Kebakaran:
    Altronix ACMS12 Series Sub Majelis Akses Kontrol Daya - FACPInput [NC] sing biasane ditutup, biasane mbukak [NO] utawa input pembalikan polaritas saka sirkuit sinyal FACP bakal micu output sing dipilih.
    Kanggo ngaktifake FACP Disconnect kanggo logika kontrol output geser output
    DIP ngalih ditandhani [FACP] kanggo output cocog ON (Fig. 5, tengen).
    Kanggo mateni FACP Disconnect kanggo output geser output logika kontrol
    DIP ngalih ditandhani [FACP] kanggo cocog output OFF (Fig. 5, tengen).
    Biasane mbukak Input:
    Sambungake relay FACP lan resistor 10K kanthi sejajar karo terminal sing ditandhani [GND] lan [EOL].
    Input Biasane Ditutup:
    Sambungake relay FACP lan resistor 10K kanthi seri kanthi terminal sing ditandhani [GND] lan [EOL].
    Pemicu input Sirkuit Sinyal FACP:
    Sambungake positif (+) lan negatif (-) saka output sirkuit sinyal FACP menyang terminal sing ditandhani [+ FACP –]. Sambungake FACP EOL menyang terminal sing ditandhani [+ RET –] (polaritas dirujuk ing kondisi weker).
    Putus Alarm Kebakaran Non-Latching:
    Sambungake jumper menyang terminal sing ditandhani [GND, RST].
    Latching Alarm Kebakaran Putus sambungan:
    Sambungake switch reset NO sing biasane mbukak menyang terminal sing ditandhani [GND, RST].
  10. FACP Kering NC output:
    Nalika daisy-chaining sinyal weker Fire antarane loro Papan, nyambung [NC & C] pisanan ACMS12(CB) kanggo [GND & EOL] saka ACMS12 sabanjuré (CB). Selehake jumper EOL ing tengah lan pin ngisor.
    Nalika nggunakake output iki minangka kontak garing NC Panggonan EOL jumper ing tengah lan pin ndhuwur.

Daisy Chaining Loro (2) ACMS12(CB)
Kontrol Daya Akses Output Ganda:
Gunakake kabel UL Listed 18 AWG utawa luwih gedhe sing dilengkapi 1/4 "terminal sambungan cepet sing Dikenal UL sing dirating kanggo vol sing tepattage / saiki kanggo kabeh sambungan jumper.

  1. Sambungake lug spade papan ACMS12(CB) pisanan sing ditandhani [PWR1 +] menyang terminal papan ACMS12(CB) kapindho sing ditandhani [+ PWR1].
  2. Sambungake lug spade papan ACMS12(CB) pisanan sing ditandhani [COM –] menyang terminal papan ACMS12(CB) kapindho sing ditandhani [PWR1 –].
  3. Sambungake lug spade papan ACMS12(CB) pisanan sing ditandhani [PWR2 +] menyang terminal papan ACMS12(CB) kapindho sing ditandhani [+ PWR2].

Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - Pengontrol Daya

Diagnostik LED:

ACMS12 lan ACMS12CB Akses Power Controller

LED ON OFF
LED 1- LED 12 (Abang) Output relay (s) de-energized. Output relay (s) energized.
FACP Input FACP dipicu (kondisi weker). FACP normal (kondisi non-alarm).
Output Ijo 1-12 12VDC
Output abang 1-12 24VDC

Tabel Identifikasi Terminal:
ACMS12 lan ACMS12CB Akses Power Controller

Katrangan Terminal Fungsi/Deskripsi
+ PWR1 — 12 utawa 24 VDC saka sumber daya.
+ PWR2 — 12 utawa 24 VDC saka sumber daya utawa salah siji 5 utawa 12 VDC saka VR6 regulator.
+ INP1 - liwat
+ INP12 -
Rolas (12) dikontrol kanthi mandiri Biasane Bukak (NO), Biasane Ditutup (NC), Open Collector Sink utawa Pemicu Input Basah.
C, NC FACP Garing NC output utawa sambungan EOL internal kanggo ACMS12 sabanjuré (CB).
GND, RST antarmuka FACP latching utawa non-latching. Ora ana input garing. Kelas 2 winates daya.
Disingkat kanggo antarmuka FACP non-latching utawa Latch FACP reset.
GND, EOL Terminal Input FACP Diawasi EOL kanggo fungsi FACP pembalikan polaritas.
Kelas 2 winates daya.
— F, + F, — R, + R Input Sirkuit Sinyal FACP lan terminal Bali. Kelas 2 winates daya.
- Output 1 + liwat
- Output 12 +
Rolas (12) output kontrol independen sing bisa dipilih (Gagal-Aman utawa Gagal-Aman).

Diagram Aplikasi Umum:

Altronix ACMS12 Series Sub Assembly Kontrol Daya Akses - Diagram Aplikasi KhasInput / Output Voltage Rating

Vol inputtage lan Sumber Output Voltage Rating
5VDC (saka VR6 regulator) 5VDC
12V (saka VR6 regulator) 12VDC
12VDC (saka sumber daya eksternal) 11.7-12VDC
24VDC (saka sumber daya eksternal) 23.7-24VDC

Output Maksimum Altronix Power Supplies:

UL Listed utawa Diakoni Power Supply Output Voltage Setelan Maks. Output Saiki
AL400ULXB2 / eFlow4NB 12VDC utawa 24VDC 4A
AL600ULXB / eFlow6NB 12VDC utawa 24VDC 6A
AL1012ULXB / eFlow102NB 12VDC 10A
AL1024ULXB2 / eFlow104NB 24VDC 10A
VR6 5VDC utawa 12VDC 6A

VR6 – Voltage Regulator

Swaraview:
VR6 voltage regulator ngowahi input 24VDC menyang output 5VDC utawa 12VDC diatur. Iki dirancang khusus kanggo nggarap ACMS12(CB) kanthi ngidini masang Kontrol Daya Akses langsung ing ndhuwur VR6 kanggo ngirit ruang pager lan nyederhanakake sambungan. Waca Pandhuan Instalasi VR6 Rev. 050517.

Spesifikasi:

Daya Input / Output:

  • Input: 24VDC @ 1.75A - Output: 5VDC @ 6A.
  • Input: 24VDC @ 3.5A - Output: 12VDC @ 6A.

Output:

  • 5VDC utawa 12VDC diatur output.
  • Rating output 6A maks.
  • Penindasan mundhak.

Indikator LED:

  • Input lan output LED.

Listrik:

  • Suhu operasi: 0ºC nganti 49ºC lingkungan.
  • Kelembapan: 20 nganti 93%, non-kondensasi.

Mekanik:

  • Bobot produk (kira-kira): 0.4 lb. (0.18 kg).
  • Bobot pangiriman (kira-kira): 0.5 lb. (0.23 kg).

Nyambungake ACMS12(CB) menyang VR6:

  1. Cepet spacer lanang/wadon (kasedhiya) menyang pem sing cocog karo pola bolongan kanggo VR6 ing lokasi / pager sing dikarepake. Gunakake spacer logam kanggo bolongan soyo tambah karo pola star (Fig. 7a, pg. 8).
  2. Plug-in konektor 8-pin lanang kanggo wadhah 8-pin wadon ing papan VR6 (Fig. 7, pg. 8).
  3. Cepet spacer wadon / wadon kanggo spacer lanang / wadon (Fig. 7, pg. 8).
    Gunakake spacers logam liwat bolongan soyo tambah karo pola star (Fig. 7a, pg. 8).
  4. Nyelarasake 8-pin konektor lanang karo wadhah wadon saka ACMS12 / ACMS12CB, banjur masang Papan kanggo spacers nggenepi kasedhiya 5/16 "ngawut-awut sirah pan (Fig. 7, pg. 8).
  5. Sambungake sumber daya 24VDC kanggo terminal ditandhani [+ PWR1 -] saka ACMS12 / ACMS12CB (Fig. 8, pg. 7).
  6. Pilih output voltage 5VDC utawa 12VDC nggunakake switch [S1] ing VR6.
  7. Rampungake langkah 4-10 (kaca 3-4).Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - Nyambungake ACMS

Diagram Hook-Up:

Gambar 8 - Daisy-chaining siji utawa luwih ACMS12 unit.
EOL Jumper [EOL JMP] kudu diinstal ing posisi EOL. Non-Latching.Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - DiagramGambar 9 - Daisy-chaining siji utawa luwih ACMS12 unit.
EOL Jumper [EOL JMP] kudu diinstal ing posisi EOL. Latching Single Reset.Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 2Gambar 10 - Daisy chaining siji utawa luwih ACMS12 unit.
EOL Jumper [EOL JMP] kudu diinstal ing posisi EOL. Latching Reset Individu.Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 3Gambar 10 - Input pembalikan polaritas saka output sirkuit sinyal FACP (polaritas dirujuk ing kondisi weker).
Non-Latching.Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 4Gambar 11 - Input pembalikan polaritas saka output sirkuit sinyal FACP (polaritas dirujuk ing kondisi weker).
Ngunci.Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 5Gambar 12 - Input pemicu Biasane Ditutup
(Non-Latching).Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 6Gambar 13 - Input pemicu Biasane Ditutup
(Ngempet).Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 7Gambar 14 - Biasane mbukak input pemicu
(Non-Latching).Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 8Gambar 15 - Biasane mbukak input pemicu
(Ngempet).Altronix ACMS12 Series Pengontrol Daya Akses Sub Majelis - Diagram 9Cathetan: -

Altronix ora tanggung jawab kanggo kesalahan tipografi.
140 58th Street, Brooklyn, New York 11220 USA
telpon: 718-567-8181
fax: 718-567-9056
websitus: www.altronix.com
e-mail: info@altronix.com
Garansi seumur hidup
IIACMS12/ACMS12CB I01VAltronix ACMS12 Series Sub Majelis Akses Pengontrol Daya - SimbolACMS12/CB Pedoman Instalasi Sub-Majelis

Dokumen / Sumber Daya

Altronix ACMS12 Series Sub Majelis Akses Pengontrol Daya [pdf] Pandhuan Instalasi
ACMS12, ACMS12CB, ACMS12 Series Pengontrol Daya Akses Sub Majelis, Pengontrol Daya Akses Sub Majelis, Pengontrol Daya Akses, Kontroler Daya

Referensi

Ninggalake komentar

Alamat email sampeyan ora bakal diterbitake. Kolom sing dibutuhake ditandhani *