User Manual for
EV200 series Variable Frequency Drive

Outsize

STEPPERONLINE EV200 Series Variable Frequency Drive

Voltage Model type Power(kW) Install size(mm) outsize(mm) Install hole
A B W H D
Single phase 220V EV200-0400G-S2 0. 4  

 

60

 

 

129

 

 

73

 

 

143

 

 

112. 6

 

 

Ф4.4

EV200-0750G-S2 0. 75
EV200-1500G-S2 1. 5
EV200-2200G-S2 2. 2
 

Three phase 380V

EV200-0750G-T3 0. 75
EV200-1500G-T3 1. 5
EV200-2200G-T3 2. 2
EV200-3700G-T3 3. 7 73 168 85. 5 180 116. 4 Ф4.4
EV200-5500G-T3 5. 5

Standard Wiring Diagram

STEPPERONLINE EV200 Series Variable Frequency Drive - Diagram

Wiring instrucons

Terminal symbol Function description
E Grounding terminal
L1、L3 Connect to the power grid single-phase (220Vac) AC power supply
L1、L2、L3 Connected to the grid three-phase (380Vac) AC power supply
U,V,W Connect a three-phase AC motor
B1 Filter capacitor DC side voltage positive terminal
B2 A DC braking resistor can be connected directly to B1

Technical specificaons

Item Specification
Highest frequency Vector control: 0~500Hz;     V/F control: 0~500Hz
Carrier frequency 0.8kHz ~ 12kHz   Carrier frequency can be adjusted automatically

according to temperature characteristics

Input frequency resolution Digital setting: 0.01Hz      Analog setting: maximum frequency × 0.025%
control mode without PG Vector(SVC),Feedback vector(FVC)   and V/F control
Start torque G type: 0.5Hz/150%(SVC);0Hz/180%(FVC) P type: 0.5Hz/100%
Speed range 1:100 (SVC) 1:1000 (FVC)
Speed control accuracy ±0.5%(SVC) ±0.02%(FVC)
Torque control accuracy ±5%(FVC)
Overload capacity G type: 150% rated current 60sec; 180% rated current 3sec

 Funcon Parameters Table

When PP-00 is set as a non-zero value, that is, the parameter protecon password is set. In the funcon parameter and the user changes the parameter mode, the parameter menu must enter the password correctly. It can cancel the password protecon funcon by seng PP-00 as 0.
The parameter menu in user-defined parameter mode is not password protected.
Group P and A include basic funcon parameters, group d includes the monitoring funcon parameters. The symbols in the funcon code table are described as follows:
“☆” : it is possible to modify the parameter when the drive in the stop or in the run status;
“★”: impossible;
“●”:the parameter is the actual measured value and can not be modified.
“*” : the parameter is a “factory parameter”, can be set only by the manufacturer, prohibit the user to operate.

Function Code Name Setting Range Default Modify
P0 Group: Basic Function
P0-01 Motor 1 control mode 0:   No   speed   sensor   vector   control   (SVC) 1: Speed sensor vector control (FVC) 2: V/F control 2
P0-02 Command source selection 0: Operation panel instruction channel 1: Terminal command channel 2:communication command channel 0
 

 

 

P0-03

 

 

 

Main frequency reference setting A channel selection

0: digital setting (preset frequency P0-08, UP/DOWN can be modified, power is not memory) 1: digital setting (preset frequency P0-08, UP/DOWN can be modified, power-down memory 2: AI1 (Note: J4 jumper in the PANEL and AI1 connected to the keyboard potentiometer input, PORT and AI1 connected to the external terminal AI1 input)          3: Ai2 4: Ai3

5:High-speed       pulse       Inputsetting       (S5) 6: multi-segment instructions      7: Simple PLC 8: PID 9: communication given 10: Reserved

 

 

 

2

 

 

 

 

 

P0-04

Auxiliary frequency source B command input selection With P0-03 (main frequency source A instruction input selection)  

0

P0-05 Auxiliay frequency source B Reference object selection 0:relative to maximum frequency 1: relative to frequency source A 0
P0-06 Auxiliary frequency source B command range 0%~150% 100%
 

 

 

 

P0-07

 

 

 

 

Frequency source combination mode selection

Bit:              frequency               source              selection 0:            Main             frequency             source             A 1: main and auxiliary operation results (operation relationship              determined              by              ten) 2: Main frequency source A   and   auxiliary frequency                 source                 B                 switch 3: Main frequency source A and master and slave operation                         result                          switching 4: auxiliary frequency source B and master and slave            operation             result             switching Ten: frequency source main and auxiliary operation relationship

0:   main   +   auxiliary   1:   main   –   auxiliary 2: the two maximum 3: the two minimum

 

 

 

 

00

 

 

 

 

 

P0-08 Preset frequency 0.00Hz~max(P0-10)   frequency 50.00Hz
P0-09 Running direction 0: same direction      1: opposite direction 0
P0-10 Max.output frequency 50.00Hz~500.00Hz 50.00Hz
P0-11 Setting channel of frequency upper limit 0: P0-12 is set       1:AI1(Note:J6jump)          2: AI2      3: AI3            4: High-speed pulse setting (S5)

5: communication given

0
P0-12 Frequency reference upper limit Upper limit P0-10 P0-14~max frequency 50.00Hz
P0-13 Frequency reference upper limit offset 0.00Hz~frequency max. P0-10 0.00Hz
P0-14 Frequency Reference lower limit 0.00Hz~frequency upper limit P0-12 0.00Hz
P0-15 Carrier frequency 0.8KHz~12.0KHz Model dependent
P0-16 Carrier frequency adjusted with temperature 0: Disabled 1: Enabled 1
P0-17 Acceleration time 1 0.00s~65000s Model dependent
P0-18 Deceleration time 1 0.00s~65000s Model dependent
P0-19 Acceleration/ Deceleration time unit 0: 1s      1: 0.1s    2: 0.01s 1
 

P0-21

Frequency offset of auxiliary frequency setting channel for main and auxiliary calculation  

0.00Hz~max.frequency    P0-10

 

0.00Hz

 

P0-22 Frequency reference resolution 2: 0.01Hz 2
P0-23 Retentive of digital setting frequency upon stop 0: do not remember 1: memory 1
P0-24 Motor parameter group selection 0: 1st motor parameter 1: 2nd motor parameter 0
P0-25 Acceleration/ Deceleration time base frequency 0:maximum (P0-10) 1:    Set    frequency 2: 100Hz frequency 0
P0-26 Base frequency for UP/DOW modification during running 0: Run frequency 1: Set frequency 0
 

 

 

P0-27

 

 

The run command is tied to the main frequency source A command selection

Bit: Operation panel command Bind frequency source   selection     0:                   no                   binding 1: Digital setting frequency 2: AI1 (Note: J6 jumper) 3: AI2 4: AI3 5: High-speed pulse input setting (S5) 6:   multi-speed       7:       Simple       PLC         8:       PID 9:                         communication                         given Ten: Terminal Command Binding Frequency Source Selection                                                               Hundreds: communication command binding frequency source selection  

 

 

0

 

 

 

P0-28 Serial port communication protocol 0: Modbus communication 0
P1 Group: Motor 1 Parameters
P1-00 Motor type selection 0:     ordinary     asynchronous     motor 1: Variable frequency asynchronous motor 0
P1-01 Rated motor power 0.1KW~1000.0KW Model dependent
P1-02 Rated motor voltage 1V~2000V Model dependent
P1-03 Rated motor current 0.01 to 655.35A (AC drive power ≤ 55 KW)

0.1 to 6553.5A (AC drive power > 55 KW)

Model dependent
P1-04 Rated motor frequency 0.01Hz~max. frequency Model dependent
P1-05 Rated motor speed 1rpm~65535rpm Model dependent
P1-06 Stator resistance 0.001Ω~65.535Ω(AC drive power≤55KW) 0.0001Ω~6.5535Ω(AC drive power>55KW) Auto- tuning dependent
P1-07 Rotor resistance 0.001Ω~65.535Ω(AC drive power≤55KW) 0.0001Ω~6.5535Ω(AC drive power>55KW) Auto- tuning dependent
P1-08 Leakage inductive reactance 0.01mH~655.35mH(AC drive power≤55KW) 0.001mH~65.535mH

( AC drive power>55KW)

Auto- tuning dependent
P1-09 Mutual inductive reactance 0.1mH~6553.5mH(AC drive power≤55KW) 0.01mH~655.35mH(AC drive power>55KW) Auto- tuning dependent
P1-10 No-load current 0.01A~P1-03(AC drive power≤55KW) 0.1A~P1-03(AC drive power>55KW) 0.1A~P1-03(AC drive power>55KW) Auto- tuning dependent
P1-27 Encoder pulses per revolution 1~65535 1024
P1-28 Encoder type 0: ABZ incremental encoder 2: Resolver 0
P1-30 A/B phase sequence of ABZ incremental encoder 0: Forward 1: Reserve 0
P1-34 Number of pole pairs of resolver 1~65535 1
P1-36 Encoder wire-break fault detection time 0.0: no operation 0.1s~10.0s 0.0s
 

 

P1-37

 

Motor auto-tuning method selection

0:                           no                           operation 1: Asynchronous machine static part of the parameters                of                self-learning 2: asynchronous machine dynamic complete    self-learning     3: asynchronous machine static complete self-learning  

 

0

 

 

P2 Group: Vector Control   Parameters
P2-00 Speed loop proportional gain 1 1~100 30
P2-01 Speed loop integral time 1 0.01s~10.00s 0.50s
P2-02 Switchover frequency 1 0.00~P2-05 5.00Hz
P2-03 Speed loop proportional gain 2 1~100 20
P2-04 Speed loop integral time 2 0.01s~10.00s 1.01.00s0s
P2-05 Switchover frequency 2 P2-02~max frequency (P0-10) 10.00Hz
P2-06 SVC/FVC slip compensation gain 50%~200% 100%
P2-07 SVC Speed feedback filter time constant 0.000s~0.100s 0.015s
 

P2-09

 

Torque upper limit command channel selection under speed control

0: function code P2-10 setting 1: AI1 2: AI2      3: AI3

4: high-speed   pulse   input   setting   (S5) 5: communication given 6: MIN (AI1, AI2) 7: MAX (AI1, AI2)

1-7 option full scale corresponds to P2-10

 

0

 

P2-10 Digital setting of torque limit in speed control 0.0%~200.0% 150.0%
 

 

 

P2-11

 

 

Torque limit source in speed control                                    (in regenerative state)

0: Function code P2-12 setting (no distinction between electric and power generation)         1: AI1 2: AI2 3: AI3 4:High-speed     pulse      input      setting 5:               communication                given 6: MIN (AI1, Ai2) 7: MAX (AI1, AI2)

8: Function code P2-12 setting

1-7 The full scale of the option corresponds to P2-12

 

 

 

0

 

 

 

P2-12 Digital setting of torque limit in speed control (in regenerative state) 0.0%~200.0% 150.0%
P2-13 Excitation adjustment proportional gain 0~60000 2000
P2-14 Excitation adjustment integral gain 0~60000 1300
P2-15 Torque adjustment proportional gain 0~60000 2000
P2-16 Torque adjustment integral gain 0~60000 1300
P2-17 Speed loop integral separation selection 0: Disabled 1: Enabled 0
P2-20 Max output voltage
P2-21 Max. torque coefficient of field weakening area 50~200% 100%
P2-22 Regenerative power limit selection 0: Disabled         1: Enabled 0
P2-23 Regenerative power limit 0~200% Model dependent
P3 Group: V/F Control Parameters
 

P3-00

 

V/F curve setting

0: Straight line V/F 1: multipoint V/F 2: square V/F        3: 1.2   Power   V/F 4: 1.4 Power V/F        6: 1.6 Power V/F 8:   1.8   power   V/F       9:   Reserved 10: VF complete separation mode 11: VF semi-separation mode  

0

 

P3-01 Torque boost 0.0%: (Ineffective) 0.1%~30.0% Model dependent  
P3-02 Cut-off frequency of torque boost 0.00Hz~max. frequency 50.00Hz
P3-03 Multi-point V/F frequency1 0.00Hz~P3-05 0.00Hz
P3-04 Multi-point V/F voltage 1 0.0%~100.0% 0.0%
P3-05 Multi-point V/F frequency 2 P3-03~P3-07 0.00Hz
P3-06 Multi-point V/F voltage 2 0.0%~100.0% 0.0%
P3-07 Multi-point V/F frequency 3 P3-05~rated motor frequency (P1-04) 0.00Hz
P3-08 Multi-point V/F voltage 3 0.0%~100.0% 0.0%
P3-09 Slip compensation gain
P3-10 V/F over-excitation gain 0~200 64
P3-11 V/F oscillation suppression gain 0~100 40
 

 

P3-13

 

 

Voltage source for V/F separation

0: digital setting (P3-14) 1: AI1 (Note: J6 jumper) 2: AI2 3: AI3

4:   High-speed    pulse    input    setting    (S5) 5: multi-segment instructions 6: Simple PLC 7:    PID        8:    communication    given Note: 100.0% corresponds to the motor

rated voltage

 

 

0

 

 

P3-14 Digital setting of voltage for V/F separation 0V~rated motor voltage 0V
P3-15 Voltage rise time of V/F separation 0.0s~1000.0s

Note: 0V to rated motor voltage

0.0s
P3-16 Voltage decline time of V/F separation 0.0s~1000.0s

Note: time of 0V to rated motor voltage

0.0s
P3-17 Stop mode selection for V/F separation 0: Frequency and voltage declining to 0 independently 1: Frequency declining after voltage declines to 0 0
P3-18 Current limit level 50~200% 150%
P3-19 Current limit selection 0: useless           1: useful 1
P3-20 Current limit gain 0~100 20
P3-21 Compensation factor of speed multiplying current limit level 50~200% 50%
P3-22 Voltage limit 650V~800.0V 770V
P3-23 Voltage limit selection 0: useless           1: useful 1
P3-24 Frequency gain for voltage limit 0~100 30
P3-25 Voltage gain for voltage limit 0~100 30
P3-26 Frequency rise threshold during voltage limit 0~50Hz 5Hz
P4 Group: Input Terminals
 

P4-00

 

S1 function selection

0: no function          1: Forward run (FWD) or run command 2: reverse run (REV) or positive and negative running direction (Note: set 1, 2 to be used with P4-11)

3:three-wire   operation control   4: forward jog (FJOG) 5: reverse jog (RJOG)       6:        Terminal        UP 7: Terminal DOWN           8:        free        parking 9: Fault reset (RESET)      10:        run        pause 11: External fault normally open input

12:Multi-step command terminal 1 13:Multi-step command terminal 2 14:Multi-step command terminal 3 15:Multi-step command terminal 4

16: Acceleration/Deceleration time selection terminal 1 17:Acceleration/Deceleration time selection terminal 2 18: Frequency command switching

19: UP/DOWN setting clear(terminal, keyboard) 20:   control   command   to   switch    terminal    1 21:     Acceleration/Deceleration     is     prohibited 22: PID pause             23: Easy PLC   status   reset 24: Wobble is suspended     25:   Counter    input 26: Counter reset

27: Length count input     28: Length reset 29: Torque control disabled

30: High-speed pulse input (only valid for S5) 31: Reserved                 32: Immediate DC braking 33:    External    fault    normally    closed    input 34:        Frequency         modification         enabled 35: PID direction is reversed

36:         External          parking         terminal         1 37:control      command      to      switch       terminal       2 38:               PID               integral               is               paused 39: Frequency source A and preset frequency switching 40: Frequency source B and preset frequency switching 41: Motor terminal selection function

42:                                  Reserved 43: PID parameter switch 44: User defined fault 1

45:       user       defined       fault       2 46:Speed control/torque control switching 47: Emergency stop

48: External parking terminal 2 49:Decelerationof   DC   braking 50: This run time is cleared 51:two-wire/three-wire switch 52:Reverse frequency disabled 53-59: Reserved

 

1

 

 

P4-01

 

S2 function selection

 

4

 

 

P4-02

 

S3 function selection

 

9

 

 

P4-03

 

S4 function selection

 

12

 

 

P4-04

 

S5 function selection

 

13

 

 

P4-05

 

S6 function selection

 

0

 

 

P4-06

 

S7 function selection

 

0

 

 

P4-07

 

S8 function selection

 

 

 

P4-08

 

Reserved

 

 

 

P4-09

 

Reserved

 

 

P4-10 S1~S4   filter time 0.000s~1.000s 0.010s
P4-11 Terminal control mode 0: two lines 1 1: two lines 2    2: three lines 1 3: three lines 2
P4-12 Terminal UP/DOWN N rate 0.001Hz/s~65.535Hz/s 1.00Hz/s
P4-13 AI curve 1 min. input 0.00V~P4-15 0.00V
P4-14 Corresponding percentage of AI curve 1 min. input – 100.0%~+100.0% 0.0%
P4-15 AI curve 1 max. input P4-13~+10.00V 10.00V
P4-16 Corresponding percentage of AI curve 1 max. input – 100.0%~+100.0% 100.0%
P4-17 AI1 filter time 0.00s~10.00s 0.10s
P4-18 AI curve 2 min. input 0.00V~P4-20 0.00V
P4-19 Corresponding percentage of AI curve 2 min. input – 100.0%~+100.0% 0.0%
P4-20 AI curve 2 max. input P4-18~+10.00V 10.00V
P4-21 Corresponding percentage of AI curve 2 max. input – 100.0%~+100.0% 100.0%
P4-22 AI2 filter time 0.00s~10.00s 0.10s
P4-23 AI3 curve min. input – 10.00V~P4-25 – 10.0V
P4-24 Corresponding percentage of AI curve 3 min. input – 100.0%~+100.0% – 100.0%
P4-25 AI curve 3 max. input P4-23~+10.00V 10.00V
P4-26 Corresponding percentage of AI curve 3 max. input – 100.0%~+100.0% 100.0%
P4-27 AI3 filter time 0.00s~10.00s 0.10s
P4-28 Pulse min. input 0.00kHz~P4-30 0.00KHz
P4-29 Corresponding percentage of pulse min. input – 100.0%~100.0% 0.0%
P4-30 Pulse max. input P4-28~100.00kHz 50.00KHz
P4-31 Corresponding percentage of pulse max. input – 100.0%~100.0% 100.0%
P4-32 Pulse filter time 0.00s~10.00s 0.10s
 

 

P4-33

 

 

AI curve selection

Bit:                  AI1                  curve                  selection 1:     curve     1     (2     points,     see     P4-13~P4-16) 2:    Curve     2     (2     points,     see     P4-18~P4-21) 3:     curve     3     (2     points,     see     P4-23~P4-26) 4:    curve     4     (4     points,     see     A6-00~A6-07) 5:    curve    5    (4    points,    see    A6-08~A6-15) Ten: AI2 curve selection, ibid Hundreds:AI3 curve selection, ibid  

 

321

 

 

 

P4-34

 

Setting selection when AI less than min. input

Bit:   AI1   is   lower   than   the   minimum   input   setting 0: corresponds to the minimum input setting     1: 0.0% Ten: AI2 is lower than the minimum input setting, ibid Hundreds: AI3 is lower than the minimum input setting, ibid  

000

 

P4-35 S1 delay 0.0s~3600.0s 0.0s
P4-36 S2 delay 0.0s~3600.0s 0.0s
P4-37 S3 delay 0.0s~3600.0s 0.0s
P4-38 S1~S5 active mode selection 1 0: active high       1: active low     Bit: S1 Ten: S2 Hundred places: S3 Thousands of bits: S4 Million: S5 00000
P5 Group: Output Terminals
 

 

 

 

 

 

 

 

 

 

 

 

P5-02

 

 

 

 

 

 

 

 

 

 

 

 

Relay 1 function selection

( TA-TC)

0: pulse output (HDP) 1: Switching output (HDY)  

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: No output             1:     The     inverter     is     running 2:              fault              output              (fault              stop) 3:      Frequency      level      detection      FDT1      output 4:                                 frequency                                 arrives 5: Zero speed operation   (no   output   at   shutdown) 6:                 motor                 overload                 pre-alarm 7:                Inverter                overload                pre-alarm 8:        Set        the        count        value        to        reach 9:     Specifies     that     the     count      value      arrives 10: length to reach             11: PLC cycle is complete 12:       The       cumulative        run        time        arrives 13: Frequency limit              14:         Torque         limit 15: Ready to run      16:                                        AI1>AI2 17:          upper           limit           frequency           arrival 18: Lower frequency arrival (operation related) 19:Undervoltage                      status                      output 20:              communication               settings 21:Positioning       completed       (reserved) 22:positioning                      close                      (reserved) 23: zero speed running 2 (also output when stopped) 24:       The       total        power-up        time        arrives 25:                                Frequency                                level 26:       Frequency       1        reaches        the        output 27:       Frequency       2        reaches        the        output 28:        current         1         reaches         the         output 29:        current         2         reaches         the         output 30: Timing arrival output

31: AI1 input is overrun      32:                  Underload 33: reverse running             34: zero current state 35:Module              temperature             arrives 36:Output              current              is              exceeded 37: Lower frequency arrival (shutdown also output) 38: Alarm output (continued)    39:Motor over temperature    warning      40: This run time arrives 41: fault output (for free stop fault), and under

voltage is not output

 

 

 

P5-07

 

 

 

A01 Output function selection

0:Operating frequency             1:Frequency setting 2:Output      current       3:Output      torque 4:Output power 5:Output voltage

6:High-speed pulse input(100%corresponding100.0khz)

7:AI1           8:AI2      9:AI3 10:length 11:Count value 12:Communication    settings    13:Motor speed 14:Output current:(100% corresponding 1000.0A) 15:Output voltage(100% Corresponding 1000.0V) 16:Motor output torque(Actual value,

Percentage relative to motor)

 

 

 

0

 

 

 

P5-10 A01 Zero bias coefficient – 100.0%~+100.0% 0.0%
P5-11 A01 gain – 10.00~+10.00 1.00
P6 Group: Start/Stop Control
P6-00 Start mode 0: Direct start            1: Catching a spinning motor 2: Pre-excited start              3: SVC quick start 0
P6-01 Mode of catching a spinning motor 0: From stop frequency   1: From 50Hz 2: From max. frequency 0
P6-02 Speed of catching a spinning motor 1~100 20
P6-03 Start frequency 0.00Hz~10.00Hz 0.00Hz
P6-04 Start frequency holding time 0.0s~100.0s 0.0s
P6-05 DC injection braking 1 level/pre-excitation level 0%~100% 50%
P6-06 DC injection braking 1 active time/

pre-excitation active time

0.0s~100.0s 0.0s
P6-07 Acceleration/ Deceleration mode 0:Linear acceleration/ deceleration 1:S-curve acceleration/ deceleration A (static)

2:S curve acceleration/ deceleration B (dynamic)

0
P6-08 Time proportion of S-curve start segment 0.0%~(100.0%-P6-09) 30.0%
P6-09 Time proportion of S-curve end segment 0.0%~(100.0%-P6-08) 30.0%
P6-10 Stop mode 0: Decelerate to stop     1 : Coast to stop 0
P6-11 DC injection braking 2 start frequency 0.00Hz~max.frequency

( P0-10)

0.00Hz
P6-12 DC injection braking 2 delay time 0.0s~100.0s 0.0s
P6-13 DC injection braking 2 level 0%~100% 50%
P6-14 DC injection braking 2 active time 0.0s~100.0s 0.0s
P6-15 Braking use ratio 0%~100% 100%
P6-18 Catching a spinning motor current  limit 30%~200% Model dependent
P6-21 Demagnetization time (effective for SVC) 0.00~5.00s Model dependent
P7 Group: Keypad Operation and LED Display
 

P7-02

 

STOP/RESET key function

0: The STOP/RES key stop function is valid only during keyboard operation

1: STOP/RES key shutdown is active in any mode of

operation

 

1

 

 

 

P7-03

 

 

LED display running parameters 1

0000~FFFF         Bit00: Operating frequency 1 (Hz) Bit01: Set frequency (Hz) Bit02: Bus voltage (V) Bit03: Output voltage (V) Bit04: Output current (A) Bit05: Output power (kW) Bit06: Output torque (%) Bit07:          S          terminal          input          status Bit08: HDO output status Bit09: AI1 voltage (V) Bit10: AI2 Voltage   (V)   Bit11:   AI3   Voltage   (V) Bit12:     Count     value      Bit13:     Length     value Bit14: Load speed display Bit15: PID setting  

 

1F

 

 

 

 

 

 

 

 

P7-04

 

 

 

 

LED display running parameters 2

0000~FFFF Bit00: PID feedback Bit01: PLC stage Bit02: High-speed pulse input frequency (kHz) Bit03:       Operating        frequency        2        (Hz) Bit04:                     Remaining                     runtime Bit05:    AI1    before    correction    voltage    (V) Bit06:    AI2    before    correction    voltage    (V) Bit07:    AI3    Correction    before    voltage    (V) Bit08: Line speed

Bit09:   Current    power-on    time    (Hour) Bit10:     Current     running     time     (Min) Bit11: High-speed pulse input frequency (Hz) Bit12:       Communication        set        point Bit13:     Encoderfeedback      speed      (Hz) Bit14: Main frequency A display (Hz)

Bit15: Secondary frequency B display (Hz)

 

 

 

 

 

0

 

 

 

 

 

 

 

P7-05

 

 

LED display stop parameters

0000~FFFF

Bit00: Set frequency (Hz) Bit01: Bus voltage (V) Bit02: S input status Bit03: HDO output status Bit04: AI1 voltage (V) Bit05: AI2 voltage (V) Bit06: AI3 voltage (V)    Bit07:   Count   value Bit08:    Length    value        Bit09:    PLC    stage Bit10:    Load    speed        Bit11:    PID    setting Bit12: High-speed pulse input frequency (kHz)

 

 

33

 

 

P7-06 Load speed display coefficient 0.0001~6.5000 1.0000
P7-07 Heatsink temperature of AC Drive IGBT – 20.0℃~ 120.0℃
P7-09 Accumulative running time 0h~65535h
 

P7-12

 

Number of decimal places for load speed display

Bit:   d0-14    the    number    of    decimal    places 0: 0 decimal places          1:    1     decimal     place 2: 2 decimal places            3: 3 decimal places Ten: d0-19/d0-29 the number of decimal places 1: 1 decimal place 2: 2 decimal places  

21

 

P7-13 Accumulative power-on time 0h~65535h
P7-14 Accumulative power consumption 0kW~65535kwh
P8 Group: Auxiliary Functions
P8-04 Deceleration time 2 0.0s to 6500.0s Model dependent
P8-05 Acceleration time 3 0.0s to 6500.0s Model dependent
P8-06 Deceleration time 3 0.0s to 6500.0s Model dependent
P8-07 Acceleration time 4 0.0s to 6500.0s Model dependent
P8-08 Deceleration time 4 0.0s to 6500.0s Model dependent
P8-09 Frequency jump 1 0.00Hz to max. frequency 0.00Hz
P8-10 Frequency jump 2 0.00Hz to max. frequency 0.00Hz
P8-11 Frequency jump band 0.00Hz to max. frequency 0.00Hz
P8-12 Forward/Reverse run switch over dead-zone time 0.0s to 3000.0s 0.0s
P8-13 Reverse RUN selection 0: invalid , 1: effective 0
P8-14 Running mode when frequency reference lower than frequency  lower limit 0 to 2 0
P8-15 Droop rate 0.00% to 100.00% 0.00%
P8-16 Accumulative power-on time threshold 0 to 65000h 0h
P8-17 Accumulative running time threshold 0 to 65000h 0h
P8-18 Startup protection selection 0: Not to be protected, 1: protect 0
P8-19 Frequency detection value 1 0.00Hz to max. frequency 50.00Hz
P8-20 Frequency detection hysteresis 1 0.0% to 100.0% 5.0%
P8-21 Detection width of target frequency reached 0.0% to 100.0% 0.0%
P8-22 Jump frequency function 0: invalid , 1: effective 0
P8-25 Switchover frequency of accel time 1 and accel time 2 0.00Hz to max. frequency 0.00Hz
P8-26 Switchover frequency of decel time 1 and decel time 2 0.00Hz to max. frequency 0.00Hz
P8-27 Set highest priority to terminal JOG function 0: invalid , 1:effective 0
P8-28 Frequency detection value 2 0.00Hz to max. frequency 50.00Hz
P8-29 Frequency detection hysteres is 2 0.0% to 100.0% 5.0%
P8-30 Detection of frequency 1 0.00Hz to max. frequency 50.00Hz
P8-31 Detection width of frequency 1 0.0% to 100.0%

( max.frequency)

0.0%
P8-32 Detection of frequency 2 0.00Hz to max. frequency 50.00Hz
P8-33 Detection width of frequency 2 0.0% to 100.0% (max frequency) 0.0%
P8-34 Zero current detection level 0.0% to 300.0% (rated motor   current) 5.0%
P8-35 Zero current detection delay 0.01s to 600.00s 0.10s
P8-36 Output over current threshold 1.1%       (no       detection) 1.2% to 300.0% (rated motor current) 200.0%
P8-37 Output over current detection delay 0.00s to 600.00s 0.00s
P8-38 Detection level of current 1 0.0% to 300.0% (rated motor current) 100.0%
P8-39 Detection width of current 1 0.0% to 300.0% (rated motor current) 0.0%
P8-40 Detection level of current 2 0.0% to 300.0% (rated motor current) 100.0%
P8-41 Detection width of current 2 0.0% to 300.0% (rated motor current) 0.0%
P8-42 Timing function 0: invalid 1: valid 0.0%
P8-43 Running time setting channel 0 to 3 0
P8-44 Running time 0.0 to 6500.0 min 0.0 min
P8-45 AI1 input voltage lower limit 0.00V to F8-46 3.10V
P8-46 AI1 input voltage upper limit F8-45 to 10.00V 6.80V
P8-47 IGBT temperature  threshold 0℃ to 100℃ 75℃
P8-48 Cooling fan working mode 0: Fan runs during operation 1: the fan keeps running 0
P8-49 Wake up frequency F8-51    to    max. Frequency (F0-10) 0.00Hz
P8-50 Wake up delay time 0.0s~6500.0s 0.0s
P8-51 Hibernating frequency 0.00Hz to wake up frequency   (P8-49) 0.00Hz
P8-52 Hibernating delay time 0.0s~6500.0s 0.0s
P8-53 Running time threshold this time 0.0~6500.0 min 0.0 min
P8-54 Output power correction coefficient 0.0% to 200.0% 100.0%
P9 Group: Fault and Protection
P9-00 Motor overload protection 0: Forbidden     1: Allowed 1
P9-01 Motor overload protection gain 0.20 to 10.00 1.00
P9-02 Motor overload pre-warning coefficient 50% to 100% 80%
P9-03 Overvoltage protection gain 0~100 30
P9-04 Overvoltage protection voltage 650 to 800V 770V
 

P9-07

Detection of

short-circuit to ground upon power-on

Units: Power-to-ground short-circuit protection selection      0:           Invalid            1:           valid Tens place: Selection of short-to-ground protection before running          0: Invalid  

01

 

P9-08 Braking unit applied voltage 650 to 800V 720V
P9-09 Auto reset times 0 to 20 0
P9-10 Selection of DO action during auto reset 0: No action 1: Action 0
P9-11 Delay of auto reset 0.1s to 100.0s 1.0s
P9-12 Input phase loss/ pre-charge relay protection Unit digit: input phase loss protection selection Tenth place: Contact or pull-in protection selection 0: Forbidden 1: Allowed  

 

P9-13

 

Output phase loss protection

Unit digits : output phase loss protection selection 0:                Forbidden                1:                 Allowed Tens place: output phase loss protection selection before running

0: Forbidden     1: Allowed

 

01

 

P9-14 1st fault type  

00-55

P9-15 2nd fault type
P9-16 3rd (latest) fault type
P9-17 Frequency upon 3rd fault
P9-18 Current upon 3rd fault
P9-19 Bus voltage upon 3rd fault
P9-20 DI state upon 3rd fault
P9-21 Do state upon 3rd fault
P9-22 AC drive state upon 3rd fault
P9-23 Power-on time upon 3rd fault
P9-24 Running time upon 3rd fault
P9-27 Frequency upon 2nd   fault
P9-28 Current upon 2nd fault
P9-29 Bus voltage upon 2nd fault
P9-30 DI state upon 2nd fault
P9-31 DO state upon 2nd fault
P9-32 AC drive state upon 2nd fault
P9-33 Power-on time upon 2nd faul
P9-34 Running time upon 2nd fault
P9-37 Frequency Upon 1st   fault
P9-38 Current upon 1st fault
P9-39 Bus voltage upon 1st faul
P9-40 DI state upon 1st fault
P9-41 DO state upon 1st fault
P9-42 AC drive state upon 1st fault
P9-43 Power-on time upon 1st fault
P9-44 Running time upon 1st fault
P9-47 Fault protection action selection 1 0:free     1:stop      2.continue running 00000
P9-48 Fault protection action selection 2 00000 to 11111 00000
P9-49 Fault protection action selection 3 00000 to 22222 00000
P9-50 Fault protection action selection 4 00000 to 22222 00000
P9-54 Frequency selection for continuing to run upon fault 0 to 4 0
P9-55 Backup frequency upon fault 0.0% to 100.0% (max. FrequencyP0-10) 100.0%
P9-56 Type of motor temperature sensor 0: No temperature sensor     1: Pt100     2: PT1000
P9-59 Power dip ride-through function selection 0: Invalid 1: constant bus voltage control 2: deceleration stop 0
P9-60 Threshold of power dip ride through function disabled 80% to 100% 85%
P9-62 Threshold of power dip ride through function enabled 60% to 100% 80%
P9-63 Load lost protection 0: Disabled    1: Enabled 0
P9-64 Load lost detection level 0.0% to 100.0% 10.0%
P9-65 Load lost detection time 0.0s to 60.0s 1.0s
P9-67 Overspeed detection level 0.0% to  50.0%( max.frequency) 20.0%
P9-68 Overspeed detection time 0.0s to 60.0s 1.0s
P9-69 Detection level of speed error 0.0% to  50.0%( max.frequency) 20.0%
P9-70 Detection time of Speed   error 0.0s to 60.0s 5.0s
P9-71 Power dip ride-through gain Kp 0 to 100 40
P9-72 Power dip ride-through integral coefficient 0 to 100 30
P9-73 Deceleration time of power dip ride-through 0.0s to 300.0s 20.0s
PA Group: PID Function
 

PA-00

 

PID reference setting channel

0: PA-01 setting 1: AI1 (Note: J6 jumper) 2: AI2 3: AI3

4: High-speed pulse input setting (S5) 5: Communication given

6: Multi-section instruction given

 

0

 

PA-01 PID digital setting 0.0v% to 100.0% 50.0%
 

PA-02

 

PID feedback

0: AI1 (Note: J6 jumper) 1: AI2 2: AI3 3: AI1-AI2

4: High-speed pulse input setting (S5) 5: Communication given   6: AI1 + AI2 7: MAX (| AI1 |, | AI2 |)

8: MIN (| AI1 |, | AI2 |)

 

0

 

PA-03 PID operation direction 0: Positive action    1: reaction 0
PA-04 PID reference and feedback range 0 to 65535 1000
PA-05 Proportional gain Kp1 0.0 to 1000.0 20.0
PA-06 Integral time Ti1 0.01s to 10.00s 2.00s
PA-07 Differential time Td1 0.000s to 10.000s 0.000s
PA-08 PID output limit in reverse direction 0.00 Hz to max. Frequency P0-10 0.00Hz
PA-09 PID error limit 0.0% to 100.0% 0.0%
PA-10 PID differential limit 0.00% to 100.00% 0.10%
PA-11 PID reference change time 0.00s to 650.00s 0.00s
PA-12 PID feedback filter time 0.00s to 60.00s 0.00s
PA-13 PID output filter time 0.00s to 60.00s 0.00s
PA-14 Reserved
PA-15 Proportional gain Kp2 0.0 to 1000.0 20.0
PA-16 Integral time Ti2 0.01s to 10.00s 2.00s
PA-17 Differential time Td2 0.000s to 10.000s 0.000s
PA-18 PID parameter switch over condition 0 to 3 0
PA-19 PID error 1 for auto switch over 0.0% to PA-20 20.0%
PA-20 PID error 2 for auto switch over PA-19 to 100.0% 80.0%
PA-21 PID initial value 0.0% to 100.0% 0.0%
PA-22 PID initial value active time 0.00s to 650.00s 0.00s
PA-23 Two output deviations forward to maximum 0.0% to 100.0% 1.00%
PA-24 Two output deviations reverse maximum 0.0% to 100.0% 1.00%
PA-25 PID integral property 00 to 11 00
PA-26 Detection level of PID feedback loss 0.0%: No detection 0.1% to 100.0% 0.0%
PA-27 Detection time of PID feedback loss 0.0s to 20.0s 0.0s
PA-28 Selection of PID operation at stop 0: Stop no operation, 1: Down time operation 0
Pb Group: Wobble Function, Fixed Length and Count
Pb-00 Wobble setting mode 0: 0: relative to the center frequency, 1: relative to the maximum frequency 0
Pb-01 Wobble amplitude 0.0% to 100.0% 0.0%
Pb-02 Wobble step 0.0% to 50.0% 0.0%
Pb-03 Wobble cycle 0.1s to 3000.0s 10.0s
Pb-04 Triangular wave rising time coefficient 0.1% to 100.0% 50.0%
Pb-05 Set length 0 to 65535m 1000m
Pb-06 Actual length 0 to 65535m 0m
Pb-07 Number of pulses per meter 0.1 ~ 6553.5 100.0
Pb-08 Set the count value 1 ~ 65535 1000
Pb-09 Specify the count value 1 ~ 65535 1000
PC Group: Multi-reference and Simple PLC Function
PC-07 Reference 7 – 100.0% to 100.0% 0.0%
PC-08 Reference 8 – 100.0% to 100.0% 0.0%
PC-09 Reference 9 – 100.0% to 100.0% 0.0%
PC-10 Reference 10 – 100.0% to 100.0% 0.0%
PC-11 Reference 11 – 100.0% to 100.0% 0.0%
PC-12 Reference 12 – 100.0% to 100.0% 0.0%
PC-13 Reference 13 – 100.0% to 100.0% 0.0%
PC-14 Reference 14 – 100.0% to 100.0% 0.0%
PC-15 Reference 15 – 100.0% to 100.0% 0.0%
PC-16 Simple PLC running mode 0: Stop at the end of a single run 1: Keep the final value at the end of a single run     2: keep circulating 0
 

 

PC-17

 

Simple PLC retentive selection

Single digit: power-down memory selection                                                        0:    No    memory     when     power     off 1:            power-down            memory Tenth   place:   Stop   memory   selection 0: Stop memory 1: shutdown memory  

 

00

 

 

PC-18 Running time of simple PLC reference 0 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-19 Acceleration/ deceleration time of simple PLC reference 0 0 to 3 0
PC-20 Running time of simple PLC reference 1 0s (h) to 6500.0s (h) 0.0s (h)
PC-21 Acceleration/ deceleration time of simple PLC reference 1 0 to 3 0
PC-22 Running time of simple PLC reference 2 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-23 Acceleration/ deceleration time of simple PLC reference 2 0 to 3 0
PC-24 Running time of simple PLC reference 3 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-25 Acceleration/ deceleration time of simple PLC reference 3 0 to 3 0
PC-26 Running time of simple PLC reference 4 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-27 Acceleration/ deceleration time of simple PLC reference 4 0 to 3 0
PC-28 Running time of simple PLC reference 5 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-29 Acceleration/ deceleration time of simple PLC reference 5 0 to 3 0
PC-30 Running time of simple PLC reference 6 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-31 Acceleration/ deceleration time of simple PLC reference 6 0 to 3 0
PC-32 Running time of simple PLC reference 7 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-33 Acceleration/ deceleration time of simple PLC reference 7 0 to 3 0
PC-34 Running time of simple PLC reference 8 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-35 Acceleration/ deceleration time of simple PLC reference 8 0 to 3 0
PC-36 Running time of simple PLC reference 9 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-37 Acceleration/ deceleration time of simple PLC reference 9 0 to 3 0
PC-38 Running time of simple PLC reference 10 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-39 Acceleration/ deceleration time of simple PLC reference 10 0 to 3 0
PC-40 Running time of simple PLC reference 11 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-41 Acceleration/ deceleration time of simple PLC reference 11 0 to 3 0
PC-42 Running time of simple PLC reference 12 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-43 Acceleration/ deceleration time of simple PLC reference 12 0 to 3 0
PC-44 Running time of simple PLC reference 13 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-45 Acceleration/ deceleration time of simple PLC reference 13 0 to 3 0
PC-46 Running time of simple PLC reference 14 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-47 Acceleration/ deceleration time of simple PLC reference 14 0 to 3 0
PC-48 Running time of simple PLC reference 15 0.0s (h) to 6500.0s (h) 0.0s (h)
PC-49 Acceleration/ deceleration time of simple PLC reference 15 0 to 3 0
PC-50 Time unit of simple PLC running 0:s, 1:h 0
 

PC-51

 

Reference 0 source

0: Function code PC-00 is given 1: AI1 2: AI2 3: AI3

4: High speed pulse input     5: PID

6: Preset frequency (P0-08) given, UP/DOWN can be modified

 

0

 

Pd Group: Communication
 

Pd-00

 

Baud rate

Bit: MODBUS   0: 300BPS   1: 600BPS 2: 1200BPS 3: 2400BPS 4: 4800BPS

5: 9600BPS      6: 19200BPS    7: 38400BPS

8: 57600BP    9: 115200BPS   Ten: keep

Hundred: reserved

 

005

 

Pd-01 Data format symbol 0: no parity (8-N-2)      1: Even check (8-E-1) 2: Odd parity (8-O-1)     3: No parity ( 8-N-1) 0
Pd-02 Local address 0: Broadcast address;     1 to 247 1
Pd-03 Response delay 0 to 20 ms 2
Pd-04 Communication timeout 1.1: invalid    1.2:s to 60.0s 0.0
Pd-05 Modbus protocol selection and PROFIBUS-DP data frame Bit: MODBUS

0: non-standard MODBUS protocol 1: standard MODBUS protocol

30
Pd-06 Current resolution read by communication 0: 0.01

1: 0.1

0
PE Group: User-Defined Parameters
PE-00 User-defined parameter 0  

P0-00 ~ PP-xx

A0-00 ~ Ax-xx d0-00 ~ d0-xx d3-00 ~ d3-xx

d3-17
PE-01 User-defined paramete1 d3-18
PE-02 User-defined parameter 2 P0.00
……… ……. P0.00
PE-29 User-defined parameter 29 P0.00
PP Group: Function Parameter Management
PP-00 User password 0 to 65535 0
 

 

PP-01

 

 

Parameter initialization

0: No operation   1:   Restore   factory 0: No operation

1: Restore factory parameters except motor parameters      2: Clear records 4: Back up current user parameters 501: Restore user backup parameter

 

 

0

 

 

 

PP-02

 

Parameter display  property

Bit:   d   group   display   selection 0: not displayed     1:     display Ten: Group A shows the selection 0: not displayed    1: display  

11

 

 

PP-03

 

Selection of individualized parameter display

Bit: user custom parameter group display selection

0:        not        displayed         1:        display Ten: User Change Parameter Group Display Selection       0: not displayed 1: display

 

00

 

PP-04 Selection of parameter modification 0: can be modified 1: can not be modified 0
A0 Group: Torque Control and Limit
A0-00 Speed/Torque control selection 0: speed control 1: torque control 0
 

 

A0-01

 

Torque reference source in torque control

0:   Digital   setting   1   (A0-03) 1: AI1 (Note: J6 jumper) 2: AI2

3: AI3         4: High-speed pulse   input   (S5) 5: Communication given   6: MIN (AI1, AI2) 7: MAX (AI1, AI2) (1-7 options Full scale, corresponding to A0-03 digital setting)

 

 

0

 

 

A0-03 Torque digital setting in torque control – 200.0% to 200.0% 150.0%
A0-05 Forward max. frequency in torque  control 0.00Hz to max Frequency:z(P0-10) to ma x.
A0-06 Reverse max. frequency in torque control 0.00Hz (P0-10) to ma x.
A0-07 Acceleration time in torque control 0.00s to 65000s 0.00s
A0-08 Deceleration time in torque control 0.00s to 65000s 0.00s
 

 

A2-47

 

 

Torque limit source in speed control

0: A2-48 setting 1: AI1 (Note: J6 jumper) 2: AI2 3: AI3 4: High-speed pulse input (S5) 5: communication given 6: MIN (AI1, AI2) 7: MAX (AI1, AI2)

1-7 option full scale, corresponding to A2- 48 digital settings

 

 

0

 

 

A2-48 Digital setting of torque limit in speed control 0.0% to 200.0% 150.0%
A2-49 Torque limit source in speed control (regenerative) 0:Function code P2-10 setting 1: AI1 (Note: J6 jumper) 0
A5 Group: Control Optimization
A5-00 DPWM switch over frequency upper limit 5.00Hz to max. frequency 8.00Hz
A5-01 PWM modulation pattern 0: Asynchronous modulation, 1: Synchronous modulation 0
A5-02 Dead zone compensation mode selection 0:   No   compensation, 1: Compensation Mode 1 1
A5-03 Random PWM depth 0 :PWM invalid    1:PWM can choose 0
A5-04 Over current fast prevention 0:enable     1:uncable 1
A5-05 Voltage over modulation coefficient 100% to 110% 105%
A5-06 Under voltage threshold 150 to 420V 350V
A5-08 Dead-zone time   adjustment 0.0% to 8.0% 0.0%
A5-09 Over voltage threshold 650 to 820V Model dependent
A6 Group: AI CA6 Group: AI Curve Settingurve Setting
A6-00 AI curve 4 min. input – 10.00V to A6-02 0.00V
A6-01 Corresponding percentage of AI curve 4 min. input – 100.0% to 100.0% 0.0%
A6-02 AI curve 4 in flexion 1 input A6-00 to A6-04 3.00V
A6-15 Corresponding percentage of AI curve 5 max. input – 100.0% to 100.0% 30.0%
A6-24 Jump point of AI1 input corresponding setting – 100.0% to 100.0% 0.0%
AC Group: AIAO Correction
AC-00 AI1 measured voltage 1 – 10.00 to 10.000V factory corrected
AC-01 AI1 displayed voltage 1 – 10.00 to 10.000V factory corrected
AC-02 AI1 measured voltage 2 – 10.00 to 10.000V factory corrected
AC-03 AI1 displayed voltage 2 – 10.00 to 10.000V factory corrected
AC-12 Ao1 Target voltage1 – 10.00 to 10.000V factory corrected
AC-13 Ao1 measured voltage 1 – 10.00 to 10.000V factory corrected
AC-14 AO1Target voltage 2 – 10.00 to 10.000V factory corrected
AC-15 Ao1 measured voltage 2 – 10.00 to 10.000V factory corrected

Monitoring Parameters

Function Code Name Display Range Communication Address
Group d0: Monitoring Parameters
d0-00 Running frequency 0.01Hz 7000H
d0-01 Frequency reference 0.01Hz 7001H
d0-02 Bus voltage 0.1V 7002H
d0-03 Output voltage 1V 7003H
d0-04 Output current 0.01A 7004H
d0-05 Output power 0.1kW 7005H
d0-06 Output torque 0.1% 7006H
d0-07 S input state 1 7007H
d0-08 HDO output state 1 7008H
d0-09 AI1 voltage 0.01V 7009H
d0-10 AI2 voltage/current 0.01V/0.01mA 700AH
d0-11 AI3 voltage 0.01V 700BH
d0-12 Count value 1 700CH
d0-13 length value 1 700DH
d0-14 Load speed display 1 700EH
d0-15 PID reference 1 700FH
d0-16 PID feedback 1 7010H
d0-17 PLC stage 1 7011H
d0-18 Pulse reference 0.01kHz 7012H
d0-19 feedback speed 0.01Hz 7013H
d0-20 Remaining running time 0.1Min 7014H
d0-21 AI1 voltage before correction 0.001V 7015H
d0-22 AI2 voltage (V)/ current (MA) before correction 0.001V/0.01mA 7016H
d0-23 AI3 voltage before 0.001V 7017H
d0-24 Motor speed 1m/Min 7018H
d0-25 Accumulative power-on time 1Min 7019H
d0-26 Accumulative running time 0.1Min 701AH

Fault Display

Fault code Fault
FU02 Over current during acceleration
FU03 Over current during deceleration
FU04 Over current at constant speed
FU05 Over voltage during acceleration
FU06 Over voltage during deceleration
FU07 Over voltage at constant speed
FU08 Pre-charge resistor fault
FU09 Under voltage
FU10 AC drive overload
FU11 Motor overload
FU13 Output phase loss
FU14 overheat
FU15 Out project fault
FU16 Communication fault
FU17 Contact or fault
Fault code Fault
FU18 Current detection failure
FU19 Motor self learning malfunction
FU20 Encoder fault
FU21 EEPROM read-write
FU23 Short circuit to ground
FU26 Accumulative running time
FU27 User-defined fault 1
FU28 User-defined fault 2
FU29 Accumulative power reach error
FU30 Load loss
FU31 PID feedback lost during running
FU40 Pulse-by-pulse current limit fault
FU41 Motor switchover fault during running
Fu42 Excessive speed deviation
FU43 Motor over speed

Documents / Resources