Product Overview
This document provides technical specifications, dimensions, and wiring diagrams for the Toshiba GCSB22414MUB package air conditioner system. The system includes an outdoor unit (ROA-RP2244HS), indoor unit (AIC-GP1121H), and associated components like branch pipes (RBC-TWP102) and remote controllers (RBC-AMSU52).
The system is an air-cooled inverter heat pump type, designed for ceiling suspension, offering both cooling and heating functionalities.
Technical Specifications (Outdoor Unit: ROA-RP2244HS)
Feature | Specification | Unit | Value (Cooling/Heating) |
---|---|---|---|
Model Name | ROA-RP2244HS | ||
Rated Cooling Capacity (Standard) | 定格冷房標準能力 | kW | 20.0 (5.3~22.4) |
EER (Standard Cooling) | 定格冷房標準エネルギー消費効率 | 3.28/3.28 | |
Rated Heating Capacity (Standard) | 定格暖房標準能力 | kW | 22.4 (4.6~28.0) |
COP (Standard Heating) | 定格暖房標準エネルギー消費効率 | 3.92/3.92 | |
APF (JIS B 8616:2015) | 通年エネルギー消費効率 | 5.8/5.8 | |
Power Supply | 電 源 | 3-Phase 200V 50/60Hz | |
Compressor Type | 圧縮機 | Fully Enclosed | |
Refrigerant Control | 冷媒制御 | Electronic Expansion Valve | |
Rated Sound Power Level (Cooling) | 定格騒音(音響パワーレベル) (冷) | dB | 76 |
Sound Pressure Level (Cooling) | 運転音(音圧レベル) | dB | 58 |
Rated Sound Power Level (Heating) | 定格騒音(音響パワーレベル) (暖) | dB | 77 |
Sound Pressure Level (Heating) | 運転音(音圧レベル) | dB | 61 |
IP Code | IPコード | IPX4 | |
Design Pressure (High Side) | 設計圧力高圧部 | MPa | 4.15 |
Design Pressure (Low Side) | 設計圧力低圧部 | MPa | 2.21 |
Refrigerant | 冷媒・出荷時封入量 | kg | R32 (5.20) |
Note: Specifications are based on JIS B 8616:2015 standards under specified conditions.
Technical Specifications (Indoor Unit: AIC-GP1121H)
Feature | Specification | Unit | Value (Fan Speed: Rapid/High+/High/Low+/Low) |
---|---|---|---|
Model Name | AIC-GP1121H | ||
Airflow (Standard) | 標準風量 | m³/min | 31.0 / 23.7 / 22.5 / 18.0 / 17.0 |
Noise (Sound Power Level) | 定格騒音(音響パワーレベル) | dB(A) | 59/54/53/48/47 |
Noise (Sound Pressure Level) | 運転音(音圧レベル) | dB(A) | 44/39/38/33/32 |
Drain Pipe Diameter | ドレン径(呼び径) | mm | 20 (PVC Pipe) |
Dimensions and External Views
Outdoor Unit (ROA-RP2244HS)
Overall Dimensions:
- Width: 1,010 mm
- Height: 1,550 mm
- Depth: 370 mm
- Mass: 141 kg
Key external features include air intake grills, fan outlets, refrigerant pipe connection ports (liquid: 9.5mm, gas: 25.4mm for P224), power supply entry, and drain holes.
Diagrams show front, side, and top views with specific port locations and mounting hole details.
Indoor Unit (AIC-GP1121H)
Overall Dimensions:
- Width: 1,586 mm
- Height: 235 mm
- Depth: 690 mm
- Mass: 38 kg
Key external features include air intake grills, air outlet louvers, refrigerant pipe connection ports (liquid: 9.5mm, gas: 15.9mm for P224), drain connection, and knock-out holes for electrical wiring and piping.
Diagrams illustrate the unit's dimensions, air inlet/outlet positions, and various connection points for piping and wiring.
Piping Specifications
Main Piping (Outdoor Unit to Branch Pipe):
- Liquid Line: Ø9.5 mm
- Gas Line: Ø25.4 mm (for P224 model)
Branch Piping (Branch Pipe to Indoor Units):
- Liquid Line: Ø9.5 mm
- Gas Line: Ø15.9 mm (for P224 model)
Maximum Piping Length: 100 meters
Maximum Height Difference: 30 meters (Outdoor unit above or below indoor unit)
Branch Pipe Length Difference: Maximum 10 meters
Diagrams on page 8 detail the dimensions of the branch pipe (RBC-TWP102) for different model capacities (P224, P280).
Wiring Diagrams
The document includes several wiring diagrams illustrating the electrical connections for the system:
- External Wiring Diagram (Page 2): Shows the connections between the outdoor unit, indoor units (twin type), and the wired remote controller. It indicates power supply, signal lines, and grounding points.
- Outdoor Unit Internal Wiring Diagram (Page 4): Details the internal electrical components and their connections within the outdoor unit, including control boards, compressor, fan motors, sensors, and various protective devices (fuses, switches).
- Indoor Unit Wiring Diagram (Page 6): Illustrates the internal wiring of the indoor unit, showing connections to the control board, fan motor, sensors, and optional components like drain pumps or air purification electrodes. It also shows connections for wired and wireless remote controllers, and central control systems.
These diagrams are crucial for installation and maintenance, showing component identification (e.g., CN for connector, F for fuse, M for motor) and wire routing.
Remote Controller (RBC-AMSU52)
The system utilizes a wired remote controller (Model: RBC-AMSU52, "Energy Saving Neo Remote Controller"). The document provides installation instructions and dimensions for mounting the controller on a wall.
Key installation notes include:
- Adherence to specific mounting dimensions and clearances.
- Use of standard switch boxes for flush mounting.
- Proper routing of remote control wiring, avoiding interference with AC power lines.
- Maximum wiring lengths for single and multiple remote controller setups are specified (up to 500m for certain configurations).
Diagrams show mounting hole patterns, dimensions, and wiring connection examples.
Electrical Specifications
Power Supply: Three-phase 200V, 50/60Hz.
Power Consumption (Cooling):
- Standard: 6.10/6.10 kW
- Intermediate: 1.67/1.67 kW
Power Consumption (Heating):
- Standard: 5.72/5.72 kW
- Intermediate: 1.71/1.71 kW
Starting Current: Not specified.
Circuit Protection:
- Leakage Circuit Breaker: 40A, 30mA, 0.1 sec or less.
- Main Switch/Fuse: 60A
- Circuit Breaker: 40A
Wiring Requirements:
- Power wiring: Stranded wire 3.5mm² to 38.0mm² depending on length (up to 120m for 3.5mm²).
- Signal wiring (Indoor to Outdoor): Stranded wire 0.5mm² x 2.
- Remote control wiring: VCTF 0.5-2.0mm² x 2 (up to 500m).