Instruction Manual for NILAN models including: CTS602 HMI Upgrade Kit, CTS602, HMI Upgrade Kit, Upgrade Kit

S24 DHW AIR GB

bel

SOFTWARE INSTRUCTIONS


File Info : application/pdf, 32 Pages, 772.98KB

PDF preview unavailable. Download the PDF instead.

S24 DHW AIR GB
SOFTWARE INSTRUCTIONS
CTS602 HMI BY NILAN

0°C

55°C 57°C

34°C

DHW AIR
Gateway

Version 1.10 - 01.08.2023 S24 DHW AIR GB

Table of contents
Installation
Central heating ..................................................................................................................................................................................... 3 Domestic hot water .............................................................................................................................................................................. 3
Software
Functions in the control panel ................................................................................................................................................................... 4 Main screen items ................................................................................................................................................................................ 4 Main screen settings options ............................................................................................................................................................. 5 Warnings and alarms ............................................................................................................................................................................ 6 Settings menu overview ..................................................................................................................................................................... 6 Installer access ...................................................................................................................................................................................... 7
Start-up settings ......................................................................................................................................................................................... 8 Language ................................................................................................................................................................................................ 8 Date/time ............................................................................................................................................................................................... 8
Unit settings ................................................................................................................................................................................................. 9 Turn on unit ............................................................................................................................................................................................ 9 Operation mode .................................................................................................................................................................................... 9 Alarm .................................................................................................................................................................................................... 10 Show data ............................................................................................................................................................................................11 Week program ..................................................................................................................................................................................... 12 Hot tapwater .......................................................................................................................................................................................13 Central heating ................................................................................................................................................................................... 14 Silent mode .......................................................................................................................................................................................... 16 Service settings .................................................................................................................................................................................. 16 Factory settings .................................................................................................................................................................................. 16
Service settings ......................................................................................................................................................................................... 17 Hot tapwater .......................................................................................................................................................................................17 Central heating ................................................................................................................................................................................... 18 Heat pump ............................................................................................................................................................................................19 Regulation ............................................................................................................................................................................................20 Smart grid ............................................................................................................................................................................................21 Defrost ................................................................................................................................................................................................. 22 Fatory reset ......................................................................................................................................................................................... 22 Manual test .......................................................................................................................................................................................... 23 Modbus address .................................................................................................................................................................................. 23 Data log interval .................................................................................................................................................................................24 Screen settings ................................................................................................................................................................................... 24 Run time ............................................................................................................................................................................................... 25
Alarm list
DHW AIR ...................................................................................................................................................................................................... 26 Alarm list .............................................................................................................................................................................................. 26
2

Installation
Central heating
How to set the central heating.
Functions What is the desired settings By which curve the control must regulate according to Should the curve be shifted so that it better suits the heat demand Desired flow temperature is set Maximum flow temperature at wooden floor

Curve / Flow temperature
Yes/No Yes/No Yes/No

Settings
Level: °C: °C: °C:

Domestic hot water
How to set the domestic hot water.
Functions What is the desired hot water temperature Should the electrical supplement be used and at what temperature Should the unit run automatic legionella treatment

Yes/No Yes/No

Settings °C: °C: Day:

3

Software

Functions in the control panel

Main screen items
The main screen of the HMI panel shows the information and the settings options that a user mostly requires.

9 6

1

7

0°C

2

3

5

4

55°C

8
34°C

1. Shows the current outdoor air temperature, measured in DHW AIR outdoor unit
2. Shows the domestic hot water temperature in the DHW tank 3. Shows supplementary electric heating domestic hot water is active. 4. Shows supplementary electric heating central heating is active. 5. Shows the supply flow temperature for the central heating in the
buffer tank. 6. Shows active menu icons in this menubar. 7. Shows active operation icons in this menubar. 8. Shows the fan in the DHW AIR outdoor unit is active. 9. Access to the settings menu

Menu-ikoner
Stop icon Indicates that the unit has stopped.

Drift-ikoner
De-icing icon Indicates that the heat pump is de-icing.

Week program icon Indicates that the week program function is active.
Alarm icon Indicates an alarm or a warning.
Compressor icon Indicates that the compressor is active.

Heating water in central heating circuit icon Indicates that the unit is producing hot water for the central heating circuit.
Domestic hot water icon Indicates that the unit is producing domestic hot water.

4

Main screen settings options
The settings options that the user needs in daily life are located on the main screen of the panel. You simply press the temperature for domestic water or central heating in order to change it.
When you press the temperature for domestic water, you will see the following panel for the selected setpoint temperature of domestic water:
You can change the hot water temperature by using the upand-down arrows. You then confirm by pressing the confirm icon, bottom right. The main screen of the panel will then be displayed again. If you select the cancel icon, bottom left, the temperature will revert to the original setting. Following this, you have to press the arrow, top left. This takes you back to the main screen.

If you press the temperature for central heating, one of the two panels below will be displayed. Which one depends on whether you have selected a fixed flow temperature for central heating or to regulate via weather compensation:

You can change the setpoint temperature for central heating by using the up-and-down arrows. You then confirm by pressing the confirm icon, bottom right. The main screen of the panel will then be displayed again. If you select the cancel icon, bottom left, the temperature will revert to the original setting. Following this, you have to press the arrow, top left. This takes you back to the main screen.

You can change the selected curve for weather compensation from this panel screen in the same way as described for the `Central Heating' function in `Unit Settings'.

5

Warnings and alarms

0°C

55°C 34°C

If the unit is faulty or an error occurs, there will be either a warning or an alarm. The icon will appear in the top right hand corner in the menu bar.

If you press the symbol, a brief description of the warning or the alarm will be displayed.
As soon as the problem is solved the big C- or W-letter will change to a small c- or w-letter.

When the problem has been solved, you can reset the warning or alarm by pressing "Clear Alarm".

You will find more detailed descriptions in the "Alarm List" section of this document.

Settings menu overview
The settings menu is constructed to make it easy to navigate through.

You navigate through the settings menu by pressing the arrow below or above. If you want to access a menu, tap the text for that menu and it will open.

6

Installer access
Settings menus consist of 3 levels. 1. User level - Settings the user can access and customize. 2. Service level - Settings that the installer needs to access in order to set the ventilation unit in relation to individual installation.
It requires expertise knowledge to select these settings. If the settings are not correct, the ventilation unit may not operate properly and it may consume more energy than necessary. The unit may even get damaged. 3. Factory level - Only Nilan has access.

The Service menu is located at the bottom of the User settings. Tap the down arrow several times to get there.

A password is required to access the Service menu.
You can set the password by using the up-or-down arrows followed by the confirm icon (bottom right).

7

Start-up settings

Language
The default language for the unit is Danish. You can change the texts to other languages in the settings menu.
> Language (DK - Sprog)

> Dansk

Description:

Select the language you want on the panel.

Date/time
It is important to set date and time correctly. It makes it easier to trace potential faults when an error is being reported. When logging data, it is important to be able to follow the history. You set the time in the settings menu.
> Date/time

> Year > Month > Day > Hour > Minute

Description: Description: Description: Description: Description:

Press "Year" on the panel and select the current year. Press "Month" on the panel and select the current month. Press "Day" on the panel and select the current day of the week. Press "Hour" on the panel and select the current hour of the day. Press "Minute" on the panel and select the current minute.

8

Unit settings
Turn on unit
When you turn on theheat pump unit, the control panel will light up, but all functions are off. This is to prevent errors from occurring when you turn on the unit.
When the unit is off, this icon is displayed on the main screen of the control panel at the top righthand corner.
ATTENTION Before touching the electrical installations, the power supply must be disconnected.
ATTENTION When the unit is off in the HMI-panel the frost protection function of the unit is still active.

You activate the functions of the unit in the settings menu under the menu item "Operation mode".
> Unit On / Off

> Unit On / Off > Off

Settings: Standard setting: Description:

Off / On Off The DHW AIR unit is switched off when it is delivered in order to prevent errors from occurring during connection.
This is also where you turn off unit when service inspection is to be carried out.

Operation mode
You can set the unit to operate in "Auto", "Winter" or "Summer" mode.
ATTENTION The Winter and Summer functions override the week program. If a week program has been activated, the mode will automatically change to "Auto" at the next shift in the week program.

> Operation mode
> Operation mode > Auto

Settings: Default setting: Description:

Auto / Winter / Summer Auto Auto:The unit is operating according to preset values. At outdoor temperatures above 17°C for 24 hours, operation will switch to summer mode. At outdoor temperatures below 13°C for 24 hours, operation will switch to winter mode. Winter: The unit produces hot water for central heating as well as for domestic hot water. Summer: The unit is set to produce only domestic hot water.

9

Alarm
You can read off warnings and alarms under the "Alarm" menu item. This is also where you reset them once the problem has been solved.
If an alarm or a warning is active, the alarm icon will be displayed in the upper righthand corner of the control panel.

> Alarm
> Alarm number and name > Alarm

Description:

When you press the alarm, the following information will be displayed: · Alarm ID number · Type of alarm · Critical alarm or warning (The alarm list will inform you of how to proceed.)

ATTENTION
Until the problem has been solved, the alarm or warning will remain active. When the problem has been solved, you will be able to reset the alarm or warning by pressing "Clear alarm".

10

Show data
You can read off current operating data for the unit. This will help you ensure that the unit is operating satisfactorily. It can also help you identify the cause of potential alarms.
> Show data

> Status

Description:

> Operation mode

Description:

> Anode

Description:

> T16 Return heating

Description:

> T17 Supply heating

Description:

> T18 Buffer tank

Description:

> T20 Outdoor temperature > T21 Top temperature

Description: Description:

> T22 Bottom temperature

Description:

> T23 Evaporator temperature
> T35 Pressure pipe temperature
> Water setpoint

Description: Description:
Description:

> Heating setpoint

Description:

> Actual capacity > Inverter > Fan power > Unit information
> AIR SW. version > Panel software

Description: Description: Description: Description: Description: Description:

Shows the operating setting in which the unit is running: Off: Heat pump stopped. HP stop: The heat pump has stopped due to an alarm. Wait: Compressor is still prevented from starting up. The stopping-time has not passed. Ready: The stopping-time has passed and the compressor is ready for start-up. Start-up: Start-up heat pump. Hot water: Heating of domestic hot water by either a heat pump or supplemental electric heating. Heating: Central heating heated by either a heat pump or supplemental electric heating.
Shows whether the user has selected `Winter' or `Summer' mode manually in Operation mode, or which type of operation AUTO has selected automatically.
Shows whether the anode is in working order. Display: Off, OK, Error or Service. In the case of Error or Service, please contact a technician.
Shows the current temperature of the return flow from the indoor unit to the outdoor unit.
Shows the current temperature of the supply flow from the outdoor unit to the indoor unit.
Shows the current temperature of the supply flow to the buffer tank.
Shows the outdoor temperature measured in the outdoor unit.
Shows the current temperature at the top of the DHW tank. Controls the supplemental electric heating.
Shows the current temperature at the bottom of the DHW tank. Controls the heat pump.
Shows the current evaporator temperature.
Shows the temperature in the pressure pipe.
Currently used setpoint for domestic water. The setpoint you select can be staggered by a week program or Smart Grid.
Currently used setpoint for central heating. You can select the setpoint manually or it can be selected automatically by the weather compensation. It may be staggered by a week program or Smart Grid.
Shows the capacity of the compressor in %
Shows the current control voltage to the inverter/compressor
Shows the current control voltage to the fan by the evaporator
Shows information about the unit in the submenus
Current AIR controller software version
Current panel/HMI350T software version

11

Week program
You can program the heat pump unit to run in accordance with specific settings at fixed times during the week via a week program. For both domestic hot water and central heating, the set point can be moved up or down during selected periods. In this way, the weekly program can work well together with the weather compensation. It is also possible to completely block domestic hot water or central heating in periods.
On the main screen in the top righthand corner of the control panel the icon for the week program is displayed when this function is active.

> Week program
> Select program > Edit program
> Program 1-3
> Monday - Sunday

Settings: Default setting: Description:
Settings: Description:
Settings:
Description:
Settings: Description:

> Function 1 - Function 6

Settings:

> Start time > Domestic hot water > Central heating > Copy next day > Reset program

Description: Settings: Description:
Settings: Description:
Settings: Description:
Description:
Settings:

De-activated / Program 1 / Program 2 / Program 3 De-activated The control system allows you to set 3 programs to meet the daily operational needs of the user.
Program 1 / Program 2 / Program 3 Under the individual program, you can set the operation of the heat pump unit with regards to days of the week and functions
Monday / Tuesday / Wednesday / Thursday / Friday / Saturday / Sunday Monday For each day of the week, you select which function you want the heat pump unit to operate in accordance with on the individual weekday.
Function 1 / Function 2 / Function 3 / Function 4 / Function 5 / Function 6 / Copy next day Here the functions are built with regards to the desired operation of the unit. Functions 1-4 are factory-built, but they can be changed as explained below. Function 6 is deactivated as default, but this can also be changed as instructed below. `Copy next day' is used when you want to use the same settings the following day. Select `Copy next day' and .....++++
Start time / Domestic hot water / Central heating Function 1: 00:00 / Setpoint +5°C / Setpoint +5°C Function 2: 11:00 / Setpoint +0°C / Setpoint +0°C Function 3: 17:00 / Setpoint -5°C / Setpoint -5°C Function 4: 21:00 / Setpoint +0°C / Setpoint +0°C Function 5: Deactivated Function 6: Deactivated
De-activated / 00:00 - 23:45 Set the time for the program to start. The program then runs in accordance with the selected values until the next change in the week program.
Off / Setpoint -5°C - Setpoint +5°C This is where you select at which temperature the production of domestic hot water is activated in relation to the selected setpoint for domestic water.
Off / Setpoint -5°C - Setpoint +5°C This is where you select at which temperature the production of central heating is activated in relation to the selected setpoint for central heating.
When you have entered some values for the program for a particular day, you will have the option to copy and use the same values the following day.
This is where you reset the selected program by pressing the "Approve" icon.

12

Hot tapwater
Settings for domestic hot water production have been set at the factory, but it may be necessary to adjust them to meet the exact requirements of the user.
> Hot tapwater

> Setpoint > El. supl. heater

Settings: Standard setting: Description:
Settings: Standard setting: Description:

> Legionella day

Settings:
Standard setting: Description:

> Legionella stop temperature

Settings: Standard setting: Description:

5  55 ºC 40 ºC 5 - 55 ºC: Indicates the temperature (T22) below which the heat pump is working for production of domestic hot water.
5  55 ºC 35 ºC 5 - 55 ºC: Indicates the temperature (T21) below which the supplementary electric heating will supply the production of domestic hot water. Is only shown if the supplementary electric heating has been selected as heat source in Service settings.
De-activated / Monday / Tuesday / Wednesday / Thursday / Friday / Saturday / Sunday De-activated Here you indicate whether or not the unit is to run a weekly legionella treatment.*
50  65ºC 62 ºC Here you set the required temperature of the legionella treatment.

*When selecting a day of the week, the legionella function will start at 1 a.m. and heat the domestic hot water to selected setpoint °C. The function will only work if supplementary electric heating is active.

13

Central heating
Here, weather compensation is used to regulate the supply flow temperature of the central heating in order to optimize operation of the unit.
> Weather compensation / Curve for outdoor temperature

> Curve for outdoor temperature Settings:
Default setting: Description:

> Manual > Min. setpoint
>Offset
>Setpointatact.amb.temp.

Settings: Default setting: Description:
Settings: Default setting: Description:
Description:

> Curve point -20°C > Curve point -10°C > Curve point 0°C > Curve point 10°C > Curve point 20°C > Curve point 30°C > Curve point 40°C > Curve 1-10 > Min. setpoint
>Offset
> Setpoint at act.amb.temp.

Settings: Default setting:
Settings: Default setting:
Settings: Default setting:
Settings: Default setting:
Settings: Default setting:
Settings: Default setting:
Settings: Default setting:
Settings: Default setting: Description:
Settings: Default setting: Description:
Description:

De-activated / Manual / Curve 1 / Curve 2 / Curve 3 / Curve 4 / Curve 5 / Curve 6 / Curve 7 / Curve 8 / Curve 9 / Curve 10 Deactivated De-activated: The unit is regulated in accordance with a fixed supply flow temperature. Manual: Here you can define the curve yourself. When switching from a fixed curve to a manual curve, the basis will initially be the last fixed curve that was used.
10  55 ºC 20 ºC This is where you set the minimum supply flow temperature.
-10  10 ºC 0 ºC Offset in relation to the selected curve
The temperature here is a readout of the setpoint of the weather compensation at current outdoor temperatures and settings for curve selection, offset, min. and max. settings.
10 - 100 °C 50°C
10 - 90 °C 47°C
10 - 70 °C 40°C
10 - 55 °C 31°C
10 - 55 °C 20°C
10 - 55 °C 20°C
10 - 55 °C 20°C
10  55 ºC 20 ºC This is where you set the minimum supply flow temperature.
-10  10 ºC 0 ºC Offset in relation to the selected curve
The temperature here is a readout of the setpoint of the weather compensation at current outdoor temperatures and settings for curve selection, offset, min. and max. settings.

14

Curve control The supply flow temperature is automatically regulated in accordance with a curve.

Max. Min.

20

15

10

5

Supply flow temperature
100

10

90

9 80
8

7

70

6 60
5

4

50

3 40
2

1

30

20

0

-5

-10

-15

-20

Outdoor temperature

15

Silent mode
In order to meet increased regulation regarding noise near property lines in the evening and during the night , as well as on hot summer days, you can limit the compressor capacity for specified time periods. Limitation can be regulated in accordance with outdoor temperatures and time intervals.
> Silent mode

> Seasonal limitation > Outdoor temp. limitation

Settings: Default setting: Description:

> Limit above > Limit below > Night limitation > Activation
>Start > End > Limit

Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:

0 - 30°C 7°C Based on the selected outdoor temperature limit, you select the maximum compressor capacity limitation above and below this temperature limit. This function is active when producing central heating and domestic hot water.
25  100% 60% This is where you set the maximum compressor capacity to be used at an outdoor temperature above the "Outdoor temperature limit"
25  100% 100% This is where you set the maximum compressor capacity to be used at an outdoor temperature below the "Outdoor temperature limit"
Activated / Deactivated Deactivated When activating time-limited capacity limitation, you can regulate time intervals and the compressor capacity for night limitation.
00:00 - 23:30 22:00 This is where you set the start time for limitation of the compressor capacity.
00:00 - 23:30 07:00 This is where you set the finishing time for limitation of the compressor capacity.
30 - 100% 40% Here you select the capacity limit of the compressor

Service settings
Password for access to service settings: 2
WARNING Service settings are intended for qualified installers with knowledge of the workings of the heat pump unit. They can identify the appropriate settings for the unit.
If a user alters these settings, the heat pump unit will no longer operate to its full potential. It may result in higher energy consumption, and errors may occur and cause damage to the unit.

Factory settings
Password factory settings: Only access for qualified Nilan installers.

16

Service settings

Hot tapwater
The settings for domestic hot water production have been set at the factory, but it may be necessary to adjust them to meet the exact requirements of the user.
> Hot tapwater

> Hot water source
> HP > Neutral zone > Hot water capacity
> EL > Neutral zone
> HP+EL > Neutral zone > Electric heating delay
> Hot water capacity

Settings: Default setting: Description:
Settings: Default setting: Description: Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description: Settings: Default setting: Description:
Settings: Default setting: Description:

None / HP / EL / HP+EL HP+EL This is where you select which heat source you want to use to heat domestic hot water.
0  15 ºC 4ºC Select the control band for electric heating of domestic water.
10 - 100% 70% Select maximum compressor capacity when heating domestic hot water.
0  15 ºC 4ºC Select the control band for electric heating of domestic water.
0  15 ºC 4ºC Select the control band for electric heating of domestic water.
0  120 min. 30 min. If during operation the heat pump is unable to reach the desired set point, this setting indicates the period of time that must pass before supplemental electric heating starts up.
10 - 100% 70% Select maximum compressor capacity when heating domestic hot water.

17

Central heating
Settings for the air to water heat pump.
> Central heating

> Heating source

Settings: Default setting: Description:

> HP > Min setpoint

Settings: Default setting: Description:

> Max setpoint > Min. Compr. Stop time
> EL > Min setpoint

Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:

> Max setpoint
> HP + EL > Min setpoint

Settings: Default setting: Description:
Settings: Default setting: Description:

> Max setpoint > Electrical neutral zone > Electric heat delay

Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:

> Min. Compr. Stop time

Settings: Default setting: Description:

None / HP / EL / HP+EL HP + EL Select the heat source for heating of water in the central heating system
10 - 55 °C 20 °C If you have selected a constant supply flow temperature, this is the setpoint. If you have selected weather compensation, this is the lowest supply flow temperature for the central heating.
20 - 55 °C 55 °C The highest supply flow temperature of the central heating.
1  45 min 5 min Min. length of time the compressor must have stopped before it can start up again.
10 - 55 °C 20 °C If you have selected a constant supply flow temperature, this is the setpoint. If you have selected weather compensation, this is the lowest supply flow temperature for the central heating.
20 - 55 °C 55 °C The highest supply flow temperature of the central heating.
10 - 55 °C 20 °C If you have selected a constant supply flow temperature, this is the setpoint. If you have selected weather compensation, this is the lowest supply flow temperature for the central heating.
20 - 55 °C 55 °C The highest supply flow temperature of the central heating.
0 - 15 °C 4 °C Select the control band for electric heating of the central heating.
0 - 60 min 30 min If during operation the heat pump is unable to reach the desired setpoint, this setting indicates the period of time that must pass before supplemental electric heating can start up.
1  45 min 5 min Min. length of time the compressor must have stopped before it can start up again.

18

Heat pump
Settings for the air to water heat pump.
> Heat pump

> Min. comp run time

Settings: Default setting: Description:

> Pump exercise

Settings: Default setting: Description:

> HP stop sensor > HP stop temperature

Settings: Default setting: Description:
Settings: Default setting: Description:

> Total stop sensor

Settings: Default setting: Description:

> Total stop temperature

Settings: Default setting: Description:

> HP stop outdoor temperature

Settings: Default setting: Description:

> Evaporator temp. min.

Settings: Default setting: Description:

0  600 sec 60 sec Min. period of time the compressor has to operate before it can stop.
De-activated / 1  60 days De-activated 1-60 days: Exercise of the circulation pumps. If the pums for the unit have not been excercised within the selected time period, all pumps are activated for 15 seconds.
None / Supply / Return Return This shows at which sensor (T16 Return flow / T17 Supply flow) the compressor should stop at high temperatures.
30  65 ºC 60 ºC This is where you select the temperature at which the compressor should stop. The heat pump will start up again automatically.
None / Supply / Return Supply This shows the sensor at which all heat supply should stop at high temperatures.
30  70 ºC 70 ºC Here you select the temperature below which all heat supply should stop.
-45  10 ºC -17 ºC Select a limit for the outside temperature below which the compressor will not be activated.
-45 - 5°C -45°C Select limit for frost protection. When the evaporator temperature drops towards this limit, the compressor speed is reduced, and below this limit the compressor stops.

19

Regulation
Settings for the air to water heat pump.
> Regulation

> Stop capacity > Start diff. capacity > Voltage at 0% > Voltage at 100% > Start voltage > Start skip > Stop skip

Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:

> Gain > Integration time

Settings: Default setting: Description:
Settings: Default setting: Description:

0  20% 1% The capacity below which heating stops.
0  20% 5% Capacity hysteresis before heating starts.
0.0 - 10.0 V 2.0 V Voltage at 0%, which is "Stop capacity" + "Start diff. capacity".
0.0 - 10.0 V 8.8 V Voltage at 100% operation, which is also 100% capacity.
0.0 - 10.0 V 6.5 V 5 seconds starting pulse voltage.
0.0 - 10.0 V 0.0 V Starting voltage for a voltage range that you do not wish to use.
0.0 - 10.0 V 0.0 V Stopping voltage for a voltage range that you do not wish to use.
1.0  20.0 5.0 Reinforcement of PI controller
30  600 sec. 240 sec. PI controller integration time.

20

Smart grid
In some countries Smart Grid can be economically advantageous because it regulates the power consumption of the heat pump in accordance with the price of electricity as it fluctuates in the course of 24 hours. Smart Grid receives an external signal from the power supply company. This determines in which operating setting the unit should run.

> Smart grid
> Smart g rid activation > Domestic hot water

Settings: Default setting: Description:
Settings: Default setting: Description:

> Hotwater temp. add > Central heating
> Central temp. add

Settings: Default setting: Description:
Settings: Default setting: Description:
Settings: Default setting: Description:

> Central overcap. add

Settings: Default setting: Description:

De-activated / Activated De-activated This is where you activate Smart Grid.
De-activated / Activated De-activated Here you select whether supplemental electric heating should be used for the production of domestic hot water during periods of cheap electricity. Supplemental electric heating must be activated.
0  10 ºC 0°C Here you specify how much the temperature in the hot water tank should be raised during periods of cheap electricity.
De-activated / Activated De-activated Here you select whether supplemental electric heating should be used for heating the water in the central heating system during periods of cheap electricity.
0  10 ºC 0 ºC Here you specify how much the supply flow temperature in the central heating circuit should be raised during periods with an overcapacity in electricity. Supplemental electric heating must be activated.
0  10 ºC 1 ºC Here you specify how much the supply flow temperature in the central heating circuit should be additionally raised during periods with an increased overcapacity in electricity.

21

Defrost
Only hot gas is used for defrost (active defrost)
> Defrost

> Defrost below

Settings: Default setting: Description:

> Defrost temperature

Settings: Default setting: Description:

> Time before defrost

Settings: Default setting: Description:

> Time between defrost

Settings: Default setting: Description:

> Evaporator stop temperature

Settings: Default setting: Description:

> Max. defrost time

Settings: Default setting: Description:

-45  10 ºC 0 ºC Here you select the temperature below which the heat pump can deice.
2  15 °C 6 °C
Here you specify at which T between the evaporator temper-
ature and the outdoor temperature deicing may start.
0  240 min. 20 min. Here you specify how much time has to pass after the deicing temperature has been reached before deicing is to start.
10  480 min. 45 min. Here you select the minimum time that has to pass between each occurrence of deicing.
1  25 °C 3°C Here you specify at which temperature the hot gas deicing is to stop.
1  240 min. 10 min. Here you specify the maximum time that deicing of the evaporator element is allowed to last. If deicing has not been completed within the set time, an alarm will be displayed and the unit will stop.

Fatory reset
You can restore the factory settings.
> Factory reset

> Factory reset

Settings: Standard settings: Description:

De-activated / Activated De-activated Activated: Restores factory settings

22

Manual test
In this menu you can manually test some of the functions of the ventilation unit.
> Manual test

> Main switch
> RE1 SHW heater
> RE2 El-heater > RE3 3-way SHW > RE4 P2 pump > RE5 P1 pump > Compressor > Compressor heater > 4-way valve > Drain heat > Compressor
> Fan power

Settings: Default setting: Description:
Description:
Description: Description: Description: Description: Description: Description: Description: Description: Description:
Description:

Off / On / Manual Off Here you select the run mode of the unit. When you select manual, you will be able to check some of the functions of the unit.
On / Off supplemental electric heating in the domestic water tank DHW
On / Off supplemental electric heating in the buffer tank
On / Off 3-way valve on domestic water tank DHW
On / Off circulation pump P2 for central heating
On / Off circulation pump P1 for buffer tank
On / Off compressor
On / Off heating of belt for compressor (R4 outdoor unit)
On / Off 4-way valve / cooling / deicing (R3 outdoor unit)
On / Off heating cable for drain (R4 outdoor unit)
0 - 100%: Select output capacity of the compressor (A01 outdoor unit)
0 - 100%: Select output capacity of the fan (A02 outdoor unit)

Modbus address
The control in NIlan DHW AIR unit has an open Modbus communication, which allows the unit to be controlled with e.g. an external CTS controller.
The CTS602 control communicates Modbus RS485, and the complete Modbus protocol can be downloaded from the Nilan website.
> Modbus adress

> Modbus address

Settings: Standard setting: Description:

1  247 30 The Modbus address for the heat pump unit.

23

Data log interval
Data can be logged at intervals of 1-1092 minutes.
· Operating data are actual readings or outputs. · Alarms are always logged when an alarm is activated or reset. · An event is either a change of an important setting or a particular operation.
Note! Only installers can download the log file, as an LMT program is required, which can be downloaded on NilanNet.
> Data log interval

> Data log interval

Settings: Standard setting: Description:

1  1092 min. 60 min. If logged with the default setting every hourthe data log can last approx. 1 year.

Data logging In order to data log you need the XML file "Devicelog.xml", which is a decoding specification required by the LMT PC program. The file can be downloaded from NilanNet under the menu item "After Sales/Software".
· Enter the file in the "..\Database" directory under the current LMT project. · You can then retrieve the log from the control system via the menu "Device - Devicelog download". · The log is shown in LMT in both tabular and graphic form. · You can export the log file to Microsoft Excel format.

Screen settings
It is possible to set the backlight in the control panel as well as calibrate it in case it comes out of focus.
> Screen settings

> Backlight (active) > Backlight (idle) > Calibrate

Settings: Standard setting: Description:
Settings: Standard setting: Description:
Settings: Standard setting: Description:

3  100 % 100 % Here you set the backlight when in active function.
0  100 % 2 % Here you set the backlight when not in active function.
No / Yes No If you select "Yes", it is possible to calibrate the screen by pressing the point as it gradually moves.
A dot appears that you must press each time it moves.

24

Run time
In this menu it is possible to see the total number of operating hours for the total unit and the operating hours for individual powerusing components
> Run time

> Heat pump > Compressor > Heater > Domestic hot water > P1 pumpe > P2 pumpe > Defrosting

Hours Hours Hours Hours Hours Hours Hours

Operating hours power connection DHW AIR unit. Operating hours compressor. Operating hours electrical supply heating central heating. Operating hours electrical supply heating domestic hot water. Operating hours for circulation pump P1. Operating hours circulation pump P2 central heating. Operating hours for de-icing evaporator.

25

Alarm list
DHW AIR
Alarm list
The following list applies to ventilation units with the CTS602 control. The events are divided into the following categories:

Warning

Operation continues, but an incident has occurred that should be kept in mind.

Alarm

Operation is partially or completely stopped as it is a critical fault that needs immediate attention.

ID Type 100 101 102 103 104 105 106 107 110 111 116 117 124

Display text THeatSupply Open THeatSupply Short THeatReturn Open THeatReturn Short TSHWBottom Open TSHWBottom Short Tamb Open Tamb Short THeatTank Open THeatTank Short Tevap Open Tevap Short TSHWTop Open

Description / cause

Troubleshooting

T17 Heating supply temperature open connection.

Check cable and connectors. Measure the resistance in the temperature sensor.

T17 Heating supply temperature shortcircuited.

Check cable and connectors. Measure the resistance in the temperature sensor.

T16 Heating return temperature open connection.

Check cable and connectors. Measure the resistance in the temperature sensor.

T16 Heating regurn temperature shortcircuited.

Check cable and connectors. Measure the resistance in the temperature sensor.

T22 Water tank temperature open connection.

Check cable and connectors. Measure the resistance in the temperature sensor.

T22 Water tank temperature short-circuited.

Check cable and connectors. Measure the resistance in the temperature sensor.

T20 Ambient temperature open connection.

Check cable and connectors. Measure the resistance in the temperature sensor.

T20 Ambient temperature short-circuited.

Check cable and connectors. Measure the resistance in the temperature sensor.

T18 Heating tank temperature open connection.

Check cable and connectors. Measure the resistance in the temperature sensor.

T18 Heating tank temperature short-circuited.

Check cable and connectors. Measure the resistance in the temperature sensor.

T23 Evaporator sensor temperature open connection.

Check cable and connectors. Measure the resistance in the temperature sensor.

T23 Evaporator sensor temperature shortcircuited.

Check cable and connectors. Measure the resistance in the temperature sensor.

T21 Temperature sensor in SHW opne connection.

Check cable and connectors. Measure the resistance in the temperature sensor.

26

125

TSHWTop Short

T21 Temperature sensor in SHW shortcir- Check cable and connectors.

cuited.

Measure the resistance in the temperature

sensor.

126

TSHWAnode

After the anode signal has been within the This may be due to an open or short-cir-

approved range, the signal is now outside cuited connection or due to a change in the

the expected range.

resistance value in the anode as a result of

corrosion.

If the database parameter HotWa-

ter.AnodeState has a value of 2, the anode

may need to be replaced due to corrosion

127

TPresTube Open

T35 Temprerature sensor Pressure open

Check cable and connectors.

connection.

Measure the resistance in the temperature

sensor.

128

TPresTube Short

T35 Temperature sensor Pressure short-

Check cable and connectors.

circuited.

Measure the resistance in the temperature

sensor.

600

HighPres

High pressure switch active.

Check hot side pump/overflow valve on high temperature side. Check if there is air in the hot side water. Check if filter is blocked on the hot side. The unit restarts when the pressure drops below high pressure switch lowlimit again. After 3rd cut-out the alarm must be acknowledged to start the unit again.

601

LowPres

Low pressure switch active.

Check refrigerant charge, expansion valve and evaporator for ice. Check fan for obstacles on an air to water evaporator. The alarm must be acknowledged to start the unit again.

603

HighPresRep

High pressure switch repeatedly active

Check hot side pump/overflow valve on

more than 3 times

high temperature side.

The alarm must be acknowledged to start

the unit again.

604

FrostProt

Frost protection has been activated

Heat pump and electrical heater running full capacity. Check that setting are not turned off.

607

LegioFail

The anti-legionella function failed. The desired temperature could not be reached within the set time limit.

Check the electric heating element and the heat supply from the heat pump.

608

FCalarm

FC alarm relays has been activated

Check electrical connecton and power to the inverter. Check if the compressor is running.

609

FCalarmRep

FC alarm relays has been activated repeat- Check electrical connection and power to

edly.

the inverter.

Check if the compressor is running.

610

Tevap Low

Evaporator temperature too low.

Brine circuit has low capacity. Risk of frost damage to the brine circuit.

611

TevapLowRep

Evaporator temperature too low.

Compressor stopped due to too low brine temperature. Compressor stopped to prevent frost damage.

615

ElHeater

8 hours (or more) with electric heating element.

Electric heating has been active, without interruption, for 8 hours or more. Check the connection of the electric element. Check also that heating is otherwise possible and that it is not lessened by other / unnecessary cooling.

630

HPstopAmb

The compressor has stopped due to a high The alarm is automatically reset and the

outdoor temperature.

system resumes normal mode when the

temperature falls below the set tempera-

ture limit again.

27

631

HPstop

The compressor has stopped because too high a temperature has been detected by the selected stop sensor.

The alarm is automatically reset and the system resumes normal mode when the temperature falls below the set temperature limit again.

632

HPstopTotal

The compressor and supplemental electric The alarm is automatically reset and the

heating have stopped because too high a

system resumes normal mode when the

temperature has been detected by the

temperature falls below the set tempera-

selected stop sensor.

ture limit again.

908

RTCinv

Invalid data from the real time clock.

Unit powered off to long. Set time and date. Else replace the controller.

910

SlaveSession

Error in communication with the outdoor

Check the cable and the cable connections

unit

if this error occurs several times and not

only after the system has been restarted.

995

SW_UPGRADE

The software has prevented an update

The warning can only be removed by

with unsupported firmware in which an old restarting the system

type of ATMEL FLASH was used.

999

Manual

The unit is in manual mode.

The warning is only active when the unit is in Manual mode.

28

Nilan A/S Nilanvej 2 8722 Hedensted Danmark Tlf. +45 76 75 25 00 nilan@nilan.dk www.nilan.dk

Nilan A/S disclaims all liability for potential errors and omissions in printed instructions - or for loss or damages arising from published materials, whether these are due to errors or inexpediency in the publications or they have other causes. Without prior notice Nilan A/S reserves the right to make changes to the products and instructions. All trademarks belong to Nilan A/S. All rights reserved.



References

Adobe PDF Library 17.0