Cooling Performance
Item | Unit | Value | Notes |
Rated Cooling Standard Capacity | kW | 25.0 (5.3~28.0) | |
Rated Cooling Standard Energy Efficiency Ratio | 2.38/2.38 | (50/60Hz) | |
Intermediate Cooling Standard Capacity | kW | 11.3 | |
Intermediate Cooling Medium Temperature Capacity | kW | 11.6 | (Note 1) |
Minimum Cooling Medium Temperature Capacity | kW | 6.3 |
Heating Performance
Item | Unit | Value | Notes |
Rated Heating Standard Capacity | kW | 28.0 (4.6~35.0) | |
Rated Heating Standard Energy Efficiency Ratio | 3.31/3.31 | ||
Intermediate Heating Standard Capacity | kW | 12.6 | |
Minimum Heating Standard Capacity | kW | 7.0 | |
Maximum Heating Low Temperature Capacity | kW | - | (Note 1) |
Annual Performance
Item | Unit | Value | Notes |
APF 2015 (JIS B 8616:2015) | APF | 22.2 | |
APF (JIS B 8616:2006) | APF | 4.6/4.6 | |
Cooling/Heating Average Energy Efficiency Ratio | 4.3/4.3 |
Electrical Characteristics
Item | Unit | Value | Notes |
Power Supply | 3-Phase 200V 50/60Hz | (Note 2) | |
Compressor Motor Rated Output | kW | 14.1 | Hermetically sealed |
Air Heat Exchanger | Finned tube | ||
Refrigerant Control | Electronic expansion valve |
Fan
Item | Unit | Value | Notes |
Outdoor Fan Motor Rated Output | kW | 0.200+0.200 | |
Standard Airflow | m³/min | 20.0 / 18.3 / 16.7 / 15.0 / 13.3 | High+/High/Low+/Low |
Fan Motor Rated Output | kW | 0.250 | |
External Static Pressure Setting Range | Pa | 50-75-100-125-150-175-200 | (Note 7) |
Airflow Limit (Lower) | m³/min | 11.3 | |
Airflow Limit (Upper) | m³/min | 24.0 |
Other Specifications
Item | Unit | Value | Notes |
Air Filter | Not included as standard. (Note 8) | ||
Drain Pipe Diameter (Nominal) | 25 (PVC pipe) | ||
Rated Sound Power Level (Cooling) | dB(A) | 60/57/55/53/51 | (Note 9) |
Rated Sound Power Level (Heating) | dB(A) | 38/36/34/32/31 | (Note 9) |
Sound Pressure Level (Cooling) | dB(A) | - | |
Sound Pressure Level (Heating) | dB(A) | - | |
IP Code | IPX4 | ||
Rated Refrigeration Tons | 4.39 | ||
Design Pressure (High Pressure Side) | MPa | 4.15 | |
Design Pressure (Low Pressure Side) | MPa | 2.21 | |
Refrigerant Shipping Charge | kg | R32 5.20 | |
Maximum Piping Length without Refrigerant Addition | m | 30 | |
Refrigerant Addition Amount | g/m | Main piping: 80, Branch piping: 40 | |
Maximum Branch Piping Length | m | 20 | |
Maximum Height Difference of Branch Piping | m | 6 | |
Maximum Height Difference (Outdoor Unit Above) | m | 30 | |
Maximum Height Difference (Outdoor Unit Below) | m | 30 |
Outdoor Unit Dimensions and Mass
Item | Unit | Value | Notes |
Model Name | ROA-RP2804HS | ||
Appearance | Silky Shade (Munsell 1Y8.5/0.5) | ||
Height | mm | 1,010 | |
Width | mm | 1,550 | |
Depth | mm | 370 | |
Total Mass | kg | 74 | |
Air Heat Exchanger | Finned tube | ||
Soundproof Insulation Material | Expanded polystyrene, Polyethylene foam | ||
Fan | Sirocco fan |
Piping Specifications
Item | Unit | Value | Notes |
Refrigerant Piping (Gas Side) | mm | 25.4 | Outdoor unit to 1st branch duct |
Refrigerant Piping (Liquid Side) | mm | 12.7 | Outdoor unit to 1st branch duct |
Refrigerant Piping (Gas Side) | mm | 15.9 | 1st branch duct to 2nd branch duct |
Refrigerant Piping (Liquid Side) | mm | 9.5 | 1st branch duct to 2nd branch duct |
Refrigerant Piping (Gas Side) | mm | 15.9 | 2nd branch duct to indoor unit |
Refrigerant Piping (Liquid Side) | mm | 9.5 | 2nd branch duct to indoor unit |
Electrical Connections
Item | Unit | Value | Notes |
High Pressure Switch | MPa | Cut-in: 4.15 | |
Low Pressure Switch | MPa | Cut-in: 3.20 | |
Protective Devices | Discharge temperature sensor, Overcurrent sensor, Compressor thermo | ||
Case Heater | W | 181.5 | |
Leakage Breaker | 50A, 30mA, 0.1sec or less | (Note 11) | |
Main Switch Capacity | A | 60 | |
Fuse Capacity | A | 50 | |
Circuit Breaker | A | 50 | |
Power Wiring | Wire size | Single wire 1.6mm², Stranded wire 3.5mm² | For up to 75m |
Power Wiring | Wire size | Single wire 2.0mm², Stranded wire 5.5mm² | For up to 120m |
Power Wiring | Wire size | Stranded wire 8.0mm², Stranded wire 14.0mm², Stranded wire 22.0mm², Stranded wire 38.0mm² | Separate cable required |
Remote Control Wiring | Wire size | Single wire 1.6mm² x 3 | For up to 120m |
Remote Control Wiring | Wire size | Stranded wire 3.5mm² x 2 | For up to 120m |
Remote Control Wiring | Wire size | Stranded wire 3.5mm² x 1 | For indoor unit A only connection |
Remote Control Wiring (Power) | Single wire 1.6mm² x 2 | (Note 12) | |
Remote Control Wiring (Signal) | Stranded wire 0.5mm² x 2 | (Up to 500m) | |
Remote Control Model | RBC-AMSU52 | (Optional accessory) |
Notes
- Cooling and heating performance and electrical characteristics are based on temperature conditions and standard piping (piping equivalent length 7.5m (5m for P40~P63 models), 0m head) according to JIS B 8616:2015. Values in < > indicate the capacity range.
- Power supply voltage should not fluctuate by more than ±10%.
- When using four indoor units, the values shown are per indoor unit.
- Remote control switches are optional accessories. Refer to the 'Remote Control Outline Drawing' for remote control wiring length.
- The Annual Performance Factor (APF) used for the "Judgment Standards for Energy Saving for Air Conditioner Performance" (commonly known as the Energy Saving Law Standards) by the Ministry of Economy, Trade and Industry Public Notice No. 213 is based on "APF (JIS B 8616:2006)".
- Rated airflow is for "High+" setting.
- External static pressure must be adjusted on-site if changed.
- Air filters are not included as standard. Prepare filters on-site or use optional filter chambers, antibacterial high-performance filters, etc.
- Rated sound power level is based on JIS B 8616:2015.
- Sound pressure level is based on JIS B 8616:2006.
- If the leakage breaker is for ground fault protection only, install a main switch + fuse or a circuit breaker. Use a harmonic-aware leakage breaker.
- Depending on optional accessories, the external dimensions, appearance, mass, sound level, and performance characteristics of the air conditioner may change.
Toshiba Package Air Conditioner Specification Sheet
Diagram Number: T2525074
Model Name: GDSF28014MUB
Version: 01
Manufacturer: Nihon Carrier Corporation