Toshiba Package Air Conditioner Specification Sheet
Model Name: GCSA22414MUBZG
Indoor Unit Model: AIC-GP2241H
Outdoor Unit Model: ROA-RP2244HSZG
Type: Air-Cooled Inverter Heat Pump Ceiling-Suspended Type
Green Purchase Law Compliant
Outdoor Unit Specifications
Item | Specification | Unit | Details |
---|---|---|---|
Model Name | ROA-RP2244HSZG | ||
Outdoor Unit Appearance | Silky Shade (Munsell 1Y8.5/0.5) | ||
Dimensions (H x W x D) | 1,550 x 1,010 x 370 | mm | |
Total Mass | 141 | kg | |
Compressor Type | Fully Sealed | ||
Number of Poles | 4 | ||
Fan Motor | Propeller Fan | ||
Fan Motor Rated Output | 0.200+0.200 | kW | |
Power Supply | 3-Phase 200V 50/60Hz | ||
High Pressure Switch | Operate: 4.15, Reset: 3.20 | MPa | |
Low Pressure Switch | MPa | ||
Protection Devices | Discharge Temperature Sensor, Overcurrent Sensor, Compressor Thermistor, Case Heater | ||
Case Heater | W | ||
Refrigerant Control | Electronic Expansion Valve | ||
Refrigerant Additional Charge (Max Length) | 30 | m | |
Refrigerant Additional Charge Amount | 40 | ||
Refrigerant Type | R32 | kg | 5.20 |
Piping Specifications (Gas/Liquid) | 25.4 / 9.5 | mm | |
Maximum Piping Length | 100 | m | |
Maximum Elevation Difference | 30 (Outdoor unit above) / 30 (Outdoor unit below) | m | |
Leakage Breaker | 40A, 30mA 0.1sec or less | ||
Main Switch Capacity | 60 | A | |
Fuse | 40 | A | |
Circuit Breaker | 40 | A | |
Power Wiring Length (Max) | 25/24, 43/42, 69/67 | m | (for 14.0mm², 22.0mm², 38.0mm² wire sizes) |
Communication Wiring | 75m or less (1.6mm x 3 wires) / 120m or less (3.5mm² x 2 wires) | ||
Remote Control Cord | Sold Separately (up to 500m) VCTF 0.5-2.0mm² etc. | RBC-AMSU52 |
Performance Data (Cooling)
Item | Specification | Unit | Details |
---|---|---|---|
Rated Cooling Capacity | 20.0 (4.6~22.4) | kW | |
Sensible Heat Ratio | 0.79 | ||
Rated Cooling Energy Efficiency | 3.15/2.86 | ||
Intermediate Cooling Capacity | 9.0 | kW | |
Intermediate Cooling Capacity (Low Temp) | 9.5 | kW | |
Minimum Cooling Capacity (Low Temp) | 5.6 | kW | |
Annual Performance Factor (APF 2015) | 4.3/4.0 | ||
Annual Performance Factor (APF 2006) | 4.3/3.8 | ||
Cooling/Heating Average Energy Efficiency | 3.24/2.99 | ||
Airflow Rate (Cooling) | 6.35/7.00 | m³/min | |
Power Consumption (Cooling) | 1.93/2.45 | kW | |
Power Consumption (Intermediate Cooling) | 1.78/1.95 | kW | |
Power Consumption (Minimum Cooling Low Temp) | 1.05/1.15 | kW | |
Operating Current (Cooling) | 19.5/21.5 | A | |
Operating Current (Max Cooling) | 28.2/28.9 | A | |
Cooling Capacity (Rated) | 94/94 | % | |
Starting Current | A | ||
Refrigerant Charge | 5.20 | kg |
Performance Data (Heating)
Item | Specification | Unit | Details |
---|---|---|---|
Rated Heating Capacity | 22.4 (4.6~28.0) | kW | |
Rated Heating Energy Efficiency | 3.32/3.11 | ||
Intermediate Heating Capacity | 10.1 | kW | |
Minimum Heating Capacity | 5.7 | kW | |
Maximum Heating Capacity (Low Temp) | 20.5 | kW | |
Airflow Rate (Heating) | 6.75/7.20 | kW | |
Power Consumption (Heating) | 2.31/2.50 | kW | |
Power Consumption (Minimum Heating) | 1.55/1.65 | kW | |
Power Consumption (Maximum Heating Low Temp) | 8.30/8.80 | kW | |
Operating Current (Heating) | 20.7/22.1 | A | |
Heating Capacity (Rated) | 94/94 | % |
Indoor Unit Specifications
Item | Specification | Unit | Details |
---|---|---|---|
Model Name | AIC-GP2241H | ||
Appearance | White (Munsell 0.7Y8.59/0.97), Galvanized steel plate, ABS | ||
Dimensions (H x W x D) | 320 x 1,800 x 800 | mm | |
Total Mass | 85 | kg | |
Air Heat Exchanger | Finned Tube | ||
Fan | Sirocco Fan | ||
Fan Motor | kW | 0.16+0.16 | |
Air Filter | Polyethylene Foam | ||
Noise Level (Sound Power Level) (Cooling) | 58.0 - 49.0 | dB(A) | (High-Low) |
Noise Level (Sound Power Level) (Heating) | 53-50 | dB(A) | (High-Low) |
Operating Noise (Sound Pressure Level) (Cooling) | 68-65 | dB(A) | (High-Low) |
Operating Noise (Sound Pressure Level) (Heating) | 53-50 | dB(A) | (High-Low) |
Drain Pipe Diameter | 20 (VP) | Attached to indoor unit | |
Remote Control Switch | Included |
Notes
- (1) Cooling and heating performance and electrical characteristics are based on temperature conditions and standard piping (equivalent pipe length 7.5m [5m for P40-P63 models], 0m elevation difference) according to JIS B 8616:2015. Values in <> indicate the performance range.
- (2) Power supply voltage should not fluctuate by more than ±10%.
- (3) Remote control switch is a separately sold part. Refer to the remote control external view diagram for remote control cord wiring length.
- (4) The Annual Performance Factor (APF) according to JIS B 8616:2006 is applied for the energy saving law standard value of the Annual Performance Factor for the judgment standards for manufacturers, etc. regarding the improvement of air conditioner performance, as stipulated in the Ministry of Economy, Trade and Industry Notification No. 213.
- (5) Rated noise (sound power level) is based on JIS B 8616:2015.
- (6) Operating noise (sound pressure level) is based on JIS B 8616:2006.
- (7) Rated airflow is for "High" speed.
- (8) If the leakage breaker is for ground fault protection only, install a main switch + fuse or a circuit breaker. Use a harmonic-compatible leakage breaker.
- (9) Depending on separately sold parts, the external dimensions, appearance, mass, and operating noise of the air conditioner may change.