USER MANUAL
CTS602 HMI BY NILAN
VGU 180 EK “RS”
Safety
Power supply
CAUTION
Always disconnect the power supply to the unit if an error occurs that cannot be rectified via the control panel.
CAUTION
If an error occurs on electrically conductive parts of the unit, always contact an authorised electrician to rectify the error.
CAUTION
Always disconnect the power supply to the unit before opening the unit doors, for instance for installation, inspection, cleaning and filter change.
Disposal
Ventilation unit
Nilan’s units consist mainly of recyclable materials. They must, therefore, not be mixed with household waste, but must be delivered to your local recycling center for disposal.
Heatpump
Concerning disposal of units with heat pumps, it is important to contact the local authorities for information about correct handling of these. The heatpump contains the refrigerant R134a, which is harmful to the environment if not handled correctly.
General information
Introduction
ATTENTION
The unit must be started up immediately after installation and connection to the duct system.
When a ventilation unit is not in operation, humidity from the rooms may penetrate into the ducts and create condensation. Condensate water may leak out of the valves and damage furniture and floors. Condensation may also form inside the unit, which can damage its electronics and fans.
The unit is delivered fully tested and ready for operation.
Type plate
Nilan’s type plate can be found on the unit
Note: Contact Nilan a/s with questions about the product, it is important to have the unit name and serial No. (SN) ready. On the basis of this information, please contact service department find all informations about the relevant aggregate and thus provide information and answer questions about what the aggregate consists of/contains, as well as the software used.
Quick guide
Functions of control panel
Main screen elements
The main screen of the HMI panel contains the settings options and the information mostly used by an operator.
- Shows the current room temperature in the dwelling, measured via the extract air.
- Shows the current air humidity. If a CO2 meter has been installed, this will be shown next to air humidity.
- Shows the current fan speed level.
- Show the current outdoor temperature
- Shows the menu icons listed below
- Shows the mode icons listed below
- Shows the hot water temperature
- Shows the central heating flow temperature
- Shows the central heating return temperature
- Access to the settings menu, which contains more settings options
Menu icons
Stop icon
Indicates that the unit has stopped
User selection icon
Indicates that the user selection function is active
Week program icon
Indicates that the week program function is active
Alarm icon
Indicates an alarm or warning
Mode icons
Compressor icon
Indicates that the compressor is active
Domestic hot water icon
Indicates that the unit is producing hot water. The flash indicates that the supplementary electric heating is active.
De-icing ikon
Indicates that the heat pump is de-icing
Settings options on the main screen
The settings options which the user needs in daily life can all be controlled from the main screen of the panel.
If you select the option of current room temperature, the desired room temperature will be displayed.
The desired room temperature can be adjusted by pressing the up-or-down arrows followed by the cancel icon (bottom left) or the accept icon (bottom right).
If you select the option of current fan speed level, the desired fan speed level will be displayed.
The desired fan speed level can be adjusted by pressing the up-or-down arrows followed by the cancel icon (bottom left) or the accept icon (bottom right).
By pressing the current hot water temperature the desired hot water temperature is displayed.
The desired hot water temperature can be adjusted by pressing the up-or-down arrows followed by the cancel icon (bottom left) or the accept icon (bottom right).
Warnings and alarms
Should an error occur in the operation of the unit, a warning or an alarm will be displayed. A warning will appear in the top righthand corner in the menu bar.
If you press the symbol, a description of the warning or the alarm will be displayed.
The warning or the alarm can be reset by pressing “Clear Alarm”.
A warning indicates that something requires attention, for instance that filters need changing.
The unit operates normally.
An alarm indicates a serious fault with the unit that is likely to require investigation by an expert.
The unit has stopped.
Settings menu overview
The settings menu is constructed to make it easy to navigate through.
Service and maintenance
Maintenance
Regular maintenance
Your Nilan ventilation unit will last for many years if it is correctly maintained. Correct maintenance will also ensure that the unit runs optimally at all times with low energy consumption.
In the following we point out the regular maintenance which you can perform yourself and the annual service which should be carried out by a professional.
External cleaning
The ventilation unit
The outside of the unit can be cleaned with a mild soap solution.
The ceiling valves
Over time a ring may develop round the inlet valves. is due to dust in the room air, not to defective filters or failure to
As very few painted ceilings are washable, you are recommended to vacuum round the valve and then wipe the area with a damp cloth.
It is a good idea to dismantle and clean the valves when necessary. The valves have been set by the installer for a specific airflow, so it is important not to rotate them, as this will change the setting and unbalance the ventilation system.
Water trap
The water trap can dry out and prevent water from draining from the condensate tray, because air will then blow into the unit. Condensate water will accumulate in the condensate tray. This will eventually overflow and potentially cause water damage to the surface supporting the unit. The water trap should therefore be checked regularly and filled with water, especially in the summer when the risk of the water trap drying out is highest.
Filter replacement
The purpose of the filters is to protect the fans and the heat exchanger from dust and dirt, which may cause damage.
For operation to run smoothly, it is important to change the filters as required. The filter timer in Nilan’s control system is set by default to indicate that filters should be replaced after 90 days, but this can be changed as required to 180 or 360 days. If the filters are not changed, ventilation will lessen. This may cause the indoor climate to deteriorate and affect the automatic humidity control system of the unit.
Illustration of filter change
- Switch off the unit on the control panel before opening the door.
- Turn the thumb screws in the door at the top right of the unit and open the door.
- Remove the filter from the unit
- It is advisable that you vacuum the filter chambers for potential dirt and dust
- Remove the filter sheet from the filter frame
- Keeping the smooth side facing downwards, place the new filter sheet in the filter frame
- Press the filter sheet firmly in place and carefully push it to the sides of the filter frame. The filter is placed back in the unit with filter mat upward
- In the ALARM menu on the control panel, press the alarm symbol at the top right and reset the alarm here.
Service
Annual service
It is important to perform an annual service on the unit to ensure it will continue to perform optimally with low energy consumption and long service life.
You are recommended to take out a service agreement with the installer, as certain elements of the service require an authorised technician.
Internal cleaning
For hygienic reasons, it is important that the unit undergoes annual internal cleaning. This will prevent the formation of fungus and bacteria which impair the internal air quality.
- Wipe down the internal plate parts and pipes with a damp cloth and a mild soap solution.
- Check and clean the evaporator coil.
- Check and clean the counterflow heat exchanger. If necessary, it may be removed and rinsed with a shower head.
- Clean the condensate trays with a damp cloth and a mild soap solution.
- Check the condensate outlet to make sure the water can exit freely.
Check the air outlet
It is important for operation of the unit that air can freely move through the air intake and outlet.
If roof stacks have been fitted to the air intake and outlet, check that they are not blocked with birds’ nests, leaves or other dirt which can hamper air passage.
If, instead of roof stacks, grilles have been mounted in facades or eaves, check that they are not Grilles are particularly likely to become
Check ventilation ducts
It is important for operation of the unit that there is free air passage through the ventilation ducts. After some years of operation, dirt will attach itself to ventilation ducts or tubes, and accumulations may lead to higher pressure drop in the ducts, leading to higher power consumption. It is therefore important to clean out the ducts when too much dirt has collected. It is therefore important to clean out the ducts when, too much dirt has formed
After attending to the inlet and outlet valves, it will be advisable to have them adjusted again, to ensure optimum operation of the ventilation system.
However, it will not be necessary to clean ducts more than every few years.
The heat pump
The heat pump must be inspected in accordance with applicable laws and regulations, such that it is kept in good condition and meets safety and environmental requirements.
The installer is obliged to inform the owner/user about applicable laws and regulations.
User settings
Ventilation settings
Stop the unit
If it is necessary to open the doors while servicing the unit, for instance when changing filters, the unit
must be turned off.
The functions of the unit are activated in Settings under Operation.
If the unit is off, an icon appears on the main screen.
Operation
↳ Operation | Settings: Description: |
Off / On The unit must be turned off before the doors are opened during a service |
Alarm
You can read warnings and alarms in the “Alarm” menu. It is likewise possible to reset warnings and alarms in this menu.
When a warning or an alarm has been triggered, an icon appears on the main screen
Alarm
↳ Alarm number and name | Description: | When selecting this, a list will appear showing the alarm ID number, information about the type of alarm, and whether it is critical or not. (See the alarm list for more information) You can approve the alarm by selecting “Clear Alarm” |
ATTENTION
When an alarm is active, it cannot be reset in the panel. When the alarm has been resolved, it will figure as inactive and it can be reset by selecting “Clear Alarm”.
Show data
It is possible to read off current data for the unit.
Show data
↳ Operating state | Description: | Shows the operating setting in which the unit is running. |
↳ T1 Outdoor air | Description: | Shows the outdoor temperature before reaching the pre-heating element. |
↳ T5 Condenser | Description: | Shows the condenser temperature. |
↳ T6 Evaporator | Description: | Shows the evaporator temperature. |
↳ T10 Extract air/Room | Description: | Shows the current room temperature, measured in the extract air. |
↳ T11 Top hot water | Description: | Shows the current temperature in the top of the domestic hot water tank. Controls the supplementary electric heating. |
↳ T12 Bottom hot water | Description: | Shows the current temperature at the bottom of the domestic hot water tank. Controls the compressor. |
↳ T13 Return flow | Description: | Shows the current return temperature of the water in the central heating system |
↳ T14 Supply flow | Description: | Shows the current flow temperature of the water in the central heating system |
↳ Air humidity | Description: | Shows the current air humidity in the dwelling. |
↳ CO2 | Description: | Shows the current CO level in the dwelling (only if installed). 2 |
↳ Extract air fan | Description: | Shows the level at which the extract air fan is operating. |
↳ Unit information | Description: | Press “Unit information” for more information. |
↳ Unit type | Description: | Shows the name of the product the software has been set to work with. |
↳ Software version | Description: | Shows the installed software version. |
↳ Panel software | Description: | Shows the installed software version on the panel. |
Date/Time
It is important to set date and time correctly. It makes it easier to localise errors indicated in an error report. When logging data, it is important to be able to follow the history. The time is shown under “Date / Time” in the display.
Date / Time
↳ Year | Description: | Select “Year” in the panel and then select the correct year. |
↳ Month | Description: | Select “Month” in the panel and then select the correct month. |
↳ Day | Description: | Select “Day” in the panel and then select the correct day. |
↳ Hour | Description: | Select “Hour” in the panel and then select the correct hour. |
↳ Minute | Description: | Select “Minute” in the panel and then select the correct amount of minutes. |
Week program
You can program the unit to run in accordance with specific settings at fixed times during the week via a week program.
On the main screen an icon will be displayed when the week program is active
Week program
↳ Select program | Description: | You can select from the Programs 1, 2, 3 or off. |
↳ Edit program | Description: | The selected week program is now active and can be edited. |
↳ Monday | Description: | You can select either Monday, Tuesday, Wednesday, Thursday, Friday, Saturday or Sunday. |
↳ Function 1 | Description: | Under each function, you can set time, temperature and fan speed level. |
↳ Start time | Settings: Standard setting: Description: |
Hours and minutes 6:00 Set the time for the program to start. The program will run until the next change in the week program. |
↳ Ventilation | Settings: Standard setting: Description: |
Level 1 / Level 2 / Level 3 / Level 4 / Off Level 3 Select the desired fan speed level here. |
↳ Temperatures | Settings: Standard setting: Description: |
5 – 40 °C 22 °C Set the desired room temperature here. |
↳ Function 2 | Under each function, you can set time, temperature and fan speed level. | |
↳ Start time | Settings: Standard setting: Description: |
Hours and minutes 8:00 Set the time for the program to start. The program will run until the next change in the week program. |
↳ Ventilation | Settings: Standard setting: Description: |
Level 1 / Level 2 / Level 3 / Level 4 / Off Level 1 Select the desired fan speed level here. |
↳ Temperatures | Settings: Standard setting: Description: |
5 – 40 °C 22 °C Set the desired room temperature here. |
↳ Function 3 | Description: | Under each function, you can set time, temperature and fan speed level. |
↳ Start time | Settings: Standard setting: Description: |
Hours and minutes 15:00 Set the time for the program to start. The program will run until the next change in the week program. |
↳ Ventilation | Settings: Standard setting: Description: |
Level 1 / Level 2 / Level 3 / Level 4 / Off Level 3 Select the desired fan speed level here. |
↳ Temperatures | Settings: Standard setting: Description: |
5 – 40 °C 22 °C Set the desired room temperature here. |
↳ Function 4 | Settings: Standard setting: Description: |
Under each function, you can set time, temperature and fan speed level. |
↳ Start time | Settings: Standard setting: Description: |
Hours and minutes 22:00 Set the time for the program to start. The program will run until the next change in the week program. |
↳ Ventilation | Settings: Standard setting: Description: |
Level 1 / Level 2 / Level 3 / Level 4 / Off Level 1 Select the desired fan speed level here. |
↳ Temperatures | Settings: Standard setting: Description: |
5 – 40 °C 22 °C Set the desired room temperature here. |
↳ Functions 5 and 6 | Settings: Standard setting: Description: |
Under each function, you can set time, temperature and fan speed level. Off The program will run until the next change in the week program. |
↳ Reset program | Description: | You can reset the program by selecting the approve icon. |
Central heating
Possible settings for room heating.
Central heating
↳ Setting | Settings: Standard setting: Description: |
Heating / Off / Requirement Heating Off: Room heating is off. Heating: Constant heating in relation to min./max. Requirement: The flow temperature is regulated automatically by the curve setting |
↳ Minimum flow temperature | Settings: Standard setting: Description: |
5 – 40 ºC 25 ºC Here, the minimum flow temperature is set. The setting overrides a potentially lower temperature from the curve control. This function may be relevant with, for example, underfloor heating if you should want a minimum comfort temperature. |
↳ Maximum flow temperature | Settings: Standard setting: Description: |
25 – 70 ºC 50 ºC Here, the maximum flow temperature is set. The setting overrides a potentially higher temperature from the curve control. |
↳ Outdoor temperature compensatio | Settings: Standard setting: Description: |
1 – 10 4 Choose which curve the control system should regulate in accordance with |
↳ Offset curve | Settings: Standard setting: Description: |
-15 – 10 ºC 0 ºC You can shift the curve to best fit the heating requirements of the dwelling |
↳ Delay | Settings: Standard setting: Description: |
0 – 30 minutes 10 minutes Set a chosen delay for when the central heating should start operating, once a heating requirement has been registered. |
↳ Circulation pump | Settings: Standard setting: Description: |
Continuous / Energy Continuous: The pump is running constantly Energy: The pump runs when required |
Curve control
The flow temperature is regulated automatically in accordance with a curve.
Domestic hot water
Settings for hot water production have been set at the factory, but it may be necessary to adjust them to match the user´s needs.
Domestic hot water
↳ Electric supplement heater hot water | Settings: Standard setting: Description: |
Off / 5 – 85 ºC 30 ºC Off: The electricity supplement is de-activated by the user 5 – 85 ºC Indicates below which temperature (T11) the electricity supplement should help by heating the hot water. |
↳ Hot water temperature | Settings: Standard setting: Description: |
Off / 5 – 60 ºC 45 ºC Off: The hot water production is switched off by the user 5 – 60 ºC Indicates below which temperature (T12) the compressor must produce hot water. |
Anti-scald device: | Settings: Standard setting: Description: |
60 – 80 ºC 65 ºC When the unit is in heating or cooling mode, heat will simultaneously be deposited in the hot water tank. To prevent the hot water from getting too hot and rinsing the user, a limit of 65ºC has been inserted. When the temperature in the hot water tank reaches 65 ° C, cooling or heating the supply air stops. NB! If a scalding valve is connected to the bottom of the hot water tank, the setting can be changed up to 80ºC. In this way, the capacity for cooling and heating of the supply air is increased. |
Air humidity
The primary purpose of ventilation is to extract humidity from the house so it does not damage the building, and to achieve a good indoor climate. During long periods with sub-zero temperatures, air humidity in the house may fall to a level that is critical for the building and for the indoor climate. Wooden floors, furniture and walls can be damaged by very dry air, which also whirls up dust, resulting in a poor indoor climate.
This is rectified by an integrated humidity control system that maintains good, relative air humidity.
When the average air humidity in the house falls below a set level (default set at 30%), ventilation may be reduced. It will typically only be for a short period of time. This will help avoid further reduction of the air humidity in the house.
The humidity control system also has a function that allows increased ventilation, should the air humidity increase, for instance when having a bath. The risk of mould growth in the bathroom is reduced, and the bathroom mirror will rarely steam up.
The humidity control system follows the average air humidity level measured over the previous 24 hours. In this way the system automatically adapts to summer and winter conditions.
Air humidity
↳ Vent.low humidity | Settings: Standard setting: Description: |
Level 1 / Level 2 / Level 3 / Level 4 / Off Level 1 At low humidity, the unit changes to the set fan speed level. |
↳ Low humidity level | Settings: Standard setting: Description: |
15 ↔ 45 % 30 % The control system calculates an average air humidity level measured over the previous 24 hours. If the average air humidity in the extract air falls below this level, the “Low humidity” function will be activated. Note! The function is only active in winter mode. |
↳ Vent.high humidity | Settings: Standard setting: Description: |
Level 2 / Level 3 / Level 4 / Off Level 3 At high humidity levels, for instance when having a bath, the unit changes to the set fan speed level. |
↳ Max time high humidity | Settings: Standard setting: Description: |
1 ↔ 180 minutes / Off 60 minutes The function “High humidity” stops when actual humidity falls below 3% above the average air humidity. The run of this function has been time limited. |
CO 2
This menu is only displayed if a CO2 sensor has been installed.
ATTENTION
CO 2 sensor.
A CO2 sensor is not a standard part of all units, but may be purchased as an accessory.
If the number of people using a building varies considerably, controlling ventilation through the CO2 level in the extract air may be a good solution. This function is often used in offices and schools where use varies greatly during the day and during the week.
↳ Vent.high CO2 level | Settings: Standard setting: Description: |
Level 2 / Level 3 / Level 4 / Off Level 3 Here you indicate the fan speed level at which the unit is to operate at high CO 2 level. |
↳ High CO2 level | Settings: Standard setting: Description: |
650 ↔ 2500 ppm 800 ppm Here you indicate the CO 2 level at which the unit is to switch to high fan speed level. |
↳ Normal CO2 level | Settings: Standard setting: Description: |
400 ↔ 750 ppm 600 ppm Here you indicate the CO2 – level at which the unit is to switch to normal control. |
Air exchange
Low humidity in the dwelling can be prevented by reducing ventilation at low outdoor temperatures.
This function can be used, for instance, in countries with regular sub-zero temperatures and at high altitudes where the outdoor air is very dry.
Air exchange
↳ Type of ventilation | Settings: Standard setting: Description: |
Comfort / Energy Comfort Comfort: The fan is constantly on. Energy: The fan stops concurrently with the compressor |
Air filter
The filter alarm has a timer. Its factory setting is 90 days between each filter change. If you want to add pressure-controlled filter change, pressure sensors can be connected via digital input and adjustment in the filter menu.
Air filter
↳ Filter alarm | Settings: Standard setting: Description: |
None / 30 / 60 / 90 / 180 / 360 90 days The number of days between filter changes can be set as required. For optimal operation, it is important that filters are clean. A clogged filter increases power consumption and provides less hot water. |
Language
The unit is factory-set to Danish language. You can change the texts to other languages.
↳ Danish | Description: | Select the desired language on the panel. |
Alarm list
VGU unit
Alarm list
The list below applies to VGU units. Events are divided into the following categories:
Warning Operation continues, but something no longer functions optimally.
Critical
Operation has stopped partially or completely as a serious error requires immediate attention.
ID | Type | Display text | Description / cause | Rectification of error |
1 | ![]() |
Hardware error | Error in the hardware of the control system. | If resetting does not help, contact service. |
2 | ![]() |
Alarm timeout | A warning alarm has become a critical alarm. | Register alarm and reset. If the alarm persists, contact service. |
3 | ![]() |
Fire alarm activated | The unit has stopped because the fire thermostat has been activated. | If there has been no fire, contact service. |
4 | ![]() |
Pressure switch | The high-pressure switch in the refrigeration circuit has been triggered, possibly due to: • Extremely warm outdoor air supply • Clogged filter • Defective fan |
Check for faults and reset the alarm. Contact service if you cannot reset the alarm or if alarms occur often. |
6 | ![]() |
Error in de-icing of heat pump |
The de-icing time has been exceeded. The exchanger or the heat pump has failed to de-ice within the maximum time. This may be due to the unit being exposed to very low outdoor temperatures. |
Contact service if resetting the alarm does not help. Register the current operating temperatures from the “Show data” menu in order to ease the service process. |
13 | ![]() |
Over temperature Supplementary electric heating HW. |
The temperature of the supplementary electric heating in the hot water tank has been too high. | Reset the overheat protection, which is situated behind the lower door. In case of repeated alarms, contact service. |
15 | ![]() |
The room temperature is too low |
When the room temperature falls below 10 °C, the unit will stop in order to prevent further cooling of the dwelling. This may, for instance, be during a period of the dwelling being unoccupied and the heating system having gone off. |
Heat up the dwelling and reset the alarm. |
16 | ![]() |
Software error | Error in the control system program. | Contact Service. |
17 | ![]() |
Watchdog warning | Error in the control system program. | Contact Service. |
18 | ![]() |
Content of database changed |
Parts of the program setting have been lost. This may be due to a prolonged power cut or a lightning strike. The unit will continue to operate with standard settings. |
Reset alarm. Set the week program you require. Contact service if the unit does not operate to your satisfaction/ as before, as some subprograms may have been lost. (Subprogram is only available for service). |
19 | ![]() |
Change filter | The filter monitor has been set at X amount of days for check-up/change of filter (30, 90, 180, 360 days). The standard setting is 90 days. | Clean/change filter. Reset alarm. |
20 | ![]() |
Error in legionella treatment |
Legionella treatment has not been performed within the time limit or number of attempts. | In case of repeated alarms, contact service. |
21 | ![]() |
Check date and time | Is displayed during power cuts. | The settings of the weekly clock must be checked and adjusted if necessary. Reset alarm. |
22 | ![]() |
Error in air temperature | It is impossible to heat the supply air as desired (only applicable if you have an after-heating element). The afterheating element and the unit cannot increase the temperature to the desired level. | Set a lower supply air temperature. Reset alarm. |
23 | ![]() |
Error in domestic hot water temperature |
Heating of domestic hot water is not possible. | Contact service |
27-58 | ![]() |
Error on the temperature sensor | One of the temperature sensors has either short circuited, been disconnected or is defective. | Register which sensor, Tx, is faulty and contact service. |
70 | ![]() |
Anode error | The hot water tank anode is either worn or not connected correctly. | Contact service |
72 | ![]() |
Abnormally low evaporator temperature |
Abnormal evaporator temperature (T6) is due to insufficient air volume. | Change filters, check outdoor air intake has not stopped. If error persists, contact service. |
92 | ![]() |
Backup error | Abnormal evaporator temperature (T6) is due to insufficient air volume. | Contact service. |
Product data
Ecodesign label
Ecodesign data cold climate
Heat pump combination heater – cold climate
Model | VGU1850EK |
Air-to-water heat pump | Yes |
Water-to-water heat pump | No |
Brine-to-water heat pump | No |
Low-temperature heat pump | Yes |
Equipped with a supplementary heater | Yes |
Heat pump combination heater | Yes |
Temperature control | |
Model | CTS602 |
Class | 2 |
Contribution to seasonal space heating energy efficiency | 2% |
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
Rated heat output (*) | Prated | 2.3 | kW | Seasonal space heating energy efficiency | ŋs | 147 | % | |
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature of Tj | Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj | |||||||
Tj = -7 °C | Pdh | 2.092 | kW | Tj = -7 °C | COPd | 3.82 | ||
Tj = +2 °C | Pdh | 2.103 | kW | Tj = +2 °C | COPd | 3.94 | ||
Tj = +7 °C | Pdh | 2.112 | kW | Tj = +7 °C | COPd | 4.00 | ||
Tj = +12 °C | Pdh | 2.096 | kW | Tj = +12 °C | COPd | 3.95 | ||
Tj = bivalent temperature | Pdh | 2.077 | kW | Tj = bivalent temperature | COPd | 3.68 | ||
Tj = operation limit temperature | Pdh | 2.119 | Tj = operation limit temperature | COPd | 3.70 | |||
For air-water-heat pumps Tj = -15 °C (hvis TOL < -20 °C) | Pdh | For air-water-heat pumps Tj = -15 °C (hvis TOL < -20 °C) | COPd | |||||
Bivalent temperature | Tbiv | -6 | For air-water-heat pumps Operation limit temperature | °C | ||||
Cycling interval capacity for heating | Pcych | Cycling interval efficiency | ||||||
Degradation co-efficient | Cdh | 0.9 | Heating water operating limit temperature | WTOL | °C | |||
Power consumption in modes other than active mode | Supplement heater | |||||||
Off mode | POFF | 0.0084 | Rated heat output | Psup | 9 | kW | ||
Thermostat off-mode | PTO | 0.0253 | ||||||
Standby mode | PSB | 0.0084 | Type of energy input | Electrical | ||||
Crankcase heater mode | PCK | 0,000 | ||||||
Other items | ||||||||
Capacity control | Variable indoor temperature regulation | For air-water-heat pumps Rated air flow outside | 360 | m3/h | ||||
Sound power level, outdoor | LWA | 58.2 | dB | |||||
Annual energy consumption | qHF | 2148 | kWh | |||||
Specified consumption profile | XL | Energy efficiency for water heating |
Ŋwh |
108 | % | |||
Daily electricity consumption | qelec | 7.212 | kWh | Daily fuel consumption | qfuel | |||
Annual energy consumption | AEC | 1557 | kWh |
Ecodesign average climate
Heat pump combination heater
Model | VGU1850EK |
Air-to-water heat pump | Yes |
Water-to-water heat pump | No |
Brine-to-water heat pump | No |
Low-temperature heat pump | Yes |
Equipped with a supplementary heater | Yes |
Heat pump combination heater | Yes |
Temperature control | |
Model | CTS602 |
Class | 2 |
Contribution to seasonal space heating energy efficiency | 2% |
Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
Rated heat output (*) | Prated | 2.5 | kW | Seasonal space heating energy efficiency | ŋs | 105 | % | |
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature of Tj | Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj | |||||||
Tj = -7 °C | Pdh | 2.078 | kW | Tj = -7 °C | COPd | 3.59 | ||
Tj = +2 °C | Pdh | 2.094 | kW | Tj = +2 °C | COPd | 3.77 | ||
Tj = +7 °C | Pdh | 2.109 | kW | Tj = +7 °C | COPd | 3.97 | ||
Tj = +12 °C | Pdh | 2.151 | kW | Tj = +12 °C | COPd | 4.13 | ||
Tj = bivalent temperature | Pdh | 2.074 | kW | Tj = bivalent temperature | COPd | 3.64 | ||
Tj = operation limit temperature | Pdh | 2.119 | Tj = operation limit temperature | COPd | 3.70 | |||
For air-water-heat pumps Tj = -15 °C (hvis TOL < -20 °C) | Pdh | For air-water-heat pumps Tj = -15 °C (hvis TOL < -20 °C) | COPd | |||||
Bivalent temperature | Tbiv | -6 | For air-water-heat pumps Operation limit temperature | °C | ||||
Cycling interval capacity for heating | Pcych | Cycling interval efficiency | ||||||
Degradation co-efficient | Cdh | 0.9 | Heating water operating limit temperature | WTOL | °C | |||
Power consumption in modes other than active mode | Supplement heater | |||||||
Off mode | POFF | 0.0084 | Rated heat output | Psup | 9 | kW | ||
Thermostat off-mode | PTO | 0.0253 | ||||||
Standby mode | PSB | 0.0084 | Type of energy input | Electrical | ||||
Crankcase heater mode | PCK | 0,000 | ||||||
Other items | ||||||||
Capacity control | Variable indoor temperature regulation | For air-water-heat pumps Rated air flow outside | 360 | m3/h | ||||
Sound power level, outdoor | LWA | 58.2 | dB | |||||
Annual energy consumption | qHF | 1732 | kWh | |||||
Specified consumption profile | XL | Energy efficiency for water heating | Ŋwh | 108 | % | |||
Daily electricity consumption | qelec | 7.212 | kWh | Daily fuel consumption | qfuel | |||
Annual energy consumption | AEC | 1557 | kWh |
CE declaration
EU/EC Declaration of Conformity
For the CE-marking inside the European Union
Nilan A/S
We declare that the Ventilation and Air to Water Heat Pump
VGU250
Confirm to the following EU/EC Directives, providing the products are used in accordance with the ordinary use.
EU-Directives:
- Directive on harmonization of the laws of the Member States concerning pressure equipment (pressure equipment directive) 2014/68/EU
- Directive on harmonization of the laws of the Member States relating to electrical equipment to be used within certain voltage limits (the low voltage directive) 2014/35/EU
- Household and similar electrical appliances – Safety – Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers. IEC 60335-2-40:2013
- Directive on harmonization of the laws of the Member States relating to electromagnetic compatibility (EMC directive) 2014/30/EU
- Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS directive) 2011/65/EU
- Directive of Energy Related Products in a framework which primarily focuses on environmental care of requirements for energy-related products (ECODESIGN) 2009/125/EU
Harmonized standards applied and EU regulations, in particular:
Nilan A/S, Nilanvej 2, 8722 Hedensted, Denmark,
Phone: +45 76 75 25 00,
Fax: +45 76 75 25 25, CVR-no. 11 77 33 97
www.nilan.dis
CEO and Owner: Torben Andersen
All rights reserved.
Document no.B24_VGU180-EK_GB
Nilan A/S disclaims all liability for potential errors and omissions in printed instructions – or for loss or damages arising f rom published materials, whether these are due to errors or inexpediency in the publications or they have other causes. Without prior notice Nilan A/S reserves the right to make changes t o products and instructions. All trademarks belong to Nilan A/S.
Nilan A/S
Nilanvej 2
DK-8722 Hedensted
Tlf. +45 76 75 25 00
Fax +45 76 75 25 25
nilan@nilan.dk
www.nilan.dk
Documents / Resources
![]() |
NILAN CTS602 HMI Upgrade Kit [pdf] User Manual CTS602 HMI Upgrade Kit, CTS602, HMI Upgrade Kit, Upgrade Kit |
![]() |
NILAN CTS602 HMI Upgrade Kit [pdf] Instruction Manual CTS602 HMI Upgrade Kit, CTS602, HMI Upgrade Kit, Upgrade Kit |
![]() |
NILAN CTS602 HMI Upgrade Kit [pdf] Installation Guide CTS602 HMI Upgrade Kit, CTS602, HMI Upgrade Kit, Upgrade Kit |