Toshiba Package Air Conditioner Specifications
Model: GCSC22414MUBZG
General Information
Set Name | GCSC22414MUBZG |
Specifications (Indoor Unit) | AIC-GP801H |
(Outdoor Unit) | ROA-RP2244HSZG |
(Branch Pipe) | RBC-TRP100 |
Type | Ceiling Suspended Inverter Simultaneous Triple |
Product Name | Toshiba Package Air Conditioner (Air Cooled Inverter Heat Pump Type Ceiling Suspended) |
Green Purchase Law Compliance | Yes |
Cooling Performance
Item | Unit | Standard Cooling Capacity | Value |
---|---|---|---|
Rated Cooling Capacity | kW | 20.0 (5.3~22.4) | - |
Sensible Heat Ratio | - | 0.78 | - |
Rated Cooling Energy Efficiency | - | 3.28/3.28 | - |
Intermediate Cooling Capacity | kW | 9.0 | - |
Intermediate Cooling Capacity (Mid-Temp) | kW | 9.5 | - |
Minimum Cooling Capacity (Mid-Temp) | kW | 5.6 | - |
Heating Performance
Item | Unit | Standard Heating Capacity | Value |
---|---|---|---|
Rated Heating Capacity | kW | 22.4 (4.6~28.0) | - |
Rated Heating Energy Efficiency | - | 3.92/3.92 | - |
Intermediate Heating Capacity | kW | 10.1 | - |
Minimum Heating Capacity | kW | 5.7 | - |
Maximum Heating Capacity (Low-Temp) | kW | 20.5 | - |
Energy Efficiency
Item | Unit | Value (JIS B 8616:2015) | Value (JIS B 8616:2006) |
---|---|---|---|
Annual Performance Factor (APF) | APF | 5.8/5.8 | 5.2/5.2 |
Cooling/Heating Average Energy Efficiency | - | 3.60/3.60 | - |
Electrical Characteristics
Item | Unit | Cooling Standard | Cooling Intermediate | Heating Standard | Heating Intermediate |
---|---|---|---|---|---|
Power Consumption | kW | 6.10/6.10 | 1.67/1.67 | 5.72/5.72 | 1.71/1.71 |
Operating Current | A | 18.7/18.7 | 17.6/17.6 | - | - |
Maximum Current | A | 28.1/28.1 | - | - | - |
Starting Current | A | - | - | - | - |
Compressor and Fan
Item | Unit | Value |
---|---|---|
Compressor Type | - | Fully Enclosed |
Compressor Motor Rated Output | kW | 4.74 |
Air Heat Exchanger | - | Finned Tube |
Refrigerant Control | - | Electronic Expansion Valve |
Fan Type | - | Propeller Fan |
Standard Airflow (Indoor Unit) | m³/min | 23.5/17.3 / 16.7/13.5 /12.5 |
Fan Motor Output | kW | 0.094 |
Dimensions and Weight
Item | Unit | Outdoor Unit | Indoor Unit |
---|---|---|---|
Height | mm | 1,010 | - |
Width | mm | 1,550 | - |
Depth | mm | 370 | - |
Total Mass | kg | 141 | 235 |
Sound Levels
Item | Unit | Cooling (Sound Power Level) | Heating (Sound Power Level) | Cooling (Sound Pressure Level) | Heating (Sound Pressure Level) |
---|---|---|---|---|---|
Rated Sound Level | dB | 76 | 77 | 58 | 61 |
Refrigerant and Piping
Item | Unit | Value |
---|---|---|
Refrigerant Type | - | R32 |
Factory Charge | kg | 5.20 |
Maximum Piping Length (No Refrigerant Addition) | m | 30 |
Refrigerant Addition | g/m | Gas Pipe: 40, Liquid Pipe: 40 |
Maximum Piping Length (Outdoor Unit Above) | m | 30 |
Maximum Piping Length (Outdoor Unit Below) | m | 30 |
Maximum Branch Pipe Length | m | 20 |
Maximum Difference in Branch Pipe Length | m | 10 |
Electrical Connections and Safety
Item | Unit | Value |
---|---|---|
Leakage Breaker | - | 40A, 30mA, 0.1sec or less |
Main Switch Capacity | A | 60 |
Fuse | A | 40 |
Power Wiring Length (Max) | m | 75m or less (Power: Single wire 1.6mm x 3, Signal: Stranded wire 0.5mm² x 2) |
Inter-unit Wiring Length (Max) | m | 120m or less (Power: Stranded wire 3.5mm² x 2, Signal: Stranded wire 3.5mm² x 1) |
Accessories
Item | Description |
---|---|
Remote Controller | RBC-AMSU52 (Sold Separately) |
Remote Control Cord | (Up to 500m) VCTF0.5-2.0mm² etc. |
Notes
- (Note 1) Cooling/heating performance and electrical characteristics are based on JIS B 8616:2015 temperature conditions and standard piping (equivalent piping length 7.5m for P40-P63 models, 5m; head difference 0m). Values in <> indicate the capacity range.
- (Note 2) Power voltage should not deviate by more than ±10%.
- (Note 3) This applies when three indoor units are used. The values shown are per indoor unit.
- (Note 4) Remote control switch is a separate option. Refer to the 'Remote Controller Outline Drawing' for remote control cord wiring length.
- (Note 5) The Annual Performance Factor (APF) is based on the "Judgment Standards for Manufacturers' Performance Improvement for Air Conditioners" (commonly known as the Energy Saving Law Standards) as per Ministry of Economy, Trade and Industry Notification No. 213, where APF (JIS B 8616:2006) applies.
- (Note 6) Rated sound level (sound power level) is based on JIS B 8616:2015.
- (Note 7) Operating sound level (sound pressure level) is based on JIS B 8616:2006.
- (Note 8) Rated airflow is for 'High' speed.
- (Note 9) If the leakage breaker is for ground fault protection only, install a main switch + fuse or a circuit breaker. Use a high-harmonic compatible leakage breaker.
- (Note 10) Depending on the optional parts, the external dimensions, appearance, mass, operating sound, and performance characteristics of the air conditioner may change.