Toshiba Package Air Conditioner Specification Sheet
Model Name: GCSC22414MUBZ
Indoor Unit Model: AIC-GP801H
Outdoor Unit Model: ROA-RP2244HSZ
Branching Pipe Model: RBC-TRP100
Type: Ceiling Suspended, Multi-Zone Inverter Heat Pump
Green Purchase Law Compliant
Cooling Performance
Specification | Value | Unit | Notes |
---|---|---|---|
Rated Cooling Standard Capacity | 20.0 (5.3~22.4) | kW | |
Sensible Heat Ratio | 0.78 | ||
Rated Cooling Standard Energy Efficiency | 3.28/3.28 | (50/60Hz) | |
Intermediate Cooling Standard Capacity | 9.0 | kW | |
Intermediate Cooling Mid-Temp Capacity | 9.5 | kW | (Note 1) |
Minimum Cooling Mid-Temp Capacity | 5.6 | kW |
Heating Performance
Specification | Value | Unit | Notes |
---|---|---|---|
Rated Heating Standard Capacity | 22.4 (4.6~28.0) | kW | |
Rated Heating Standard Energy Efficiency | 3.92/3.92 | ||
Intermediate Heating Standard Capacity | 10.1 | kW | |
Minimum Heating Standard Capacity | 5.7 | kW | |
Maximum Heating Low-Temp Capacity | 20.5 | kW | (Note 1) |
Overall Energy Efficiency
Specification | Value | Unit | Notes |
---|---|---|---|
APF 2015 (JIS B 8616:2015) | 5.8/5.8 | (Cooling/Heating) | |
APF (JIS B 8616:2006) | 5.2/5.2 | (Cooling/Heating) | |
Annual Energy Consumption Efficiency (Cooling/Heating Average) | 3.60/3.60 |
Outdoor Unit Specifications
Specification | Value | Unit | Notes |
---|---|---|---|
Model Name | ROA-RP2244HSZ | ||
Exterior Finish | Silky Shade (Munsell 1Y8.5/0.5) | ||
Dimensions (H x W x D) | 1,550 x 1,010 x 370 | mm | |
Total Mass | 141 | kg | |
Compressor Type | Hermetically Sealed | ||
Compressor Motor Rated Output | 4.74 | kW | |
Number of Poles | 4 | ||
Air Heat Exchanger | Finned Tube | ||
Refrigerant Control | Electronic Expansion Valve | ||
Fan Type | Propeller Fan | ||
Standard Airflow Rate (Cooling) | 152.5 | m³/min | |
Power Supply | 3-Phase 200V 50/60Hz | (Note 2) | |
Power Consumption (Cooling Standard) | 6.10/6.10 | kW | |
Power Consumption (Intermediate Cooling Standard) | 1.67/1.67 | kW | |
Power Consumption (Intermediate Cooling Mid-Temp) | 1.46/1.46 | kW | |
Power Consumption (Minimum Cooling Mid-Temp) | 0.680/0.680 | kW | |
Power Consumption (Heating Standard) | 5.72/5.72 | kW | |
Power Consumption (Intermediate Heating Standard) | 1.71/1.71 | kW | |
Power Consumption (Minimum Heating Standard) | 0.930/0.930 | kW | |
Power Consumption (Maximum Heating Low-Temp) | 9.15/9.15 | kW | |
Operating Current (Cooling) | 18.7/18.7 | A | |
Operating Current (Heating) | 17.6/17.6 | A | |
Operating Current (Max) | 28.1/28.1 | A | |
Power Factor (Cooling) | 94/94 | % | |
Power Factor (Heating) | 94/94 | % | |
Starting Current | - / - | A | |
Refrigerant Type and Charge | R32: 3.20 | kg | |
Maximum Piping Length (No Refrigerant Charge) | 30 | m | |
Refrigerant Charge per Unit Length (Piping) | 40 (Main) / 40 (Branch) | g/m | |
Maximum Piping Length (Outdoor to Branch) | 30 | m | |
Maximum Piping Length (Branch to Indoor) | 100 | m | |
Maximum Height Difference (Outdoor Unit Above) | 30 | m | |
Maximum Height Difference (Outdoor Unit Below) | 30 | m | |
Maximum Branch Piping Length | 20 | m | |
Maximum Branch Piping Length Difference | 10 | m | |
Leakage Circuit Breaker | 40A, 30mA, 0.1sec or less | (Note 9) | |
Main Switch Fuse Capacity | 60 | A | |
Fuse Capacity | 40 | A | |
Circuit Breaker Capacity | 40 | A | |
Power Wiring Conductor Size (Max) | Single wire 1.6mm² / Stranded wire 3.5mm² | ||
Power Wiring Length (Max) | 25/25 | m | (Single wire 1.6mm² / Stranded wire 2.0mm²) |
Connection Wiring (Max Length) | 44/44 | m | (Stranded wire 3.5mm²) |
Connection Wiring (Max Length) | 69/69 | m | (Stranded wire 5.5mm²) |
Connection Wiring (Max Length) | 119/119 | m | (Stranded wire 8.0mm²) |
Connection Wiring (Max Length) | 119/119 | m | (Stranded wire 14.0mm²) |
Connection Wiring (Max Length) | 119/119 | m | (Stranded wire 22.0mm²) |
Connection Wiring (Max Length) | 119/119 | m | (Stranded wire 38.0mm²) |
Outdoor-Indoor Unit Piping (Max Length) | 75m or less | (Single wire 1.6mm² x 3) | |
Outdoor-Indoor Unit Piping (Max Length) | 120m or less | (Stranded wire 3.5mm² x 2) | |
Indoor A-Indoor B Piping (Max Length) | (Stranded wire 3.5mm² x 1) | ||
Indoor B-Indoor C Piping (Max Length) | |||
Remote Control Cord | (Connects only to Indoor Unit A) | (Up to 500m) VCTF 0.5-2.0mm² etc. | |
Optional Accessories | Remote Controller: RBC-AMSU52 | (Note 10) |
Indoor Unit Specifications
Specification | Value | Unit | Notes |
---|---|---|---|
Model Name | AIC-GP801H | ||
Exterior Finish | Pure White (Munsell N9.1) | ||
Dimensions (H x W x D) | 235 x 1,270 x 690 | mm | |
Total Mass | 30 | kg | |
Air Heat Exchanger | Finned Tube | ||
Insulation Material | Foamed Polystyrene, Polyethylene Foam | ||
Fan Type | Sirocco Fan | ||
Airflow Rate (High/High+/Normal+/Normal/Low) | 23.5/17.3 / 16.7/13.5 /12.5 | m³/min | (Note 8) |
Sound Power Level (Cooling) | 56/53/51/46/44 | dB(A) | (Note 6) |
Sound Power Level (Heating) | 41/38/36/31/29 | dB(A) | (Note 7) |
Sound Pressure Level (Cooling) | 58 | dB | |
Sound Pressure Level (Heating) | 61 | dB | |
IP Code | IPX4 | ||
High Pressure Side Design Pressure | 4.15 | MPa | |
Low Pressure Side Design Pressure | 2.21 | MPa | |
Piping Diameter (Gas Side) | $25.4 | mm | |
Piping Diameter (Liquid Side) | $9.5 | mm | |
Drain Pipe Diameter (Nominal) | |||
Air Filter | Included with indoor unit | ||
Operation Adjustment Device | Remote Control Switch | (Note 4) |
Notes
- (Note 1) Cooling and heating performance, and electrical characteristics are based on JIS B 8616:2015 temperature conditions and standard piping (equivalent length 7.5m (5m for P40~P63 models), 0m height difference). Values in < > indicate the performance range.
- (Note 2) Power supply voltage should not deviate by more than ±10%.
- (Note 3) This applies when three identical indoor units are used. Values shown are per indoor unit.
- (Note 4) Remote control switch is an optional accessory. Refer to the 'Remote Controller Outline Drawing' for remote control wiring length.
- (Note 5) The Annual Energy Consumption Efficiency is determined by the "APF (JIS B 8616:2006)" value, in accordance with the Ministry of Economy, Trade and Industry Notification No. 213, "Criteria for Manufacturers etc. for Improving Air Conditioner Performance" (commonly known as the Energy Saving Law criteria).
- (Note 6) Rated sound power level is based on JIS B 8616:2015.
- (Note 7) Operating sound pressure level is based on JIS B 8616:2006.
- (Note 8) Rated airflow is for "High" fan speed.
- (Note 9) If the leakage circuit breaker is for ground fault protection only, install a main switch + fuse, or a circuit breaker. Use a harmonic-aware leakage circuit breaker.
- (Note 10) Some optional accessories may alter the external dimensions, appearance, mass, operating sound, or performance characteristics of the air conditioner.