Beijer ELECTRONICS GT-4468 Analog Output Module
The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document. All examples in this document are only intended to improve understanding of the functionality and handling of the equipment. Beijer Electronics AB cannot assume any liability if these examples are used in real applications. In view of the wide range of applications for this software, users must acquire sufficient knowledge in order to ensure that it is correctly used in their specific application. Persons responsible for the application and the equipment must themselves ensure that each application is in compliance with all relevant requirements, standards, and legislation in respect to configuration and safety. Beijer Electronics AB will accept no liability for any damage incurred during the installation or use of equipment mentioned in this document. Beijer Electronics AB prohibits all modification, changes, or conversion of the equipment.
Head Office
- Beijer Electronics AB
- Box 426
- 201 24 Malmö, Sweden
- www.beijerelectronics.com
- +46 40 358600
About This Manual
This manual contains information on the software and hardware features of the Beijer Electronics GT-4468 Analog Output Module. It provides in-depth specifications, guidance on the installation, setup, and usage of the product.
Symbols Used in This Manual
This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information. The corresponding symbols should be interpreted as follows:
Safety
Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions! In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product. The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.
Product Certifications
The product has the following product certifications.
General Safety Requirements
WARNING
- Do not assemble the products and wires with power connected to the system.Doing so cause an “arc flash”, which can result in unexpected dangerous events(burns, fire, flying objects, blast pressure, sound blast, heat).
- Do not touch terminal blocks or IO modules when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
- Never let external metallic objects touch the product when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
- Do not place the product near inflammable material. Doing so may cause a fire.
- All wiring work should be performed by an electrical engineer.
- When handling the modules, ensure that all persons, the workplace and the packing are well grounded. Avoid touching conductive components, the modules contain electronic components that may be destroyed by electrostatic discharge.
CAUTION
- Never use the product in environments with temperature over 60℃. Avoid placing the product in direct sunlight.
- Never use the product in environments with over 90% humidity.
- Always use the product in environments with pollution degree 1 or 2.
- Use standard cables for wiring
About the G-series System
System Overview
- Network Adapter Module – The network adapter module forms the link between the field bus and the field devices with the expansion modules. The connection to different field bus systems can be established by each of the corresponding network adapter modules, e.g., for MODBUS TCP, Ethernet IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc.
- Expansion Module – Expansion module types: Digital IO, Analog IO, and Special modules.
- Messaging – The system uses two types of messaging: Service messaging and IO messaging.
IO Process Data Mapping
An expansion module has three types of data: IO data, configuration parameter, and memory register. The data exchange between the network adapter and the expansion modules is made via IO process image data by internal protocol.
Data flow between network adapter (63 slots) and expansion modules The input and output image data depend on the slot position and the data type of the expansion slot. The ordering of input and output process image data is based on the expansion slot position. Calculations for this arrangement are included in the manuals for network adapter and programmable IO modules. Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data.
Specifications
Environmental Specifications
Operating temperature | -20°C – 60°C |
UL temperature | -20°C – 60°C |
Storage temperature | -40°C – 85°C |
Relative humidity | 5% – 90% non-condensing |
Mounting | DIN rail |
Shock operating | IEC 60068-2-27 (15G) |
Vibration resistance | IEC 60068-2-6 (4 g) |
Industrial emissions | EN 61000-6-4: 2019 |
Industrial immunity | EN 61000-6-2: 2019 |
Installation position | Vertical and horizontal |
Product certifications | CE, FCC, UL, cUL |
General Specifications
Power dissipation | Max. 30 mA @ 5 VDC |
Isolation | I/O to logic: Isolation
Field power: Non-isolation |
UL field power | Supply voltage: 24 VDC nominal, class 2 |
Field power | Supply voltage: 24 VDC nominal Voltage range: 18 – 30 VDC
Power dissipation: 70 mA @ 24 VDC |
Wiring | I/O cable max. 2.0 mm2 (AWG 14) |
Torque | 0.8 Nm (7Ib-in) |
Weight | 58 g |
Module size | 12 mm x 99 mm x 70 mm |
Dimensions
Output Specifications
Output per module | 8 channels single ended, non-isolated between channel |
Indicators (logic side) | 8 green output status |
Resolution in ranges | 16 bit (include sign)
15 bits: 0.31 mV/bit |
Output range | 0 – 10 VDC |
Data format | 16 bits integer (2′ compliment) |
Module error | ±0.1 % full scale @ 25 ℃
±0.3 % full scale @ -40 °C, 70 ℃ |
Load resistance | Min. 2 kΩ |
Diagnostic | Field power off: LED blinking Field power on: No output LED off
Field power on: Output LED on |
Conversion time | 0.2 ms / all channels |
Calibration | Not required |
Common type | 2 common, field power 0 V is common (AGND) |
Wiring Diagram
Pin no. | Signal description |
0 | Analog output channel 0 |
1 | Analog output channel 1 |
2 | Analog output channel 2 |
3 | Analog output channel 3 |
4 | Analog output channel 4 |
5 | Analog output channel 5 |
6 | Analog output channel 6 |
7 | Analog output channel 7 |
8 | Output channel common (AGND) |
9 | Output channel common (AGND) |
LED Indicator
LED no. | LED function / description | LED color |
0 | OUTPUT channel 0 | Green |
1 | OUTPUT channel 1 | Green |
2 | OUTPUT channel 2 | Green |
3 | OUTPUT channel 3 | Green |
4 | OUTPUT channel 4 | Green |
5 | OUTPUT channel 5 | Green |
6 | OUTPUT channel 6 | Green |
7 | OUTPUT channel 7 | Green |
LED Channel Status
Status | LED | Indication |
Normal operation | No output channel off
Output channel green |
No output
Output |
Field power error | All channel repeat the green and off | Field power is unconnected |
Data Value / Voltage
Voltage range: 0 – 10 VDC
Voltage | 0.0 V | 2.5 V | 5.0 V | 10.0 V |
Data (Hex) | H0000 | H1FFF | H3FFF | H7FFF |
Mapping Data From the Image Table
Output image value
Bit no. | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
Byte 0 | Analog output Ch 0 low byte | |||||||
Byte 1 | Analog output Ch 0 high byte | |||||||
Byte 2 | Analog output Ch 1 low byte | |||||||
Byte 3 | Analog output Ch 1 high byte | |||||||
Byte 4 | Analog output Ch 2 low byte | |||||||
Byte 5 | Analog output Ch 2 high byte | |||||||
Byte 6 | Analog output Ch 3 low byte | |||||||
Byte 7 | Analog output Ch 3 high byte | |||||||
Byte 8 | Analog output Ch 4 low byte | |||||||
Byte 9 | Analog output Ch 4 high byte | |||||||
Byte 10 | Analog output Ch 5 low byte | |||||||
Byte 11 | Analog output Ch 5 high byte | |||||||
Byte 12 | Analog output Ch 6 low byte | |||||||
Byte 13 | Analog output Ch 6 high byte | |||||||
Byte 14 | Analog output Ch 7 low byte | |||||||
Byte 15 | Analog output Ch 7 high byte |
Output module data – 16 byte output data
Analog output Ch 0 |
Analog output Ch 1 |
Analog output Ch 2 |
Analog output Ch 3 |
Analog output Ch 4 |
Analog output Ch 5 |
Analog output Ch 6 |
Analog output Ch 7 |
Parameter Data
Valid parameter length: 4 bytes
Bit no. | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
Byte 0 | Fault action for channel 3 | Fault action for channel 2 | Fault action for channel 1 | Fault action for channel 0 | ||||
00: Fault value / 01: Hold last state / 10: Low limit / 11: High limit | ||||||||
Byte 1 | Fault action for channel 7 | Fault action for channel 6 | Fault action for channel 5 | Fault action for channel 4 | ||||
Byte 2 | Fault value low byte | |||||||
Byte 3 | Fault value high byte |
Hardware Setup
CAUTION
- Always read this chapter before installing the module!
- Hot surface! The surface of the housing can become hot during operation. If the device is used in high ambient temperatures, always let the device cool down before touching it.
- Working on energized devices can damage the equipment! Always turn off the power supply before working on the device.
Space Requirements
The following drawings show the space requirements when installing the G-series modules. The spacing creates space for ventilation and prevents conducted electromagnetic interference from influencing the operation. The installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion.
CAUTION
NOT following the space requirements may result in damaging the product.
Mount Module to DIN Rail
The following chapters describe how to mount the module to the DIN rail.
CAUTION
The module must be fixed to the DIN rail with the locking levers.
Mount GL-9XXX or GT-XXXX Module
The following instructions apply to these module types:
- GL-9XXX
- GT-1XXX
- GT-2XXX
- GT-3XXX
- GT-4XXX
- GT-5XXX
- GT-7XXX
GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module.
Mount GN-9XXX Module
To mount or dismount a network adapter or programmable IO module with the product nameGN-9XXX, for example GN-9251 or GN-9371, see the following instructions:
Mount Removable Terminal Block
To mount or dismount a removable terminal block (RTB), see the instructions below.
Connect Cables to Removable Terminal Block
To connect/disconnect cables to/from the removable terminal block (RTB), see the instructions below.
WARNING
Always use the recommended supply voltage and frequency to prevent damage to the equipment and ensure optimal performance.
Field Power and Data Pins
Communication between the G-series network adapter and the expansion module, as well as system / field power supply of the bus modules is carried out via the internal bus. It is comprised of 2 Field Power Pins and 6 Data Pins.
WARNING
Do not touch the data and field power pins! Touching can result in soiling and damage by ESD noise.
Pin no. | Name | Description |
P1 | System VCC | System supply voltage (5 VDC) |
P2 | System GND | System ground |
P3 | Token output | Token output port of processor module |
P4 | Serial output | Transmitter output port of processor module |
P5 | Serial input | Receiver input port of processor module |
P6 | Reserved | Reserved for bypass token |
P7 | Field GND | Field ground |
P8 | Field VCC | Field supply voltage (24 VDC) |