Toshiba Package Air Conditioner Specifications
Model: GBSB28014MUB
Indoor Unit Model: AID-GP1401BH x2
Outdoor Unit Model: ROA-RP2804HS
Branching Pipe Model: RBC-TWP102
Type: Ceiling Embedded Inverter Heat Pump Type, Simultaneous Twin
Cooling Performance
Item | Unit | Standard Cooling Capacity | Cooling Capacity Range |
---|---|---|---|
Standard Cooling Capacity | kW | 25.0 | <5.3~28.0> |
Standard Cooling Energy Efficiency | 2.38/2.38 | ||
Intermediate Cooling Standard Capacity | kW | 11.3 | |
Intermediate Cooling Medium Temperature Capacity (Note 1) | kW | 11.6 | |
Minimum Cooling Medium Temperature Capacity | kW | 6.3 |
Heating Performance
Item | Unit | Standard Heating Capacity | Heating Capacity Range |
---|---|---|---|
Standard Heating Capacity | kW | 28.0 | <4.6~31.5> |
Standard Heating Energy Efficiency | 3.31/3.31 | ||
Intermediate Heating Standard Capacity | kW | 12.6 | |
Minimum Heating Standard Capacity | kW | 7.0 | |
Maximum Heating Low Temperature Capacity (Note 1) | kW | 22.2 |
General Specifications
Item | Unit | Value |
---|---|---|
Annual Performance Factor (APF2015) (JIS B 8616:2015) | (Cooling) | 4.6/4.6 |
(Heating) | 4.3/4.3 | |
Annual Performance Factor (APF) (JIS B 8616:2006) | 2.85/2.85 | |
Power Supply | 3-Phase 200V 50/60Hz | |
Compressor Motor Rated Output | kW | 7.16 |
Compressor Type | Fully Sealed | |
Refrigerant Control | Electronic Expansion Valve | |
Fan Motor Output | kW | 0.200+0.200 |
High Pressure Switch | MPa | Operating: 4.15, Reset: 3.20 |
Low Pressure Switch | MPa | |
Protection Devices | Compressor Thermistor, Overcurrent Sensor, Discharge Temperature Sensor | |
Case Heater | W | 181.5 |
Rated Noise (Sound Power Level) (Note 8) | (Cooling) dB | 78 |
(Heating) dB | 80 | |
Operating Noise (Sound Pressure Level) (Note 9) | (Cooling) dB(A) | 61 |
(Heating) dB(A) | 63 | |
IP Code | IPX4 | |
Rated Refrigeration Tonnage | 4.39 | |
Efficiency (Note 1) | (Cooling) % | 95/95 |
(Heating) % | 95/95 | |
High Pressure Side Design Pressure | MPa | 4.15 |
Low Pressure Side Design Pressure | MPa | 2.21 |
Refrigerant Shipping Charge | kg | R32: 5.20 |
Indoor Unit Specifications (AID-GP1401BH)
Item | Unit | Value |
---|---|---|
Dimensions (H x W x D) | mm | 275 x 1,400 x 925 |
Weight | kg | 141 |
Air Heat Exchanger | Finned Tube | |
Fan Motor Output | kW | 0.250 |
Fan Speed Settings | Urgent/Strong+/Strong/Weak+/Weak | |
Airflow Rate (Standard) | m³/min | 35.0 / 32.0 / 29.0 / 26.5 / 25.0 |
External Static Pressure Setting Range (Note 7) | Pa | 20-30-40-50-65-80-100 |
Fan Airflow Limit (Lower) | m³/min | 21.0 |
Fan Airflow Limit (Upper) | m³/min | 39.6 |
Rated Noise (Sound Power Level) (Note 8) | dB(A) | 64/62/60/57/55 |
Operating Noise (Sound Pressure Level) (Note 9) | dB(A) | 49/47/45/42/40 |
Drain Pipe Diameter (Nominal) | 25 (PVC Pipe) | |
Air Filter | Included with indoor unit |
Refrigerant Piping
Item | Unit | Outdoor Unit to Branching Pipe | Branching Pipe to Indoor Unit |
---|---|---|---|
Pipe Diameter (Gas Side) | mm | 25.4 | 15.9 |
Pipe Diameter (Liquid Side) | mm | 12.7 | 9.5 |
Maximum Actual Length | m | 80 | 20 |
Maximum Height Difference | m | 30 (Outdoor unit above), 30 (Outdoor unit below) | 10 |
Electrical Specifications
Item | Unit | Cooling | Heating |
---|---|---|---|
Power Consumption (Standard) | kW | 10.5 / 10.5 | 8.46 / 8.46 |
Power Consumption (Intermediate) | kW | 2.57 / 2.57 | 2.51 / 2.51 |
Power Consumption (Intermediate Medium Temp.) | kW | 2.30 / 2.30 | 1.47 / 1.47 |
Power Consumption (Minimum Cooling Medium Temp.) | kW | 0.859 / 0.859 | 10.2 / 10.2 |
Operating Current | A | 31.9 / 31.9 | 25.7 / 25.7 |
Operating Current (Max) | A | 38.7 / 38.7 | |
Starting Current | A | - | - |
Electrical Wiring
Item | Specification | Length |
---|---|---|
Power Supply Wiring (Outdoor to Indoor) | Solid wire 1.6mm² x 3 core | 75m or less |
Stranded wire 3.5mm² x 2 core | 120m or less | |
Indoor Unit to Indoor Unit (Power) | Solid wire 1.6mm² x 2 core | |
Indoor Unit to Indoor Unit (Signal) | Stranded wire 0.5mm² x 2 core | |
Remote Control Cord | VCTF 0.5-2.0mm² etc. | (Up to 500m) |
Other
Item | Specification |
---|---|
Leakage Circuit Breaker (Note 10) | 50A, 30mA, 0.1 sec or less |
Main Switch Fuse Capacity | 60A |
Circuit Breaker Fuse Capacity | 50A |
Remote Controller | RBC-AMSU52 (Sold Separately) (Note 11) |
Green Purchasing Law Compliant |
Notes
- (Note 1) Cooling and heating performance and electrical characteristics are based on JIS B 8616:2015 temperature conditions and standard piping (piping equivalent length 7.5m (5m for P40~P63 models), 0m height difference). Values in <> indicate the capacity range.
- (Note 2) Power supply voltage should not fluctuate by more than ±10%.
- (Note 3) When two indoor units are used, the values shown are per indoor unit.
- (Note 4) Remote control switches are sold separately. Refer to the "Remote Controller Outline Drawing" for remote control cord wiring length.
- (Note 5) The Annual Performance Factor (APF) (JIS B 8616:2006) is applied for the Annual Performance Factor in the judgment standards for manufacturers etc. for improving air conditioner performance (commonly known as the Energy Saving Law standard value) as per Ministry of Economy, Trade and Industry Notification No. 213.
- (Note 6) Rated airflow is for "Urgent" setting.
- (Note 7) External static pressure must be set on site if changed.
- (Note 8) Rated noise (sound power level) is based on JIS B 8616:2015.
- (Note 9) Operating noise (sound pressure level) is based on JIS B 8616:2006.
- (Note 10) If the leakage circuit breaker is for ground fault protection only, install a main switch with a fuse or a circuit breaker. Use a high-harmonic compatible leakage circuit breaker.
- (Note 11) Some separately sold accessories may change the external dimensions, appearance, weight, operating noise, or performance characteristics of the air conditioner unit.